Eaton SPC Series Installation Instructions Manual

Type
Installation Instructions Manual

Eaton SPC Series is a surge protective device (SPD) that safeguards critical electrical and electronic equipment from damage by voltage transients and surges when properly installed. By diverting high energy lightning surges and other transient disturbances through thermally protected metal oxide varistors, the Eaton SPC Series ensures the longevity of your valuable electronics.

Type 2 SPCs are designed for installation on the load side of the service equipment overcurrent device, including branch panel locations, to protect sensitive electronic equipment from damaging voltage transients and surges.

Eaton SPC Series is a surge protective device (SPD) that safeguards critical electrical and electronic equipment from damage by voltage transients and surges when properly installed. By diverting high energy lightning surges and other transient disturbances through thermally protected metal oxide varistors, the Eaton SPC Series ensures the longevity of your valuable electronics.

Type 2 SPCs are designed for installation on the load side of the service equipment overcurrent device, including branch panel locations, to protect sensitive electronic equipment from damaging voltage transients and surges.

Instruction Booklet IB158007EN
Effective September 2016 Rev. 1
Contents
Description Page
1 Introduction ............................2
2 SPC series catalog number ................3
3 SPC series product nameplate ..............3
4 Installation .............................3
5 Wiring diagrams .........................6
6 Operation ..............................7
7 Specifications ...........................7
8 Maintenance ............................8
9 Liability ................................8
10 Ordering guidelines .....................9
11 Voltage configurations per enclosure size ....9
12 Warranty .............................10
Installation instructions for Eaton SPC series
surge protective device (SPD)
2
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
1 Introduction
1.1 Manual introduction
This installation manual describes the installation and operation of
the Eaton SPC series surge protective device (SPD). This techni-
cal document covers most aspects of installation and operation.
This document is a guide only for licensed/qualified electricians. If
you require further information regarding a particular installation,
application, or maintenance activity, please contact your Eaton rep-
resentative. These instructions do not cover all details, variations or
combinations of the equipment, its storage, delivery, installation,
check-out, safe operation or maintenance. Care must be exercised to
comply with local, state, and national regulations, as well as safety
practices for this class of equipment.
Please read and understand ALL installation and operating
instructions prior to installation and use of this equipment.
1.2 Product overview
The Eaton SPC series protects critical electrical and electronic equip-
ment from damage by voltage transients and surges when properly
installed. This is done by shunting high energy lightning surges (and
other transient disturbances) away from the equipment being pro-
tected. It does this in nanoseconds by providing a low impedance
surge path through thermally protected metal oxide varistors while
supporting power frequency voltage. Eatons Type 2 SPC models
equipped with EMI Filtering are designed to protect sensitive equip-
ment from electrical noise. Proper installation is critical to ensure
the SPC operates as intended.
Eatons Type 1 SPC is intended for installation between the sec-
ondary of the service transformer and the line side of the service
equipment overcurrent device. As well as the load side, including
watt-hour meter socket enclosures and Molded Case surge protec-
tive devices intended to be installed without an external overcurrent
protective device.
Eatons Type 2 SPC is intended for installation on the load side of the
service equipment overcurrent device. Including branch panel loca-
tions and functions to protect sensitive electronic equipment from
damaging voltage transients and surges.
The SPC should be installed as close as possible to the equipment
to be protected.
The SPC series is available in voltage ratings from 120 Vac to
600 Vac, surge current ratings from 50kA to 200kA, and two sizes
of Type 4X enclosures. Enclosure size is determined by voltage
and peak surge current rating. The P1 enclosure measures 6.00” x
5.56” x 3.19” (152.3 mm x 141.2 mm x 81.1 mm) with a maximum
weight of 2.5 lbs (1.13 kg). The P2 enclosure measures 8.50” x
7.56” x 3.19” (215.9 mm x 192.0 mm x 81.1 mm) with a maximum
weight of 4.15 lbs (1.81 kg).
The Eaton SPC series is available in eight feature options, see
Section 10, Ordering guidelines for more details.
1.3 Safety precautions
WARNING
WARNING – SHOCK HAZARD – DO NOT OPEN.
AVERTISSEMENT – RISQUE DE CHOC – NE PAS OUVRIR.
WARNING NO SERVICEABLE PARTS.
ATTENTION : AUCUNE PIÈCE REMPLACABLE OU RÉPARABLE.
A LICENSED/QUALIFIED ELECTRICIAN MUST COMPLETE ALL
INSTRUCTIONS IN THIS MANUAL IN ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE (NEC), CANADIAN ELECTRICAL CODE (CEC), STATE, AND
LOCAL CODES, OR OTHER APPLICABLE COUNTRY CODES. ALL APPLICABLE
LOCAL ELECTRICAL CODES SUPERSEDE THESE INSTRUCTIONS.
CHECK THE VOLTAGE-RATING LABEL LOCATED ON THE SIDE OF THE SPC
TO VERIFY THAT THE ELECTRICAL SYSTEM’S VOLTAGE AND WIRING
CONFIGURATION ARE THE SAME AS THE SPC.
CONDUCTING DIELECTRIC, MEGGAR, OR HI-POTENTIAL TESTING WITH
THE SPD INSTALLED WILL CAUSE INTERNAL DAMAGE TO THE SPD. THE
SPD WILL CAUSE THE TEST TO FAIL.
IMPROPER INSTALLATION COULD CAUSE DEATH, INJURY AND
EQUIPMENT DAMAGE. FOLLOW ALL WARNINGS AND CAUTIONS.
COMPLETELY READ AND UNDERSTAND THE INFORMATION IN THIS
INSTRUCTION MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE
THIS EQUIPMENT.
ARC FLASH DURING INSTALLATION COULD CAUSE INJURY OR DEATH.
USE APPROPRIATE SAFETY PRECAUTIONS AND EQUIPMENT FOR ARC
FLASH PROTECTION.
INSTALLING A PROTECTION DEVICE WHICH IS UNDER RATED FOR THE
ELECTRICAL SYSTEM VOLTAGE CAN CREATE A POTENTIALLY HAZARDOUS
CONDITION.
CHECK THE FACILITY’S GROUNDING SYSTEM. ALL GROUNDING, BONDING
AND EARTHING PRACTICES MUST MEET NEC, CEC AND LOCAL APPROVED
PRACTICES. A POOR GROUND, OR A GROUNDING / BONDING VIOLATION
WILL SERIOUSLY AFFECT THE SPD’S ABILITY TO FUNCTION AS SPECIFIED.
3
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
2 SPC series catalog number
Each Eaton SPC series unit is identified by a catalog number, see
Table 1. The number identifies the parameters that make up the
unit.
Table 1. Catalog Numbering System
For example, an SPC unit with a catalog number of SPC200208Y8P,
where:
SPC = SPC series
200 = peak surge current rating (50 kA – 200 kA)
208Y = voltage code and system configuration
8 = feature option (1 – 8)
P = enclosure type (Type 4X enclosure)
See Section 10. Ordering guidelines for additional surge current kA
ratings, voltage codes and feature options.
3 SPC series product nameplate
Each Eaton SPC series unit has a nameplate affixed to the side of
the unit that identifies the catalog number and operating parameters.
The catalog # consists of letters and numbers which identify the
SPC series, kA rating, voltage code, feature option and type enclo-
sure as shown in Figure 1.
Figure 1. SPC Series Product Nameplate.
4 Installation
WARNING
A LICENSED/QUALIFIED ELECTRICIAN MUST COMPLETE ALL
INSTRUCTIONS IN THIS MANUAL IN ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE (NEC), CANADIAN ELECTRICAL CODE (CEC), STATE, AND
LOCAL CODES, OR OTHER APPLICABLE COUNTRY CODES. ALL APPLICABLE
LOCAL ELECTRICAL CODES SUPERSEDE THESE INSTRUCTIONS.
INSTALLING AN SPD THAT IS IMPROPERLY RATED FOR THE ELECTRICAL
SYSTEM VOLTAGE COULD CREATE A POTENTIALLY HAZARDOUS
CONDITION, RESULTING IN INJURY OR EQUIPMENT DAMAGE.
CHECK THE VOLTAGE-RATING LABEL LOCATED ON THE SIDE OF THE SPD
TO VERIFY THAT THE ELECTRICAL SYSTEM’S VOLTAGE AND WIRING
CONFIGURATION ARE THE SAME AS THE SPD.
TO PROVIDE THE BEST PROTECTION FOR SENSITIVE ELECTRICAL
EQUIPMENT THE 10 AWG WIRES SHOULD BE LESS THAN 14” IN LENGTH,
TWISTED TOGETHER AND THEN BOUNDED.
AVOID USING 90° CONDUIT ELBOWS AND KEEP THE CONDUIT RUN AS
SHORT AND STRAIGHT AS POSSIBLE. SEE FIGURES 1 AND 2
WHEN MOUNTING THE SPD OUTDOORS, USE WEATHERPROOF CONDUIT
AND FITTINGS TO MAINTAIN THE ENCLOSURE’S NEMA TYPE 4X RATING.
FOR USE ON CIRCUITS DELIVERING UP TO 5000 RMS AMPS. CONVIENT Á
DES CIRCUITS PRODUCISANT AU PLUS 5000 A EFF.
Before installing an Eaton SPC Series unit:
1. Verify that the area is clear of any dirt, debris or clutter that may
hamper the installation process.
2. Verify that there is enough space to install the SPC. See Figures
4 & 5 for dimensions.
3. Confirm that the system voltage and wiring configuration is
the same as the SPC you are installing. See Section 5. Wiring
Diagrams.
4. Check the facility grounding system. All grounding, bonding, and
earthing must meet the NEC, CEC and any other national, state
and local electrical codes.
5. An insulated grounding conductor that is identical in size and
insulation material and thickness to the grounded and unground-
ed circuit supply conductors, except that it is green with or with-
out one or more yellow stripes, is to be installed as part of the
circuit that supplies the SPC Series unit.
6. Refer to Table 250-122 of the NEC to select the appropriate size
of the grounding conductor. This grounding conductor is to be
grounded to earth at the service equipment or other acceptable
building earth ground such as the building frame in the case of a
high steel-frame structure.
4.1 Mounting
IMPORTANT
ALL CONNECTIONS IN THIS PROCEDURE MUST BE MADE IN ACCORDANCE
WITH NEC, CEC, STATE, COUNTY AND LOCAL CODES FOR ALL SAFETY RAT-
INGS.
TO ENSURE MAXIMUM EFFECTIVENESS AND PROVIDE THE BEST POS-
SIBLE PROTECTION FOR SENSITIVE ELECTRICAL EQUIPMENT, MOUNT IN
SUCH A WAY AS TO MINIMIZE THE CABLE LENGTH AND ELIMINATE ANY
SHARP BENDS IN THE WIRING CONDUIT. SEE FIGURE 2.
WHEN USING CONDUIT, AVOID USING 90° ELBOWS AND KEEP THE CON-
DUIT RUN AS SHORT AND STRAIGHT AS POSSIBLE. SEE FIGURE 3.
4
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
4.2 Panel mounted
The preferred mounting of the SPC is directly to the electrical panel
with its integrated male connector hub and the supplied ¾” trade
size conduit locknut. Insert the wires through the panel wall being
careful not to damage the wire insulation. Install the provided lock-
nut and tighten to 20.3 lb-in (2.3 N·m). If mounting requires the
NEMA 4X rating, install the supplied mounting feet to the enclosure
and securely mount the unit using #8 flat head screws (not includ-
ed). Be sure to use the appropriate gasket/liquid-tight fitting (not
included) between the unit and the panel wall. Liquid-tight conduit
torque should not exceed 200 lb-in (22.5 N·m).
Figure 2. Preferred Installation.
4.3 Panel mounted with conduit
In situations where the above preferred direct mounting cannot be
employed optional conduit mounting can be utilized. In this case
mount the SPC as close as possible to the electrical panel using ¾”
trade size conduit, ¾” trade size coupling, ¾” trade size connector
and the supplied ¾” trade size conduit locknut.
ote:N to maximize the SPC’s performance, 10 AWG wire length should be
less than 14” (35 cm) twisted and bound together.
