Danfoss Termix One-B Operating instructions

Type
Operating instructions
InstallationGuide
TermixOne-Bwithcompleteinsulation
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotesgeneral............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
5.0Design.............................................................6
5.1Design...............................................................6
5.2Schematicdiagram................................................7
6.0Controls..........................................................8
6.1DHWtemperaturecontrol........................................8
6.2Maintenance........................................................9
7.0Troubleshooting..............................................10
7.1Troubleshootingingeneral......................................10
7.2TroubleshootingDHW............................................10
7.3Disposal.............................................................11
8.0Declaration......................................................14
8.1Declarationofconformity........................................14
DanfossDistrictEnergy
VI.IE.F2.02/LUK38003
DEN-GT
1
InstallationGuideTermixOne-Bwithcompleteinsulation
2.0Functionaldescription
Instantaneouswaterheaterwithheatexchangerand
thermostaticcontrol.Designedforwallmounting.
Application
TheTermixOneisaninstantaneouswaterheaterfeaturingsuperb
heatextractionandhighperformance.TheTermixOneissuitable
forats,single-familyhousesaswellasforsmallapartment
buildingswithupto10apartments.Thewaterheaterisavailablein
threesizes,eitherfor1apartment,for14apartmentsorfor5up
to10apartments.TheTermixOneisapplicablefordecentralized
heatingsystemsaswellasfordistrictheatingnetworkswith
summeroperationatlowtemperaturesorchangesindifferential
pressure.TheTermixOneheatexchangercoolsoutthedistrict
heatingwaterveryefciently,therebycreatingaverygood
operationeconomy.
Domestichotwater(DHW)
Thedomestichotwaterispreparedintheheatexchangerand
thetemperatureisregulatedwithathermostaticcontrolvalve.
Thepatentedsensoracceleratoracceleratestheclosingofthe
DanfossAVTBvalveandprotectstheheatexchangeragainst
overheatingandlimescaleformation.Thesensoracceleratorand
AVTBvalvealsoworksasabypasskeepingthehousesupplyline
warm.Thisshortensthewaitingperiodsduringsummerwhenthe
heatingsystemisinreducedoperation.Thesensoraccelerator
helpstoensureastablehotwatertemperaturebyvaryingloads,
owtemperaturesanddifferentialpressurewithouttheneedfor
readjustingthevalve.Thereisnoadditionalpressurelossonthe
secondarysideoftheDHWheatexchangerwithathermostatic
control.Thereforethistypeofregulationcanbeusedbylow
pressureontheinthecoldwatermains.
2
DEN-GT
VI.IE.F2.02/LUK38003
DanfossDistrictEnergy
InstallationGuideTermixOne-Bwithcompleteinsulation
3.0Safetynotes
3.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossDistrictEnergy
VI.IE.F2.02/LUK38003
DEN-GT
3
InstallationGuideTermixOne-Bwithcompleteinsulation
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connections:
1.Domesticcoldwater(DCW)
2.Domestichotwater(DHW)
3.Districtheating(DH)supply
4.Districtheating(DH)return
Connectionsizes:
DH:
G¾”(int.thread)
DCW+DHW:
G¾”(int.thread)
Dimensions(mm):
Type1+2withinsulation:
H435xW355xD195
Weight(approx.):1012kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4
DEN-GT
VI.IE.F2.02/LUK38003
DanfossDistrictEnergy
InstallationGuideTermixOne-Bwithcompleteinsulation
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
Keyholeformounting.
