4 www.na.heating.danfoss.com Toll Free: 1.866.375.4822 © Danfoss 10/2013
MECHANICAL RANGE ADJUSTMENT, cont’d
Clockwise-to-open
a. Insert the shaft adapter to the right as close as
possible to the raised stop.
b. Hold down the PUSH button and rotate the shaft
adapter to the left until it stops.
c. Release the PUSH button
d. If the shaft adapter is not resting against the
left raised stop, remove the adapter and insert it
against the left stop.
e. Place the position indicator to “0” on the outside
scale.
Counterclockwise-to-open
a. Insert the shaft adapter to the left as close as pos-
sible to the raised stop.
b. Hold down the PUSH button and rotate the shaft
adapter to the right until it stops
c. Release the PUSH button.
d. If the shaft adapter is not resting against the right
raised stop, remove the adapter and insert it
against the right stop.
e. Place the position indicator to “0” on the inside
scale.
4. Determine the angle of rotation for the valve’s rota-
tion. Subtract the angle of rotation from 90°.
5. Remove the shaft adapter and insert it with the posi-
tion indicator pointing to mark on the scale calculated
in the previous step
6. Attach the clip.
7. Manually rotate the valve stem to its ‘0’ position
8. Return the actuator to the stem extender and
tighten the shaft adapter to the extender.
WIRING
• All wiring must conform to NEC and local codes
and regulations
• Use earth ground isolating step down Class 2
transformers. Do not use auto transformers.
M
6 7
1
GRND
P1 P2 P3
0% 100%
1000
M
8 9
1
2
3-position Control
Modulating Control
Wiring Designations
Function Terminal Color
1 Supply 24VAC G RED
2Neutral G0BLACK
6Clockwise signal Y1 VIOLET
7 Counter-clock singal Y2 ORANGE
80-10VDC input Y GRAY
9
Output (0-10VDC) position
indication
UPINK
GND Ground GRN/YLLW
P1
Feedback potentiometer,
0-100% P
1
-P
2
aWHT/RED
P2
Feedback potentiometer,
common
bWHT/BLUE
P3
Feedback potentiometer,
0-100% P
2
-P
3
cWHT/PINK
• The maximum rating for a Class 2 step-down
transformer is 100VA. It is recommended that
no more than 10 actuators are powered by one
100VA transformer.
CAUTION
Do not parallel wire GIB actuators with any other type
of actuator.
Direction of Actuator Rotation
If the actuator turns counterclockwise to open, reverse
the 6 & 7 wires at the controller