Attach the conduit coupling, conduit and connector. Then insert the
wires through the conduit and through the panel wall being careful
not to damage the wire insulation. Install the provided locknut and
tighten to 20.3 lb-in (2.3 N-m). If mounting requires the NEMA 4X
rating, install the provided four mounting feet to the enclosure and
be sure to use the appropriate gasket/liquid-tight fittings (not includ-
ed) between the unit and the panel wall. Liquid-tight conduit torque
should not exceed 200 lb-in (22.5 N·m).
Figure 3. Alternate Installation.
When mounting the SPC outdoors, use the supplied mounting
feet, weatherproof conduit and fittings to maintain the enclo-
sure’s Type 4X rating.
4.4 Enclosure mounting feet
The mounting feet attach to the bottom of the enclosure with the
provided screws (hardware to mount the feet to wall are not includ-
ed). See Figure 4 and 5.
Figure 4. P1 Enclosure w/Mounting Feet Dimensions.
Figure 5. P2 Enclosure w/Mounting Feet Dimensions.
5
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
4.5 Optional flush mount plate
Optional Flush Mount Plates are available for both the P1 and P2
enclosure sizes. See Figures 6 & 7.
Catalog# FLUSHMNTPLATE13 – P1 Enclosure Flush Mount Plate
Catalog# FLUSHMNTPLATE14 – P2 Enclosure Flush Mount Plate
Figure 6. Optional P1 Enclosure Flush Mount Plate. Catalog#
FLUSHMNTPLATE13.
Figure 7. Optional P2 Enclosure Flush Mount Plate. Catalog#
FLUSHMNTPLATE14.
4.6 Wiring installation
WARNING
IMPROPER WIRING COULD CAUSE DEATH, INJURY AND/OR EQUIPMENT
DAMAGE. ONLY LICENSED/QUALIFIED ELECTRICIANS WHO ARE TRAINED
IN THE INSTALLATION AND SERVICE OF ELECTRICAL SERVICES ARE TO
INSTALL AND SERVICE THIS EQUIPMENT.
TO MAXIMIZE THE SPD’S PERFORMANCE, TWIST AND BIND THE WIRES
TOGETHER TO REDUCE THE IMPEDANCE OF THE WIRE.
ARC FLASH DURING INSTALLATION COULD CAUSE INJURY OR DEATH.
USE APPROPRIATE SAFETY PRECAUTIONS AND EQUIPMENT FOR ARC
FLASH PROTECTION.
Locate the electrical system’s applicable wiring schematic in Section
5 Wiring Diagrams.
Turn OFF power to the electrical equipment being connected to the
SPC in accordance with NEC, CEC, state, county and local codes
for all safety ratings.
Eaton SPC’s covered in this guide are designed with internal overcur-
rent protection and do not require an external overcurrent protection
device (OCPD) unless otherwise required by NEC, UL, and local
electrical requirements to protect electrical conductors. NEC Article
310.15 (B) (16) defines the maximum rating of the OCPD required to
protect the electrical conductors.
NEC shows #10 AWG conductors at 60°C typically requiring a 1-pole
(for single phase systems), 2-pole (for split-phase systems) or 3 pole
(for 3-phase systems) 30A branch circuit breaker to protect SPC con-
ductors.
Twist and bind the wires of the SPC unit tightly together. Minimize
overall lead length to optimize SPC performance. For wire lengths
longer than four inches, phase wires should be twisted once for
each four inches of wire length to maximize performance.
ote:N to maximize the SPC’s performance, 10 AWG wire length should be
less than 14” (35cm) twisted and bound together.
If remote monitoring is required, connect the Form C relay contact
wiring to an alarm or building monitoring system. These relay con-
tacts are rated:
2A at 30Vdc or 250Vac
Refer to Table 2 – SPC Series Form C Wire Color Codes for color
codes of relay wires (shown in the energized state).
ote:N Utilization of Form C contacts is optional. Connection of Form C wires
is not required for the proper operation of the SPC.
Tighten and recheck all connections and mounting.
Table 2. SPC Series Form C Wire Color Code
FORM C WIRE COLOR CODE
CONTACT COLOR
COM BLUE/WHITE
NO RED/WHITE
NC ORANGE/WHITE
6
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
5. Wiring diagrams
Table 3. SPC Series Phase Wire Color Code
PHASE WIRE COLOR CODE
PHASE WIRE COLOR
L1 (Phase A) Black
L2 (Phase B) Black
L2 (Phase B) Hi Leg Delta Orange
L3 (Phase C) Black
Neutral White
Ground / Protected Earth Green w/ Yellow Stripe
Figure 8. Single Phase (2W+G).
Figure 9. Split Phase (3W+G).
Figure 10. Three Phase Delta (3W+G).
Figure 11. Three Phase Wye (4W+G).
Figure 12. Three Phase High Leg Delta on Phase B (4W+G).
Figure 13. Three Phase High Leg Delta on Phase C (4W+G).
7
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
6 Operation
6.1 Power up and system checkout
Switch main panel power to ON and then switch SPC’s branch circuit
breaker to ON. One LED should light for each phase voltage being
monitored. Single phase electrical systems will light only one LED,
split phase systems light two LEDs, and three phase systems will
light all three LEDs.
If the connected LEDs do not light, remove power, check connec-
tions, and test again. If the LEDs still do not light, contact your local
authorized distributor or Power Quality Technical Resource Center at:
1-800-809-2772, Option 4, sub-option 2, or email [email protected] as
the SPC may be damaged.
6.2 LED color states
The LED’s located on the lid of the SPC has three LED color states,
Green – fully protected
Yellow – loss of Neutral to Ground protection
Red – loss of phase protection
If the electrical system is single, split or 3 phase, the SPC will have
either one, two or three green illuminated LEDs, respectively. Each
LED will illuminate when its associated phase voltage is present.
If any of these LEDs are yellow or red a problem may exist with
incoming power, wiring, branch circuit breaker wiring or within the
SPC itself. Disconnect power, check connections and test again. If
the LEDs are still yellow or red, disconnect power to the SPC and
contact your local authorized distributor or Power Quality Technical
Resource Center at: 1-800-809-2772, Option 4, sub-option 2, or
email [email protected] as the SPC may be damaged.
6.3 Options: audible alarm and form C relay
ote:N Utilization of Form C contacts is optional. Connection is not required
for the proper operation of the SPC.
The audible alarm and Form C relay are tied to the Phase LED’s
located on the SPC Series enclosure’s lid. If protection to one or
more phases is lost the following will occur:
Single, Split and 3 Phase devices - if all voltage is lost to the SPC
then the green LED(s) will go out, the alarm will not sound and
the relay will not be energized.
Split and 3 Phase devices - if one phase voltage is lost to the SPC
then that one green LED will go out, the alarm will not sound and
the relay will stay energized (if there is another phase voltage
present).
3 Phase Wye and 3 Phase High Leg Delta devices - if one or two
phase voltages are lost to the SPC then one or two green LEDs
will go out, the alarm will not sound and the relay will stay ener-
gized (if there is another phase voltage present).
3 Phase Delta – SPC needs at least 2 phases to energize the relay
and to keep the alarm from sounding (if installed).
Single, Split and 3 Phase devices - if one or more LEDs turn red,
the alarm will sound and the relay will de-energize. To silence
the alarm, disconnect power to the SPC and contact your
local authorized distributor or Power Quality Technical Resource
Center at: 1-800-809-2772, Option 4, sub-option 2, or email
[email protected] as the SPC may be damaged.
ote:N Form C relay contacts are “fail safe” and only change state when
power is applied to the SPC and the electrical system is operating normally or
when loss of protection is detected and yellow or red LEDs are illuminated.