DanfossDistrictEnergy
VI.IE.F2.02/LUK38003
DEN-GT
5
InstallationGuideTermixOne-Bwithcompleteinsulation
5.0Design
5.1Design
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
B
Heatexchanger,DHW
O
Termixsensoraccelerator
7
Thermostaticcontroller,DHW
6
DEN-GT
VI.IE.F2.02/LUK38003
DanfossDistrictEnergy
InstallationGuideTermixOne-Bwithcompleteinsulation
5.2Schematicdiagram
DH
Supply
DHW
HWC
DH
Return
DCW
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
B
Heatexchanger,DHW
6
Thermostatic/non-returnvalve
7
Thermostaticvalve
21
Tobeorderedseparately
DHW:DomesticHotWater
DCW:
DomesticColdWater
HWC:
HotWaterCirculation
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
5.2.1Technicalparameters
Technicalparameters
Nominalpressure:
PN16
Max.DHsupplytemperature:
120°C
Min.DCWstaticpressure:
0.5bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:30bar
Soundlevel:55dB
DanfossDistrictEnergy
VI.IE.F2.02/LUK38003
DEN-GT
7
InstallationGuideTermixOne-Bwithcompleteinsulation
6.0Controls
6.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
6.1.1AVTBcontroller(20–60°)
Thetemperaturesettingisasfollows:
1=20°C
2=35°C
3=50°C
4=60°C
5=70°C
Thevaluesareintendedasaguide.
TheAVTBoperatesatitsbestatDHsupplytemperaturesofupto
90°C.
Thermostaticcontrol
DHWtemperatureisadjustedasfollows:
Toincreasetemperature,turnthehandleonthethermostatic
controllertoselectahighernumber.
Todecreasetemperature,turnthehandleonthethermostatic
controllertoselectalowernumber.
6.1.2Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
8
DEN-GT
VI.IE.F2.02/LUK38003
DanfossDistrictEnergy
InstallationGuideTermixOne-Bwithcompleteinsulation
6.1.3Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditionsand
themanufacturer’sinstructions.
6.1.4GTUPressureEqualizer
TheGTUPressureEqualizerabsorbstheexpansiononthe
secondarysideoftheTermixwaterheatersandcanbeusedasa
substitutetothesafetyvalve.
Furthermorethepressureequalizerabsorbsapossibleincreasein
pressure,soadischargeoutletisomitted.
TheGTUPressureEqualizermaynotbeappliedinsystemswithhot
watercirculation.
6.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
DanfossDistrictEnergy
VI.IE.F2.02/LUK38003
DEN-GT
9
InstallationGuideTermixOne-Bwithcompleteinsulation
7.0Troubleshooting
7.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheDHsupplypipeisclean,
thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetworkifindoubt,ask
theDHplantsupervisor,
pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
7.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivemotorizedvalve.Check(usemanualfunction)replace.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Checkset.
Scalingoftheplateheatexchanger.
Replacerinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
Thermostaticcontrolvalvedoesnotclose
TemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
10
DEN-GT
VI.IE.F2.02/LUK38003
DanfossDistrictEnergy
InstallationGuideTermixOne-Bwithcompleteinsulation
7.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
DanfossDistrictEnergy
VI.IE.F2.02/LUK38003
DEN-GT
11
InstallationGuideTermixOne-Bwithcompleteinsulation
12
DEN-GT
VI.IE.F2.02/LUK38003
DanfossDistrictEnergy
InstallationGuideTermixOne-Bwithcompleteinsulation
DanfossDistrictEnergy
VI.IE.F2.02/LUK38003
DEN-GT
13
InstallationGuideTermixOne-Bwithcompleteinsulation
8.0Declaration
8.1Declarationofconformity
8.1.1Category0withoutelectricalequipment
ECDeclarationofConformity
GeminaTermixA/S
MemberoftheDanfossGroup
Navervej15-17
DK-7451Sunds
Declaresonoursoleresponsibilitythatthebelowproducts:
SubstationsCategory0withoutelectricalequipment,
coveredbythisdeclarationareinconformitywiththefollowingdirectives,standardsandothernormative
documents,providedthattheyareusedaccordingtoourinstructions.
MachineryDirective2006/42/EC
DS/EN60204-1/A1:2009.Safetyofmachinery
Part1GeneralRequirements.
DS/EN12100:2011.SafetyofmachineryRisk
assessment.
Sunds2013.03.15
PlaceanddateofissueClausGjøderumMortensen
Quality&EnvironmentManager
14
DEN-GT
VI.IE.F2.02/LUK38003
DanfossDistrictEnergy
InstallationGuideTermixOne-Bwithcompleteinsulation
ProducedbyDanfossA/S©05/2013
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15

Danfoss Termix One-B Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI