Seeley BM1150 Owner's manual

Category
Mobile air conditioners
Type
Owner's manual
ILL1456-A
(English)(LCB,CPL,BM)
OWNER’SMANUAL
EvaporativeCooler
®
®
1
CPL LCBBMEvaporativeCooler
Introduction
WallControlFunctions
DrainValve&BleedSystem
Maintenance
ServiceChecklist
Troubleshooting
7
9
6
3
2
10
®
INTRODUCTION
CoolerModels
Exhaust
Opening
2.0m
2
LCB250 BM500 CPL450
CPL700
CPL850
CPL1100
BM750
BM900
BM1150
LCB350
LCB450
LCB550
2.5m
2
3.0m
2
4.0m
2
2
SEELEY INTERNATIONAL – OWNER’SMANUAL
CongratulationsonchoosinganewSeeley
Internationalcoolerforyourhome.
Yourcoolerisbuiltfromthehighestquality
materialsandengineeredtoprovidemanyyears
ofeconomical,troublefreecooling.
Pleasetakeafewminutestoreadthese
instructionssoyouhaveafullunderstandingof
howtooperateyourcooler. Yourinstallershould
demonstratethefeaturesandproceduressetout
intheseinstructions. Theinstallershouldalso
provideyouwithaModelandSerialnumber,
whichcanbefilledoutonthelastpage.
Keeptheseinstructionsinasafeplacefor
futurereference.
Thisapplianceisnotintendedforuseby
persons(includingchildren)withreduced
physical,sensoryormentalcapabilities,orlack
ofexperienceandknowledge,unlesstheyhave
beengivensupervisionorinstructionconcerning
useoftheappliancebyapersonresponsiblefor
theirsafety.
Childrenshouldbesupervisedtoensurethat
theydonotplaywiththeappliance.
Effectivecooling
Toprovideefficientcoolingorventilationthe
buildingmusthavesufficientexhaustopenings
tooutdoorsintheformofdoors,windowsor
othervents. Toassistaircirculation,open
windowsordoorsthatarefurthestfromthe
outletventineachroom.Ineveryroomthathas
anoutletvent,provideanexhaustopeningabout
2or2.5timestheventsizeoftheroom.Where
thedesignofthebuildingpreventsadequate
exhaust,considerationshouldbegiventothe
provisionofmechanicalextractionsuchasan
exhaustfan.
Totalminimumopeningsforthewholebuilding
aredemonstratedbythefollowingtable:
Pleasenotethatanaveragesizedooris1.5m
2
®
1
CPL LCBBMEvaporativeCooler
Introduction
WallControlFunctions
DrainValve&BleedSystem
Maintenance
ServiceChecklist
Troubleshooting
7
9
6
3
2
10
®
INTRODUCTION
CoolerModels
Exhaust
Opening
2.0m
2
LCB250 BM500 CPL450
CPL700
CPL850
CPL1100
BM750
BM900
BM1150
LCB350
LCB450
LCB550
2.5m
2
3.0m
2
4.0m
2
2
SEELEY INTERNATIONAL – OWNER’SMANUAL
CongratulationsonchoosinganewSeeley
Internationalcoolerforyourhome.
Yourcoolerisbuiltfromthehighestquality
materialsandengineeredtoprovidemanyyears
ofeconomical,troublefreecooling.
Pleasetakeafewminutestoreadthese
instructionssoyouhaveafullunderstandingof
howtooperateyourcooler. Yourinstallershould
demonstratethefeaturesandproceduressetout
intheseinstructions. Theinstallershouldalso
provideyouwithaModelandSerialnumber,
whichcanbefilledoutonthelastpage.
Keeptheseinstructionsinasafeplacefor
futurereference.
Thisapplianceisnotintendedforuseby
persons(includingchildren)withreduced
physical,sensoryormentalcapabilities,orlack
ofexperienceandknowledge,unlesstheyhave
beengivensupervisionorinstructionconcerning
useoftheappliancebyapersonresponsiblefor
theirsafety.
Childrenshouldbesupervisedtoensurethat
theydonotplaywiththeappliance.