7 Specications
kA per Phase 50, 80, 100, 120, 150, 160, 200
Nominal Discharge Current 20kA
Single Phase Voltages 120, 240, 277, 480
Split Phase Voltages 120/240
Wye System Voltages 120/208, 240/415, 277/480, 347/600
Delta System Voltages 240, 480, 600
High Leg Delta Voltage 240
Input Power Frequency 50/60 Hz
Protection Modes Single Phase L-N, N-G, L-G
Split Phase L-N, N-G, L-G, L-L
Wye L-N, N-G, L-G, L-L
Delta L-G, L-L
High Leg L-N,N-G,L-G,L-L,H-N,H-G,H-L
Mounting feet Torque rating
20.3 lb-in (2.3 N·m)
Conduit locknut Torque rating
Not to exceed 200 lb-in (22.5 N·m)
Operating Temperature -40°F to +140°F (-40°C to +60°C)
Relative Humidity 5% - 95%, non condensing
Max. altitude 2000 m
Weight, vary per configuration P1 enclosure ~2.5 lbs
P2 enclosure ~4.0 lbs
Certification/Listing UL 1449 4th edition, UL1283 6th edition, CSA
269.1-14, 269.2-15, C22.2 No. 8-13 EMI Filter
SPD Type UL1449 4th edition & CSA Type 1 and Type
2 SPD
RoHS Compliant Yes
Enclosure Rating Type 4X Enclosure w/ mounting feet, IP56
8
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
8 Maintenance
The SPC is a self-contained device that requires no maintenance and
contains no serviceable parts. If any LED turns red or yellow the
unit has lost surge protection and must be replaced. Please contact
your local authorized distributor or Power Quality Technical Resource
Center at: 1-800-809-2772, Option 4, sub-option 2, or email spd@
eaton.com for additional information and technical assistance, as the
SPC may be under warranty.
9 Liability
This instruction booklet is published solely for information purposes
and should not be considered all-inclusive. If further information
is required, you should consult Eatons Power Quality Technical
Resource Center at: 1-800-809-2772, Option 4, sub-option 2 or email
[email protected]. Sale of the product shown in this literature is sub-
ject to terms and conditions outlined in appropriate Eaton selling
policies or other contractual agreements between the parties. This
literature is not intended to and does not enlarge or add to any such
contract. The sole source governing the rights and remedies of any
purchaser of this equipment is the contract between the purchaser
and Eaton.
NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE
OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING
THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS
CONTAINED HEREIN.
In no event will Eaton be responsible to the purchaser or user in con-
tract, in tort (including negligence), strict liability or otherwise for any
special, indirect, incidental or consequential damage or loss what-
soever, including but not limited to damage or loss of equipment
use, plant or power system, cost of capital, loss of power, additional
expenses in the use of existing power facilities or claims against
the purchaser or user by its customers resulting from the use of the
information, recommendations and description contained herein.
9
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
10 Ordering guidelines
Figure 14. Ordering Guidelines
11 Voltage congurations per enclosure size
P1 Enclosure P2 Enclosure
120N/240N/277N/480N 50kA – 200kA 600D 50kA – 200kA
240S 50kA – 100kA 240S 120kA – 200kA
208Y/415Y/480Y/600Y 50kA – 100kA 208Y/415Y/480Y/600Y 120kA – 200kA
240D/480D 50kA – 100kA 240D/480D 120kA – 200kA
240H 50kA – 100kA 240H 120kA – 200kA
SPC 200 208Y 8 P
Series
kA Rating
Voltage Code
Options
120N – 120V Single Phase (2W +G)
240N – 240V Single Phase (2W +G)
277N – 277V Single Phase (2W +G)
480N – 480V Single Phase (2W +G)
240S – 120/240V Split Phase (3W +G)
240D – 240V Delta (3W + G)
480D – 480V Delta (3W + G)
600D – 600V Delta (3W + G)
240H – 240V High Leg Delta (4W + G)
208Y – 120/208VWye (4W + G)
415Y – 240/415V Wye (4W + G)
480Y – 277/480V Wye (4W + G)
600Y – 347/600V Wye (4W + G)
Options
050kA per Phase
080kA per Phase
100kA per Phase
120kA per Phase
150kA per Phase
160kA per Phase
200kA per Phase
Options
1 – No Options*
2 – Filtering, UL1283 6
th
Edition
3 – Audible Alarm*
4 – Form C Relay*
5 – Audible Alarm and Form C Relay*
6 – Filtering and Audible Alarm
7 – Filtering and Form C Relay
8 – Filtering, Audible Alarm and Form C Relay
*Type 1 SPD's, all others are Type 2 SPD's.
