www.pulsar.pl INTU
5
3. Connection configuration in the PowerSecurity program.
For further configuration, the PowerSecurity program is required. Download it from the following page:
http://www.pulsar.pl/pl/pliki/PowerSecurity.exe
The program is saved as an executable file therefore does not require installation in the system.
1) Run the PowerSecurity.exe program saved on the hard drive.
2)
From the menu bar choose: Power Supplies > New Power Supply. There will appear a window of
Connection Settings in which all settings are to be adjusted.
Fig. 4. The window of connection configuration.
PSU Description
Name
PSU’s name
The name that is to be assigned individually to each PSU.
Address
1;
Static address.
Refreshing Period
of View [ms]
100 ÷ 60 000ms;
Parameters refreshing time in the preview window.
Connection
Type
Modbus RTU
Port
Enter the number of the COM port – same as the one assigned in the Device
Manager.
Baud Rate
19 200 bauds
Parity
Even
Response Timeout
[ms]
100 ÷ 60 000ms;
Time of reply from the PSU.
Delay Between
Pools [ms]
Minimum break between subsequent transmissions.
Number of
retransmission
Number of retransmissions after which the program will report a connection failure.
3.After loading the connection configuration the window with a ”Preview” tab will open. In the top left-hand
corner there is an
icon which is to be clicked to make a connection with the PSU. As the connection has
been made, the window will display current parameters of the PSU. They will be automatically updated
according to the previosly set refreshing cycle.