Effectivecooling
Toprovideefficientcoolingorventilationthe
buildingmusthavesufficientexhaustopenings
tooutdoorsintheformofdoors,windowsor
othervents. Toassistaircirculation,open
windowsordoorsthatarefurthestfromthe
outletventineachroom.Ineveryroomthathas
anoutletvent,provideanexhaustopeningabout
2or2.5timestheventsizeoftheroom.Where
thedesignofthebuildingpreventsadequate
exhaust,considerationshouldbegiventothe
provisionofmechanicalextractionsuchasan
exhaustfan.
Totalminimumopeningsforthewholebuilding
aredemonstratedbythefollowingtable:
Pleasenotethatanaveragesizedooris1.5m
2
ILL1085-A
3
Startingyourcooler
TheON/OFFbuttonturnstheaircooleronand
off.
Therearetwomodesofoperationtochoose
from, AutomaticmodeorManualmode.When
theaircooleristurnedon,itwillstartinthe
modeofoperationitwasinwhenlastturnedoff.
Ifyouraircoolerhasnotbeenoperatedfora
while,thenwhenyoustartit,“PreCoolCycle”
maysometimesflashonthedisplayasshown.
Thisindicatesthatthewaterpumpwilloperateto
saturatethecoolingpadsforafewminutes
beforethefanisturnedon. Thisistoensurethat
whenthefanstarts,onlycoolairentersthe
building.
WALL CONTROL FUNCTIONS
WALL CONTROL FUNCTIONS - cont.
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
4
Automaticmode
Manualmode
The AUTObuttonisusedtoselect Automatic
modeorManualmode.When“Auto”isdisplayed
thecoolerisunder Automaticcontrolandwill
operateaccordingtothetemperaturesensedat
thewallcontrol.
Whentheaircooleristurnedon,itwillreadthe
temperatureandsetthecooleroperation
accordingly.Ifthetemperatureincreasesatthe
wallcontrol,thenthefanspeedwillincrease. As
thetemperaturedecreasesthefanspeedwill
decreaseuntilthecoolerturnsoff.
PressSorTtooveridetheautomatic
coolinglevelsettingandadjustyourroom
temperature.
ToswitchtoManualmode,press AUTOuntil
“Man”appearsinthedisplay.InManualmode
thecoolinglevelcanbemanuallyadjusted.
InManualmode,press tochoose
betweencirculatingcoolairorun-cooledair.
When“Cool”isdisplayed,freshcoolairwill
circulateintothebuilding.When“Vent”is
displayedasshown,freshun-cooledairwill
circulatethroughthebuilding.
PressStoincreasethefanspeedand
circulatemoreair.PressTtodecreasethefan
speedandcirculatelessair.Pressonceto
changethespeedbyoneincrement.Holdthe
buttondowntochangethespeedmorequickly.
COOL
AUTOMATICMODEDISPLAY
MANUAL MODEDISPLAY
ILL1085-A
3
Startingyourcooler
TheON/OFFbuttonturnstheaircooleronand
off.
Therearetwomodesofoperationtochoose
from, AutomaticmodeorManualmode.When
theaircooleristurnedon,itwillstartinthe
modeofoperationitwasinwhenlastturnedoff.
Ifyouraircoolerhasnotbeenoperatedfora
while,thenwhenyoustartit,“PreCoolCycle”
maysometimesflashonthedisplayasshown.
Thisindicatesthatthewaterpumpwilloperateto
saturatethecoolingpadsforafewminutes
beforethefanisturnedon. Thisistoensurethat
whenthefanstarts,onlycoolairentersthe
building.
WALL CONTROL FUNCTIONS
WALL CONTROL FUNCTIONS - cont.
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
4
Automaticmode
Manualmode
The AUTObuttonisusedtoselect Automatic
modeorManualmode.When“Auto”isdisplayed
thecoolerisunder Automaticcontrolandwill
operateaccordingtothetemperaturesensedat
thewallcontrol.
Whentheaircooleristurnedon,itwillreadthe
temperatureandsetthecooleroperation
accordingly.Ifthetemperatureincreasesatthe
wallcontrol,thenthefanspeedwillincrease. As
thetemperaturedecreasesthefanspeedwill
decreaseuntilthecoolerturnsoff.
PressSorTtooveridetheautomatic
coolinglevelsettingandadjustyourroom
temperature.
ToswitchtoManualmode,press AUTOuntil
“Man”appearsinthedisplay.InManualmode
thecoolinglevelcanbemanuallyadjusted.
InManualmode,press tochoose
betweencirculatingcoolairorun-cooledair.
When“Cool”isdisplayed,freshcoolairwill
circulateintothebuilding.When“Vent”is
displayedasshown,freshun-cooledairwill
circulatethroughthebuilding.
PressStoincreasethefanspeedand
circulatemoreair.PressTtodecreasethefan
speedandcirculatelessair.Pressonceto
changethespeedbyoneincrement.Holdthe
buttondowntochangethespeedmorequickly.
COOL
AUTOMATICMODEDISPLAY
MANUAL MODEDISPLAY
5
Timedautomaticstart
Timedautomaticstop
Youcansettheaircoolersothatitwillturnon
afterasetnumberofhours.
1. Tosetthedelayedstarttime,press
withthecoolerturnedOFF.“Startingin”will
bedisplayedasshownwiththelastmodeof
operation(Manualor Automatic).
2. Ifyouwanttheaircoolertoturnonin
Automaticmodewiththeprevioussettings,
thenpress until“Auto”isdisplayed.
Alternatively,ifyouwanttheaircoolerto
turnoninManualmode,press until
“Man”isdisplayedandthenpress
andthenSorTtosettherequiredfan
speed.
3. Tosetthetimeuntilthestart,press .
4. ThenpressSorTtoadjustthetime.
Thecoolercanstartupto24hoursin
advance.
5. Press againtoinitiatethetimed
automaticstart. Thetimedstartwillnot
repeat.
Youcanalsosettheaircoolersothatitwillturn
offafterasetnumberofhours.
1. Tosetadelayedstoptime,press
withthecoolerrunning.”Stoppingin”will
display.
TIMER
AUTO
AUTO
COOL
TIMER
TIMER
TIMER
2. PressSorTtoadjustthenumberof
hoursbeforetheaircoolerwillstop. The
maximumdelaysettingis24hours.
3. Press againtobeginthetimedstop.TIMER
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
6
Usingthecooler
Nowthatyouhavereadtheseinstructions,press
the buttontoturnyouraircooleron.If
theaircoolerhasnotoperatedforawhile,“Pre
CoolCycle”willflashonthedisplay. The“Pre
CoolCyclewillbeginandwilltakeonlyafew
minutestocomplete. Afterthistime,thefanwill
comeonautomatically,andyoucanenjoythe
comfortofcoolfreshair!
POWER
Airtoocold
Withthecoolerrunningin Automaticmode,you
mayfindthatyouaretoocoldorthattheair
coolerisblowingtoomuchair.PressTto
lowertheautomatictemperaturesettingand
reducetheamountofcooling.
Ifyouaretoocoldwiththecoolerrunningin
Manualmode,thenpressTtoreducethefan
speed. Youcanalsocirculatefreshun-cooledair
bypressing until“Vent”displays.COOL
Airnotcoldenough
Youmayfindthatwiththeaircoolerrunningin
Automaticmode,youarenotcoolenough.
SimplypressStoincreasethecoolingrate.
Ifyouarenotcoolenoughwiththeaircooler
runninginManualmode,thenpressSto
increasethefanspeed.Ensurethatcooledairis
circulatingbypressing until“Cool”
displays.
COOL
Youcanexperimentwiththesettingsonyour
wallcontrol.Thisisthebestwaytogetthe
mostfromyouraircooler.
WALL CONTROL FUNCTIONS- cont.
WALL CONTROL FUNCTIONS - cont.
Thiscoolercomeswithacontinuousbleed
system(CoolairCPL,BraemarBM)orautomatic
DrainValve(standardforBraemarLCB,optional
forCoolairCPL andBraemarBM).
Duringoperation,thebleedsystemwilldrain
smallamountsofwater. Thisensuresfreshwater
iscontinuallyaddedtodilutesaltaccumulationin
thewatercausedthroughevaporation. This
helpskeeptheaircooleringoodconditionand
ensureoptimumperformance. Thebleedratewill
dependonlocaloperatingconditionsandwillbe
setbytheinstaller.
Ifthedrainvalvewasinstalledinsteadofthe
continuousbleedsystemthenyourcoolerwill
automaticallydrainperiodically. Thisensuresthe
waterisalwaysfreshandhelpsmaintainyour
cooleringoodconditiontoensureoptimum
coolingperformance. Thefrequencyofthe
automaticdrainmayhavebeenadjustedbyyour
installeraccordingtothegeneralwaterqualityin
yourarea.
Whenthecooleristurnedofffor72hours,the
drainvalvewillopenautomaticallyandempty
waterfromthecooler.Whenthecooleristurned
onagain,fanoperationwilldelayforafew
minuteswhilethetankrefillsandthecooling
padsaresaturatedagain.
AtanytimewhenthethermostatisOFF,youcan
drainthecoolerbypressingandholdingS
andTfor1second. Thedisplaywillshow“dr”
toconfirmtheoperationhasactivated.
Continuous bleed system
Automatic drain valve
DRAINVALVE&BLEEDSYSTEM
ILL1478-A
5
Timedautomaticstart
Timedautomaticstop
Youcansettheaircoolersothatitwillturnon
afterasetnumberofhours.
1. Tosetthedelayedstarttime,press
withthecoolerturnedOFF.“Startingin”will
bedisplayedasshownwiththelastmodeof
operation(Manualor Automatic).
2. Ifyouwanttheaircoolertoturnonin
Automaticmodewiththeprevioussettings,
thenpress until“Auto”isdisplayed.
Alternatively,ifyouwanttheaircoolerto
turnoninManualmode,press until
“Man”isdisplayedandthenpress
andthenSorTtosettherequiredfan
speed.
3. Tosetthetimeuntilthestart,press .
4. ThenpressSorTtoadjustthetime.
Thecoolercanstartupto24hoursin
advance.
5. Press againtoinitiatethetimed
automaticstart. Thetimedstartwillnot
repeat.
Youcanalsosettheaircoolersothatitwillturn
offafterasetnumberofhours.
1. Tosetadelayedstoptime,press
withthecoolerrunning.”Stoppingin”will
display.
TIMER
AUTO
AUTO
COOL
TIMER
TIMER
TIMER
2. PressSorTtoadjustthenumberof
hoursbeforetheaircoolerwillstop. The
maximumdelaysettingis24hours.
3. Press againtobeginthetimedstop.TIMER
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
6
Usingthecooler
Nowthatyouhavereadtheseinstructions,press
the buttontoturnyouraircooleron.If
theaircoolerhasnotoperatedforawhile,“Pre
CoolCycle”willflashonthedisplay. The“Pre
CoolCyclewillbeginandwilltakeonlyafew
minutestocomplete. Afterthistime,thefanwill
comeonautomatically,andyoucanenjoythe
comfortofcoolfreshair!
POWER
Airtoocold
Withthecoolerrunningin Automaticmode,you
mayfindthatyouaretoocoldorthattheair
coolerisblowingtoomuchair.PressTto
lowertheautomatictemperaturesettingand
reducetheamountofcooling.
Ifyouaretoocoldwiththecoolerrunningin
Manualmode,thenpressTtoreducethefan
speed. Youcanalsocirculatefreshun-cooledair
bypressing until“Vent”displays.COOL
Airnotcoldenough
Youmayfindthatwiththeaircoolerrunningin
Automaticmode,youarenotcoolenough.
SimplypressStoincreasethecoolingrate.
Ifyouarenotcoolenoughwiththeaircooler
runninginManualmode,thenpressSto
increasethefanspeed.Ensurethatcooledairis
circulatingbypressing until“Cool”
displays.
COOL
Youcanexperimentwiththesettingsonyour
wallcontrol.Thisisthebestwaytogetthe
mostfromyouraircooler.
WALL CONTROL FUNCTIONS- cont.
WALL CONTROL FUNCTIONS - cont.
Thiscoolercomeswithacontinuousbleed
system(CoolairCPL,BraemarBM)orautomatic
DrainValve(standardforBraemarLCB,optional
forCoolairCPL andBraemarBM).
Duringoperation,thebleedsystemwilldrain
smallamountsofwater. Thisensuresfreshwater
iscontinuallyaddedtodilutesaltaccumulationin
thewatercausedthroughevaporation. This
helpskeeptheaircooleringoodconditionand
ensureoptimumperformance. Thebleedratewill
dependonlocaloperatingconditionsandwillbe
setbytheinstaller.
Ifthedrainvalvewasinstalledinsteadofthe
continuousbleedsystemthenyourcoolerwill
automaticallydrainperiodically. Thisensuresthe
waterisalwaysfreshandhelpsmaintainyour
cooleringoodconditiontoensureoptimum
coolingperformance. Thefrequencyofthe
automaticdrainmayhavebeenadjustedbyyour
installeraccordingtothegeneralwaterqualityin
yourarea.
Whenthecooleristurnedofffor72hours,the
drainvalvewillopenautomaticallyandempty
waterfromthecooler.Whenthecooleristurned
onagain,fanoperationwilldelayforafew
minuteswhilethetankrefillsandthecooling
padsaresaturatedagain.
AtanytimewhenthethermostatisOFF,youcan
drainthecoolerbypressingandholdingS
andTfor1second. Thedisplaywillshow“dr”
toconfirmtheoperationhasactivated.
Continuous bleed system
Automatic drain valve
DRAINVALVE&BLEEDSYSTEM
ILL1478-A
7
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
8
Health regulations
Note that some regulating authorities require
services to be conducted at specific intervals.
Removal of pad frames
To remove a pad frame, insert a flat screw driver
tip into the slot as shown and lever until
disengagement occurs.
MAINTENANCE MAINTENANCE- cont.
Take hold of the pad frame and pull it towards
you until the internal side clips disengage.
Pivot the pad frame outwards and lift up. Take
care not to damage the pad. Repeat these steps
for the remaining pad frames.
End of season service
!
!
!
!
!
Turn off the power supply to the cooler.
External inspection
1 Inspect the external cabinet for any
damage or deterioration.
2 Inspect the dropper duct, flashing etc.
for signs of corrosion
3 Check water supply valve for correct
operation and leakage.
Turn off the water supply to the cooler.
Remove the pad frames as shown.
A. Turn off the power switch in the cooler.
! B. Check and clean the lid water channels.
! C. If fitted, first unclip and then remove the
bleed system as shown. Allow the tank
water to drain. Do not lose the o-ring.
A
ILL1060-B
B
C
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Thoroughly clean the tank and pump filter.
Donotreplacethebleedsystem.(IfaDrain
Valveisfitteditwillautomaticallydrain.)
AnytimethethermostatisOFF,youcan
drainthecoolerbypressingandholdingS
andTfor1second. Thedisplaywillshow
“dr”toconfirmtheoperationhasactivated.
Re-fitthepadframes.
Turnoffthepowersupplytothecooler
RepeatexternalinspectionsasperEndof
SeasonService.
Removethepadframesasshown.
Ensurethepowerswitchinthecoolerisoff.
Gentlywashthepadstoremoveanydust
buildupduringthewinterperiod.Ifthepads
areinpoorcondition,replacethem.
Inspectpadretentionpinsandwashersfor
damageandthattheyaresecurelyfitted.
Replacethebleedsystemifitwasremoved
duringpreviousmaintenanceandensure
theo-ringisfitted.(Ifthecoolerisfittedwith
adrainvalvethiswillnotbenecessaryasit
willautomaticallyclosewhenthecooler
turnson).
Checkthefanmotor,mountsandbladesfor
damage.
Checkelectricalisolationswitchoperates
correctly.
Turnonthepowerswitchinsidethecooler.
Turnonthewaterandthenthepowertothe
cooler
Checkfloatvalveoperation.
Checkwaterpumpoperation.
Re-fitthepadframesandrunthecooler.
Checkthepadsarewettingevenly.
Checktherearenowaterleakseither
internallyorexternaltothecooler.
CheckDrainValve/BleedFunneloperation.
CheckWallControloperation.
1 Manualand Automodes
2 SpeedControl
3 DisplayPanel.
Pre-seasonservice
IMPORTANT:Donotdamagethepads
withhighpressurewaterspray.
Seasonalmaintenanceisonlyrequiredifyou
haveacoolerfittedwithableedsystem. The
followingpagesoutlinethemaintenance
requiredattheendoftheseasonandthenatthe
startofthenextseason. Thisensuresthatyour
coolercontinuestooperateefficiently.
Ifyourcoolerisfittedwithadrainvalveno
seasonalmaintenanceisrequired.However,we
requirethatthefollowingcomponentsandthe
operationthereof,becheckedafterthefirstyear,
thenevery2yearsasroutinemaintenance.
(1)......Pump.
(2)......DrainValve.
(3)......Solenoidandassociatedfilter.
(4)......Fanmotoroperationandcurrent.
(5)......Floatvalve.
Routinemaintenancemayberequiredmore
frequentlyinadverseenvironmental
situationsorwheretheapplianceisinstalled
innon-domesticapplications.
Regularmaintenanceisessentialtoensurethe
cooleroperatesefficientlyformanyyears.
Servicesmustbeperformedbeforeandafterthe
summerseason.Morefrequentservicingmaybe
requiredindustyconditionsorinareaswithpoor
waterquality.Itisimportanttonotethatall
evaporativecoolershavecomponentsthatmay
needperiodicreplacement(eg.filterpads,hoses,
o-ringsetc).
WARNING: We recommend maintenance is
carried out by an authorised service agent.
Climbing onto the roof is hazardous and can
result in personal injury or property damage.
Failure to carry out maintenance will affect
your warranty coverage.
7
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
8
Health regulations
Note that some regulating authorities require
services to be conducted at specific intervals.
Removal of pad frames
To remove a pad frame, insert a flat screw driver
tip into the slot as shown and lever until
disengagement occurs.
MAINTENANCE MAINTENANCE- cont.
Take hold of the pad frame and pull it towards
you until the internal side clips disengage.
Pivot the pad frame outwards and lift up. Take
care not to damage the pad. Repeat these steps
for the remaining pad frames.
End of season service
!
!
!
!
!
Turn off the power supply to the cooler.
External inspection
1 Inspect the external cabinet for any
damage or deterioration.
2 Inspect the dropper duct, flashing etc.
for signs of corrosion
3 Check water supply valve for correct
operation and leakage.
Turn off the water supply to the cooler.
Remove the pad frames as shown.
A. Turn off the power switch in the cooler.
! B. Check and clean the lid water channels.
! C. If fitted, first unclip and then remove the
bleed system as shown. Allow the tank
water to drain. Do not lose the o-ring.
A
ILL1060-B
B
C
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Thoroughly clean the tank and pump filter.
Donotreplacethebleedsystem.(IfaDrain
Valveisfitteditwillautomaticallydrain.)
AnytimethethermostatisOFF,youcan
drainthecoolerbypressingandholdingS
andTfor1second. Thedisplaywillshow
“dr”toconfirmtheoperationhasactivated.
Re-fitthepadframes.
Turnoffthepowersupplytothecooler
RepeatexternalinspectionsasperEndof
SeasonService.
Removethepadframesasshown.
Ensurethepowerswitchinthecoolerisoff.
Gentlywashthepadstoremoveanydust
buildupduringthewinterperiod.Ifthepads
areinpoorcondition,replacethem.
Inspectpadretentionpinsandwashersfor
damageandthattheyaresecurelyfitted.
Replacethebleedsystemifitwasremoved
duringpreviousmaintenanceandensure
theo-ringisfitted.(Ifthecoolerisfittedwith
adrainvalvethiswillnotbenecessaryasit
willautomaticallyclosewhenthecooler
turnson).
Checkthefanmotor,mountsandbladesfor
damage.
Checkelectricalisolationswitchoperates
correctly.
Turnonthepowerswitchinsidethecooler.
Turnonthewaterandthenthepowertothe
cooler
Checkfloatvalveoperation.
Checkwaterpumpoperation.
Re-fitthepadframesandrunthecooler.
Checkthepadsarewettingevenly.
Checktherearenowaterleakseither
internallyorexternaltothecooler.
CheckDrainValve/BleedFunneloperation.
CheckWallControloperation.
1 Manualand Automodes
2 SpeedControl
3 DisplayPanel.
Pre-seasonservice
IMPORTANT:Donotdamagethepads
withhighpressurewaterspray.
Seasonalmaintenanceisonlyrequiredifyou
haveacoolerfittedwithableedsystem. The
followingpagesoutlinethemaintenance
requiredattheendoftheseasonandthenatthe
startofthenextseason. Thisensuresthatyour
coolercontinuestooperateefficiently.
Ifyourcoolerisfittedwithadrainvalveno
seasonalmaintenanceisrequired.However,we
requirethatthefollowingcomponentsandthe
operationthereof,becheckedafterthefirstyear,
thenevery2yearsasroutinemaintenance.
(1)......Pump.
(2)......DrainValve.
(3)......Solenoidandassociatedfilter.
(4)......Fanmotoroperationandcurrent.
(5)......Floatvalve.
Routinemaintenancemayberequiredmore
frequentlyinadverseenvironmental
situationsorwheretheapplianceisinstalled
innon-domesticapplications.
Regularmaintenanceisessentialtoensurethe
cooleroperatesefficientlyformanyyears.
Servicesmustbeperformedbeforeandafterthe
summerseason.Morefrequentservicingmaybe
requiredindustyconditionsorinareaswithpoor
waterquality.Itisimportanttonotethatall
evaporativecoolershavecomponentsthatmay
needperiodicreplacement(eg.filterpads,hoses,
o-ringsetc).
WARNING: We recommend maintenance is
carried out by an authorised service agent.
Climbing onto the roof is hazardous and can
result in personal injury or property damage.
Failure to carry out maintenance will affect
your warranty coverage.
9
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
SERVICE
“SERVICE”
immediatelyonpower
upindicates
communicationsneeds
tobeestablished
Push&holdthe
buttonforat
least10secondsuntil
theword
disappears
“DOWN”
“SERVICE”
10
PROBLEM–UnpleasantOdour
CAUSE
ACTION
1. Odourfromnewpads. Allowtimetoconditionbyrunningtheair
cooler.Drainthewater,thenallowthetankto
re-fill.
PROBLEM–InadequateCooling
CAUSE
ACTION
1. Drypads.
Checkwaterflowtopads.
Inspectfitmentofdistributorcap.
Checkforblockedorkinkedhose.Ifblocked,
dismantle,cleanandflushorun-kinkthehose.
2. Insufficientexhaustopeningsfor
conditionedair.
Ensuresufficientopenings.Refertocharton
Pg.2
3. Excessiveambienthumidity
(SeealsoInsufficientexhaust)
Ondayswheretheambienthumidityishigh,
thecoolerwillnotreducethetemperatureas
muchasondrierdays.
IfyourwallcontroldisplaysSERVICEorshouldyouconsiderthatyourcoolerrequiresservice,contact
yourlocalDealerortheServicenumberonthebackofthismanual.
Note! Ifoninitialstartuptheword“Service”appearsonthecontrollerandbypushingtheon/offbutton
nothinghappens,thenyouwillneedtoestablishcommunicationbetweenthewallcontrolandthe
electroniccontroller.Simplypushandholdthe“DOWN”buttonforapprox.10secondsoruntilthe
word“Service”disappears.Ifbypushingtheon/offbuttonanumberappears,contactyourlocal
DealerortheServicenumberonthebackofthismanual.
TROUBLE-SHOOTINGGUIDE
ROUTINEMAINTENANCESERVICESCHEDULECHECKLIST
ServiceItem Check/adjust Clean Replace
1 2 3 4 5 1
WaterDistributionSystem
ComponentFunction
GeneralOperation
Chillcelpads(replaceasrequired)
Padretainingwashers/pins
Base/waterreservoir
Pumpfilterbasket
Waterprobes
Waterdistributionsystem
Washers,sealsandO-rings(replace
asrequired)
Drainoperation
Bleedrateset(whererequired)
Pumpoperation
Drainvalveoperation
Motoroperation(setmotoramps
whererequired)
Solenoidoperation
Wallcontroloperation
Waterlevelsetpoint
Waterfilltime
Waterdraintime
Waterdistributionacrosspads(nodryspots)
Airflowthroughsystem/outlets
Generalproductcondition
ServiceNo ServiceDate Service Technician ServiceCompany
No1 ..................... .......................................... ........................................................
(includescorrectfittingofallcomponentsanditems-
replaceasrequired)
2 3 4 5 1 2 3 4 5
No2 ..................... .......................................... ........................................................
No3 ..................... .......................................... ........................................................
No4 ..................... .......................................... ........................................................
No5 ..................... .......................................... ........................................................
9
SEELEY INTERNATIONAL – OWNER’SMANUAL
®
CPL LCBBMEvaporativeCooler
®
SERVICE
“SERVICE”
immediatelyonpower
upindicates
communicationsneeds
tobeestablished
Push&holdthe
buttonforat
least10secondsuntil
theword
disappears
“DOWN”
“SERVICE”
10
PROBLEM–UnpleasantOdour
CAUSE
ACTION
1. Odourfromnewpads. Allowtimetoconditionbyrunningtheair
cooler.Drainthewater,thenallowthetankto
re-fill.
PROBLEM–InadequateCooling
CAUSE
ACTION
1. Drypads.
Checkwaterflowtopads.
Inspectfitmentofdistributorcap.
Checkforblockedorkinkedhose.Ifblocked,
dismantle,cleanandflushorun-kinkthehose.
2. Insufficientexhaustopeningsfor
conditionedair.
Ensuresufficientopenings.Refertocharton
Pg.2
3. Excessiveambienthumidity
(SeealsoInsufficientexhaust)
Ondayswheretheambienthumidityishigh,
thecoolerwillnotreducethetemperatureas
muchasondrierdays.
IfyourwallcontroldisplaysSERVICEorshouldyouconsiderthatyourcoolerrequiresservice,contact
yourlocalDealerortheServicenumberonthebackofthismanual.
Note! Ifoninitialstartuptheword“Service”appearsonthecontrollerandbypushingtheon/offbutton
nothinghappens,thenyouwillneedtoestablishcommunicationbetweenthewallcontrolandthe
electroniccontroller.Simplypushandholdthe“DOWN”buttonforapprox.10secondsoruntilthe
word“Service”disappears.Ifbypushingtheon/offbuttonanumberappears,contactyourlocal
DealerortheServicenumberonthebackofthismanual.
TROUBLE-SHOOTINGGUIDE
ROUTINEMAINTENANCESERVICESCHEDULECHECKLIST
ServiceItem Check/adjust Clean Replace
1 2 3 4 5 1
WaterDistributionSystem
ComponentFunction
GeneralOperation
Chillcelpads(replaceasrequired)
Padretainingwashers/pins
Base/waterreservoir
Pumpfilterbasket
Waterprobes
Waterdistributionsystem
Washers,sealsandO-rings(replace
asrequired)
Drainoperation
Bleedrateset(whererequired)
Pumpoperation
Drainvalveoperation
Motoroperation(setmotoramps
whererequired)
Solenoidoperation
Wallcontroloperation
Waterlevelsetpoint
Waterfilltime
Waterdraintime
Waterdistributionacrosspads(nodryspots)
Airflowthroughsystem/outlets
Generalproductcondition
ServiceNo ServiceDate Service Technician ServiceCompany
No1 ..................... .......................................... ........................................................
(includescorrectfittingofallcomponentsanditems-
replaceasrequired)
2 3 4 5 1 2 3 4 5
No2 ..................... .......................................... ........................................................
No3 ..................... .......................................... ........................................................
No4 ..................... .......................................... ........................................................
No5 ..................... .......................................... ........................................................
seeleyinternational.com
AU0112
834955-F
Affixserial&model
number kerherestic
ItisthepolicyofSeeleyInternationaltointroducecontinual
productimprovement. Accordingly,specificationsare
subjecttochangewithoutnotice.Pleaseconsultwithyour
dealertoconfirmthespecificationsofthemodelselected.
WhenyoucontactyourDealerregardingservice
orwarrantypleasequotethecoolermodel
numberandserialnumberasshownbelow.
®
WarrantyService
Australia1-300-650-644
seeleyinternational.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12