P – Type 4X Enclosure
Features
Enclosure
10
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
12 Warranty
Eaton warrants the SPC to be free from defects in both workman-
ship and materials for a period of five years, ten years if the product
is properly registered, from the date of delivery to the purchaser. To
register, go to www.eaton.com/spc and click on the warranty regis-
tration icon.
Eaton assumes no risk or liability for results of the use of the prod-
uct purchased, including but not limiting the generality of the forego-
ing:
(1) The use in combination with any electrical or electronic compo-
nents, circuits, systems, assemblies or any other materials or sub-
stances.
(2) Unsuitability of any product for use in any circuit or assembly.
Purchasers rights under the warranty shall consist solely of requir-
ing Eaton to repair, or at Eatons sole discretion, replace, free of
charge, F.O.B. factory, any defective items received at said factory
within said term determined by Eaton to be defective. The giving of
or failure to give any advice or recommendations by Eaton shall not
constitute any warranty by or impose any liability upon Eaton AND
IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED,
IMPLIED OR STATUTORY AS TO THE MERCHANTABILITY, FITNESS
FOR PURPOSE SOLD, PRODUCTIVENESS OR ANY OTHER
MATTER. In no event shall Eaton be liable for special or consequen-
tial damages or for delay in performance of the warranty.
This warranty does not apply if the unit has been misused, abused,
altered, tampered with, or applied in excess of the specifications
other than those written on the nameplate. At the end of the war-
ranty period Eaton shall be under no further warranty obligation
expressed or implied.
The Eaton SPC covered by this warranty certificate can only
be repaired or replaced by the factory. A RETURN MATERIAL
AUTHORIZATION (RMA) number must be obtained. Please enter
a Vista warranty claim by contacting your local authorized Eaton
Distributor or the Eaton Technical Resource Center at 1 800 809-
2772 option 4, option 2, or email [email protected] for help entering a
claim or to obtain an update on your claim status. Repair or replace-
ment will be returned collect. If it is determined that the returned
product contains manufacturer’s defects then Eaton will replace the
defective product at Eatons expense (including shipping charge).
11
Instruction Booklet IB158007EN
Effective September 2016
Installation instructions for Eaton SPC series
surge protective device (SPD)
EATON www.eaton.com
Notes:
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2016 Eaton
All Rights Reserved
Printed in USA
Publication No. IB158007EN / TBG001323
September 2016
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.
Installation instructions for Eaton SPC series
surge protective device (SPD)
Instruction Booklet IB158007EN
Effective September 2016
Notice:
Product improvements and enhancements are
continuous; therefore the specifications and
information contained in this document may
change without notice.
Eaton shall not be liable for errors contained
herein or for incidental or consequential dam-
ages in connection with the furnishing, perfor-
mance, or use of this material.
No part of this document may be reproduced
for publication, or translated to another lan-
guage without the prior written consent of
Eaton.
Copyright © 2016, Eaton, All Rights Reserved
For additional information please call:
All Rights Reserved
Eaton’s Technical Resource Center
Publication No. IB158007EN
1-800-809-2772 Option 4, sub-option 2
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Eaton SPC Series Installation Instructions Manual

Type
Installation Instructions Manual

Eaton SPC Series is a surge protective device (SPD) that safeguards critical electrical and electronic equipment from damage by voltage transients and surges when properly installed. By diverting high energy lightning surges and other transient disturbances through thermally protected metal oxide varistors, the Eaton SPC Series ensures the longevity of your valuable electronics.

Type 2 SPCs are designed for installation on the load side of the service equipment overcurrent device, including branch panel locations, to protect sensitive electronic equipment from damaging voltage transients and surges.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI