ICM Controls ICM531 Application/Install Guide

  • Hello! I am an AI chatbot trained to assist you with the ICM Controls ICM531 Application/Install Guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
Description Ratings
Service Voltage (3-Phase) 480 VAC Delta OR 277/480 VAC Wye
Short Circuit Current
Rating (SCCR) 200 kA
Nominal Discharge
Current (In) 20 kA
SPD Type Type 1 (Can also be used in Type 2 applications)
Surge Protection
Technology TFMOV
Protection Mode 

VPR (Vpk)
VOLTS (V) MODE VPR (Vpk)
480 L-L 2500
480/277 L-L 2500
L-N 1200
Maximum Continuous
Operation Voltage (MCOV)
L-L: 700 VAC
L-N:
Input Power Frequency 50/60Hz
Diagnostics 
Enclosure Rating 
outdoor and indoor installation
Installation Point Electrical panel/disconnect
Dimensions 4.3” X 4.1” X 2.3”
Operating Temperature -40°F to 185°F (-40°C to 85°C)
Operating Humidity 
Operating Altitude 
Agency Certication and
Approvals

Listed
ICM531

ICM531
ICM531


ICM531
ICM531 can










E347279
MAINTENANCE
MODE OF OPERATION
SPECIFICATIONS



disconnect.

ICM531

ICM531
electrical panel.
ICM531.



Wiring Type 1 installation
 


codes.
 

Wiring Type 2 installation
 


national electrical codes.
 



ELECTRICAL SHOCK HAZARD!
Before installing
this unit, turn o power at the main service panel by
removing the fuse or switching the appropriate circuit
breaker to the OFF position.
• WARNING — No Serviceable Parts (Attention: Aucune pièce
remplaçable ou reparable).
• WARNING — Shock hazard — Do not open (ATTENTION – RISQUE
DE CHOC – NE PAS OUVRIR).
INSTALLATION, OPERATION & APPLICATION GUIDE

www.icmcontrols.com
ICM531
Surge Protective Device for 3-Phase Delta 480 VAC or Wye 277/480 VAC
IMPORTANT SAFETY INFORMATION
INSTALLATION INSTRUCTIONS
Limited lifetime
product, up to a 3-year
$10,000 connected
equipment warranty
Please follow all State, Local and National electrical codes when
installing this product. Installation should only be done by a licensed
electrician for Type 1 devices or a licensed HVAC technician for Type
2 devices.
BLK
BLK
BLK
Neutral
Bus
WHT
Wire
Nut
ICM531
A C
B
Incoming
3-Phase Voltage

Ground
Bus
Type 1 Wiring – 
Ground Bus
BLK
BLK
BLK
Neutral
Bus
WHT
Wire
Nut
A C
B
Incoming
3-Phase Voltage

ICM531
Type 2 Wiring – 
Optional
cornered
ground on
any of the
phases
Grounded
on any of
the phases
Ground
Bus
Neutral
C
B
A
Ground
Incoming
3-Phase Voltage

BLK
BLK
BLK
WHT
ICM531
Neutral
Bus
Type 1 Wiring – 
BLK
BLK
BLK
Ground Bus
Neutral
C
B
A
Ground
WHT
ICM531
Neutral
Bus
Incoming
3-Phase Voltage

Type 2 Wiring – 
Black
WHT White
  Incoming phase
Ground


For the ease of checking the SPD protection
status, the LED display should face
outwards aer installation has been
complete.


is a Type 1 and 2 SPD, designed to
be compatible with 3-phase Delta and
3-phase Wye voltage conguration. Please
check your supply voltage conguration
and voltage levels before installing the
 per wiring diagram.

• When installing the Surge Protecting
Device (SPD), avoid sharp bends in the
conduit and long line sets.
• Keep the mounting conduit straight and
short in length
Black
WHT White
  Incoming phase
Ground


For the ease of checking the SPD protection
status, the LED display should face
outwards aer installation has been
complete.


is a Type 1 and 2 SPD, designed to
be compatible with 3-phase Delta and
3-phase Wye voltage conguration. Please
check your supply voltage conguration
and voltage levels before installing the
 per wiring diagram.

• When installing the Surge Protecting
Device (SPD), avoid sharp bends in the
conduit and long line sets.
• Keep the mounting conduit straight and
short in length
LIMITED LIFETIME PROTECTION WARRANTY
Review enclosed warranty information for full details & registration information
For warranty registration, please go to www.icmcontrols.com and click on
Warranty Registration

800.365.5525

Phone: Fax: 
www.icmcontrols.com
WIRING DIAGRAMS – DELTA CONFIGURATION
WIRING DIAGRAMS – WYE CONFIGURATION
/