Johnson Controls VFD67 Series Getting Started Manual

Type
Getting Started Manual
Getting Started Guide
AC variable frequency drive
for 3 phase induction
motors from 0.25kW to
7.5kW, 0.33hp to 10hp
Model sizes A, B, C and D
Part Number: 24-10511-23
Issue: 1
VFD67
General Information
The manufacturer accepts no liability for any consequences resulting from inappropriate, negligent
or incorrect installation or adjustment of the optional parameters of the equipment or from
mismatching the variable speed drive with the motor.
The contents of this guide are believed to be correct at the time of printing. In the interests of
commitment to a policy of continuous development and improvement, the manufacturer reserves the
right to change the specification of the product or its performance, or the content of the guide without
notice.
Drive software version
This product is supplied with the latest version of user-interface and machine control software. If this
product is to be used in a new or existing system with other drives, there may be some differences
between their software and the software in this product. These differences may cause the product
to function differently.
Copyright © April 2009
Issue: 1
Software: 01.08.01 onwards
VFD67 Size A to D Getting Started Guide
Issue Number: 1 www.johnsoncontrols.com
Contents
EC Declaration of Conformity ............................................ 4
1 Safety Information .............................................................. 5
1.1 Warnings, Cautions and Notes ............................................................... 5
1.2 Electrical Safety - general warning .......................................................... 5
1.3 System design and safety of personnel ..................................................5
1.4 Environmental Limits ............................................................................... 5
1.5 Access ..................................................................................................... 6
1.6 Compliance and regulations .................................................................... 6
1.7 Motor ....................................................................................................... 6
1.8 Adjusting parameters .............................................................................. 6
1.9 Electrical installation ................................................................................ 6
2 Rating Data .......................................................................... 9
3 Mechanical Installation .................................................... 11
4 Electrical Installation ........................................................ 13
4.1 Power terminal connections .................................................................. 13
4.2 Ground leakage ..................................................................................... 14
4.3 EMC ...................................................................................................... 15
4.4 Control terminals I/O specification ........................................................ 16
5 Keypad and Display .......................................................... 19
5.1 Programming keys ................................................................................ 19
5.2 Control keys .......................................................................................... 19
5.3 Selecting and changing parameters ...................................................... 20
5.4 Saving parameters ................................................................................ 21
5.5 Parameter access ................................................................................. 21
5.6 Security codes ....................................................................................... 22
5.7 Setting drive back to default values ......................................................22
6 Parameters ........................................................................ 23
6.1 Parameter descriptions - Level 1 ..........................................................23
6.2 Parameter descriptions - Level 2 ..........................................................30
6.3 Parameter descriptions - Level 3 ..........................................................38
6.4 Diagnostic parameters .......................................................................... 39
7 Quick Start Commissioning ............................................. 40
7.1 Keypad control ...................................................................................... 40
7.2 Terminal control .................................................................................... 42
8 Diagnostics ....................................................................... 44
9 Parameter List ................................................................... 47
10 Technical specifications .................................................. 49
11 UL Listing Information ..................................................... 50
11.1 UL information (for VFD67 size A, B, C and D) ..................................... 50
4 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
EC Declaration of Conformity
Certify and declare under our sole responsibility that the following:
conforms with the essential requirements of the following directives:
The following harmonised standards have been applied:
and therefore complies with the essential requirements and provisions of the Directives.
The Technical documentation can by the surveillance Authorities be requested at the following
address:
Name and position of person authorised by the manufacturer
PDM Name: EU-DOC-VFD67-SERIES
Manufacturer: Johnson Controls Inc.
Address: 4620 Olympic Blvd, Erlanger KY 41018-0000
Country: USA
Phone number: 859-283-1384
Description: Variable Frequency Drive for 3 phase induction motors
Product name: VFD67
Brand: Johnson Controls / Penn
Identification
VFD67 followed by AAA, ABA, ADA, AEA, BAA, BBA, BCA, BDA, BEB, BFB, BCG,
BJD, BKE, BME, BNF, BPF, CBB, CCB, CDB, CEB, CFD, CGC, CHC, CJC, CKD,
CMD, CNE, CPE, DJF, DKF, DMF, OR DPF. All can be followed by up to three
additional numbers followed by up to two additional letters.
EMC Directive 2004/108/EC
Low Voltage Directive 2006/95/EC
EN 61800-5-1:2007
EN 61800-3:2004
EN 61000-6-2:2005
EN 61000-6-4:2007
EN 61000-3-2:2006
EN 61000-3-3:2008
Company: Johnson Controls Inc. - Att: Environment and Legislation
Address, City: Christian X’s Vej 201, 8270 Hoejbjerg
Country: Denmark
Phone number: + 45 8736 7000
George Rudich
Engineering Manager. Johnson Controls Inc
Date: 6/11/2009
VFD67 Size A to D Getting Started Guide 5
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
1 Safety Information
1.1 Warnings, Cautions and Notes
1.2 Electrical Safety - general warning
The voltages used in the drive can cause severe electrical shock and/or burns, and
could be lethal. Extreme care is necessary at all times when working with or adjacent to
the drive.
Specific warnings are given at the relevant places in this guide.
1.3 System design and safety of personnel
The drive is intended as a component for professional incorporation into complete
equipment or system. If installed incorrectly, the drive may present a safety hazard.
The drive uses high voltages and currents, carries a high level of stored electrical
energy, and is used to control equipment which can cause injury.
System design, installation, commissioning and maintenance must be carried out by
personnel who have the necessary training and experience. They must read this safety
information and this guide carefully.
The STOP and START controls or electrical inputs of the drive must not be relied
upon to ensure safety of personnel. They do not isolate dangerous voltages from
the output of the drive or from any external option unit. The supply must be
disconnected by an approved electrical isolation device before gaining access to
the electrical connections.
The drive is not intended to be used for safety-related functions.
Careful consideration must be given to the function of the drive which might result in a
hazard, either through its intended behaviour or through incorrect operation due to a
fault. In any application where a malfunction of the drive or its control system could lead
to or allow damage, loss or injury, a risk analysis must be carried out, and where
necessary, further measures taken to reduce the risk - for example, an over-speed
protection device in case of failure of the speed control, or a fail-safe mechanical brake
in case of loss of motor braking.
1.4 Environmental Limits
Instructions within the supplied data and information within Chapter 10 Technical
specifications on page 49 regarding transport, storage, installation and the use of the
drive must be complied with, including the specified environmental limits.
A Warning contains information, which is essential for avoiding a safety hazard.
WARNING
A Caution contains information, which is necessary for avoiding a risk of damage to the
product or other equipment.
CAUT ION
A Note contains information, which helps to ensure correct operation of the product.
NOTE
6 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
1.5 Access
Access must be restricted to authorized personnel only. Safety regulations which apply
at the place of use must be complied with.
The IP (Ingress Protection) rating of the drive is installation dependant.
1.6 Compliance and regulations
The installer is responsible for complying with all relevant regulations, such as national
wiring regulations, accident prevention regulations and electromagnetic compatibility
(EMC) regulations. Particular attention must be given to the cross-sectional areas of
conductors, the selection of fuses and other protection, and protective ground (earth)
connections.
Within the European Union, all machinery in which this product is used must comply
with the following directives:
98/37/EC: Safety of machinery
2004/108/EC: Electromagnetic compatibility
1.7 Motor
Ensure the motor is installed in accordance with the manufacturer's recommendations.
Standard squirrel cage induction motors are designed for single speed operation. If it is
intended to use the capability of a drive to run a motor at speeds above its designed
maximum, it is strongly recommended that the manufacturer is consulted first.
Low speeds may cause the motor to overheat because the cooling fan becomes less
effective. If necessary, an electric force vent fan should be used or a protection
thermistor can be installed.
The values of the motor parameters set in the drive affect the protection of the motor.
The default values in the drive should not be relied upon.
It is essential that the correct value is entered into parameter 06, motor rated current.
This affects the thermal protection of the motor.
1.8 Adjusting parameters
Some parameters have a profound effect on the operation of the drive. They must not
be altered without careful consideration of the impact on the controlled system.
Measures must be taken to prevent unwanted changes due to error or tampering.
1.9 Electrical installation
1.9.1 Electric shock risk
The voltages present in the following locations can cause severe electric shock and may
be lethal:
AC supply cables and connections
DC bus, dynamic brake cables and connections
Output cables and connections
Many internal parts of the drive, and external option units
Unless otherwise indicated, control terminals are single insulated and must not be
touched.
1.9.2 Isolation device
The AC supply must be disconnected from the drive using an approved isolation device
before any cover is removed from the drive or before any servicing work is performed.
VFD67 Size A to D Getting Started Guide 7
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
1.9.3 STOP function
The STOP function does not remove dangerous voltages from the drive, the motor or
any external option units.
1.9.4 Stored charge
The drive contains capacitors that remain charged to a potentially lethal voltage after the
AC supply has been disconnected. If the drive has been energized, the AC supply must
be isolated at least ten minutes before work may continue.
Normally, the capacitors are discharged by an internal resistor. Under certain, unusual
fault conditions, it is possible that the capacitors may fail to discharge, or be prevented
from being discharged by a voltage applied to the output terminals. If the drive has failed
in a manner that causes the display to go blank immediately, it is possible the capacitors
will not be discharged. In this case, consult Johnson Controls Inc or their authorized
distributor.
1.9.5 Equipment supplied by plug and socket
Special attention must be given if the drive is installed in equipment which is connected
to the AC supply by a plug and socket. The AC supply terminals of the drive are
connected to the internal capacitors through rectifier diodes which are not intended to
give safety isolation. If the plug terminals can be touched when the plug is disconnected
from the socket, a means of automatically isolating the plug from the drive must be used
(e.g. a latching relay).
1.9.6 Ground leakage current
The drive is supplied with an internal EMC filter capacitor installed. If the input voltage to
the drive is supplied through an ELCB, GFCI or RCD, these may trip due to the ground
leakage current. See section 4.3.1 Internal EMC filter on page 15 for further information
and how to disconnect the internal EMC capacitor.
The VFD67 series variable speed drives are intended to control equipment under normal
operating conditions. Where failure or malfunction of a VFD67 drive could lead to an
abnormal operating condition that could cause personal injury or damage to the
equipment or other property, other devices, (limit or safety controls) or systems (alarm or
supervisory) intended to warn of, or protect against, failure or malfunction of the VFD67
drive must be incorporated into and maintained as part of the control system.
WARNING
Risk of thermal damage
The VFD67 control can generate and dissipate significant heat. Mount the control on a
metal, concrete, or ciderblock mounting surface. Mounting the VFD67 control on
surfaces made of wood or other heat-sensitive material may result in damage to the
mounting surface.
CAUT ION
Risk of equipment damage
Motors used with the VFD67 controls must meet certain specifications for proper
performance and operation. Motors that do not meet these specifications may be
damaged.
CAUT ION
Risk of electrical shock
The printed wiring board and its components are at AC line voltage. Direct or indirect
contact with line voltage can result in personal injury or death.
WARNING
8 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
Risk of electrical shock
The VFD67 drive remains electrically charged for a period of time after the power is
removed. To avoid possible electrical shock, wait at least 10 minutes after AC supply
power has been disconnected from the VFD67 drive before servicing the control. Failure
to wait until the VFD67 drive fully discharges could cause electrical shock, personal
injury, or death.
WARNING
Risk of equipment damage
Connect each of these items to the VFD67 drive using a separate conduit for each set
of wires:
Line voltage supply power
Line voltage output power to motor
Low voltage signals from input devices
Running different voltage and frequency wires in the same conduit can create electronic
noise or harmonics, which may damage the condenser fan motors.
CAUT ION
VFD67 Size A to D Getting Started Guide 9
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
2Rating Data
Figure 2-1 Model code explanation (Size A to D)
Table 2-1 VFD67, 1 phase, 100 to 120VAC ±10%, 48 to 62Hz units
*No dynamic braking available with VFD67 size A 110V drive.
Table 2-2 VFD67, 1 phase, 200 to 240VAC ±10%, 48 to 62Hz units
Table 2-3 VFD67, 1 and 3 phase, 200 to 240VAC ±10%, 48 to 62Hz units
*Dual rated models.
VFD67
Frame size / Enclosure:
Nominal motor rating (hp):
Drive voltage rating (V):
Model: VFD67
A A A
A = 6.1 x 3 x 5.7in, NEMA 1
B = 8.1 x 3.4 x 6.2in, NEMA 1
C = 10.2 x 4 x 6.8in, NEMA 1
D = 13.2 x 4.5 x 7.9in, NEMA 1
A = 0.33
B = 0.5
C = 0.75
D = 1.0
E = 1.5
F = 2.0
G = 3.0
H = 4.0
J = 5.0
K = 7.5
M = 10
A = 115
B = 230
C = 460
Model
Number
Nominal motor
power
Input fuse
rating
Typical full
load input
current
100% RMS
output current
A
150% overload
current for 60s
A
Minimum
braking
resistor value
kW hp A A Heavy Duty
Ω
VFD67AAA 0.25 0.33 10 7.5 1.7 2.55
N/A*
VFD67ABA 0.37 0.5 15 11 2.2 3.3
VFD67ADB 0.75 1.0 25 19.6 4.0 6.0
28
VFD67AEB 1.1 1.5 32 24.0 5.2 7.8
Model
Number
Nominal motor
power
Input fuse
rating
Typical full
load input
current
100% RMS
output current
A
150% overload
current for 60s
A
Minimum
braking
resistor value
kW hp A A Heavy Duty
Ω
VFD67BAA 0.25 0.33 6 4.3 1.7 2.55
68
VFD67BBA 0.37 0.5 10 5.8 2.2 3.3
VFD67BCA 0.55 0.75 10 8.1 3.0 4.5
VFD67BDA 0.75 1.0 16 10.5 4.0 6.0
Model
Number
Nominal
motor power
Input fuse
rating
A
Typical full
load input
current
A
Maximum
continuous
input current
A
100% RMS
output
current
A
150% overload
current for 60s
A
Minimum
braking
resistor
value
Ω
kW hp 1ph 3ph 1ph 3ph 1ph 3ph Heavy Duty
VFD67BEB* 1.1 1.5 16 10 14.2 6.7
9.2 5.2 7.8 28
VFD67BFB* 1.5 2.0 20 16 17.4 8.7
12.6 7.0 10.5 28
VFD67BGC* 2.2 3.0 25 20 23.2 11.9
17.0 9.6 14.4 28
VFD67BJD 4.0 5.0
20 15.7 19.5 17.0 25.5 20
10 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
Table 2-4 VFD67, 3 phase, 380 to 480VAC ±10%, 48 to 62Hz units
Output frequency
0 to 1500Hz
Output voltage
110V drives:
3 phase, 0 to 240Vac (240 Vac maximum set by Pr 08).
200V and 400V drives:
3 phase, 0 to drive rating (240 or 480Vac maximum set by Pr 08).
Model
Number
Nominal
motor power
Input
fuse
rating
Typical full
load input
current
Maximum
continuous
input current
100% RMS
output
current
A
150% overload
current for 60s
A
Minimum
braking
resistor value
kW hp A A A Heavy Duty
Ω
VFD67CBB 0.37 0.5 6 1.7 2.5 1.3 1.95 100
VFD67CCB 0.55 0.75 6 2.5 3.1 1.7 2.55 100
VFD67CDB 0.75 1.0 6 3.1 3.75 2.1 3.15 100
VFD67CEB 1.1 1.5 6 4.0 4.6 2.8 4.2 100
VFD67CFB 1.5 2.0 10 5.2 5.9 3.8 5.7 100
VFD67CGC 2.2 3.0 16 7.3 9.6 5.1 7.65 100
VFD67CHC 3.0 4.0 16 9.5 11.2 7.2 10.8 55
VFD67CJC 4.0 5.0 16 11.9 13.4 9.0 13.5 55
VFD67CKD 5.5 7.5 16 12.4 14.3 13.0 19.5 53
VFD67CMD 7.5 10.0 20 15.6 16.9 16.5 24.75 53
110V drives contain a voltage doubler circuit on the AC input.
NOTE
The output voltage can be increased by 20% during deceleration. See Pr 30 on page 33
NOTE
The maximum continuous current inputs are used to calculate input cable and fuse
sizing. Where no maximum continuous input currents are indicated, use the typical full
load input current values.
NOTE
VFD67 Size A to D Getting Started Guide 11
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
3 Mechanical Installation
The drive complies with the requirements of IP20 as standard.
Figure 3-1 VFD67 dimensions
Mounting holes: 4 x M4 holes (size A to C), 4 x M5 holes (size D)
Table 3-1 VFD67 dimensions
*Size C and D are not DIN rail mountable.
The DIN rail used should conform to DIN46277-3.
Enclosure
The drive is intended to be mounted in an enclosure which prevents access except by
trained and authorized personnel, and which prevents the ingress of contamination. It is
designed for use in an environment classified as pollution degree 2 in accordance with
IEC 60664-1. This means that only dry, non-conducting contamination is acceptable.
WARNING
A
B
I
G
D
C
H
E
E
F
G
C
Drive
size
ABCDEFGH*I
mm in mm in mm in mm in mm in mm in mm in mm in mm in
A 140 5.51 154 6.06 11 0.43 64 2.52 75 2.95 145 5.71 104 4.09 143 5.63
B 190 7.48 205 8.07 10.9 0.43 65.9 2.6 85 3.35 77 3.0 156 6.15 155.5 6.12 194 7.64
C 240 9.45 258 10.16 10.4 0.41 81.1 3.2 100 3.94 91.9 3.62 173 6.81
244 9.61
D 300 11.81 335 13.19 14.5 0.57 100.5 3.96 115 4.53
198 7.80 315 12.4
If DIN rail mounting is used in an installation where the drive is to be subjected to shock
or vibration, it is recommended that the bottom mounting screws are used to secure the
drive to the back plate.
If the installation is going to be subjected to heavy shock and vibration, then it is
recommended that the drive is surface mounted rather than DIN rail mounted.
NOTE
The DIN rail mounting mechanism has been designed so no tools are required to install
and remove the drive from a DIN rail. Please ensure the top mounting lugs are located
correctly on the DIN rail before installation is initiated.
NOTE
12 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
Figure 3-2 Minimum mounting clearances
*This is the minimum spacing between drives at the base of the drive where it is
mounted against a back plate.
Figure 3-3 Features of the drive (size B illustrated)
Drive size
ABC
mm in mm in mm in
A
10 0.39
00
100 3.94
B (0.75kW) 10* 0.39*
B (1.1kW) or B (110V) 0 0
C 50* 1.97*
D00
A
A
B
C
C
Display
SmartStick
slot
Power
terminals
Control
terminals
Serial
communications
port connector
EMC filter tab
VFD67 Size A to D Getting Started Guide 13
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
4 Electrical Installation
4.1 Power terminal connections
Figure 4-1 Size A power terminal connections
Figure 4-2 Sizes B, C and D power terminal connections
*For further information, see section 4.3.1 Internal EMC filter on page 15.
**The other PE terminal can be used for connecting cable shields to ground if required.
Optional
ground
connection
+
L1 L2/N U V W PE
Optional
line reactor
Braking
resistor
Mains supply
Optional
Thermal
protection
device
Stop
Start/
Reset
PE**
Supply
ground
Internal
EMC filter
*
Optional
EMC filter
-DC
Optional ground
connection
Supply
ground
Optional
EMC filter
Optional
line reactor
Fuses
Mains supply
L3/N U V W
+
PE PE
L1 L2
_
L3/N U V WL1 L2
+
PE PE**
_
Internal
EMC filter
*
Start/
Reset
Braking
resistor
Optional
Thermal
protection
device
Stop
On the VFD67 size B 110V drives, the supply should be connected to L1 and L3/N.
NOTE
14 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
4.2 Ground leakage
The ground leakage current depends upon the internal EMC filter being installed. The
drive is supplied with the filter installed. Instructions for removal of the internal EMC filter
are given in section 4.3.2 Removing the internal EMC filter .
With internal EMC filter installed
30
μ
A DC (10M
Ω
internal bleed resistor, relevant where DC leakage current is being measured)
Size A
1 phase 110V drives
4mA AC at 110V, 50Hz (proportional to supply voltage and frequency)
1 phase 200V drives
10mA AC at 230V, 50Hz (proportional to supply voltage and frequency)
Size B
1 phase 110V drives
10mA AC at 110V, 50Hz (proportional to supply voltage and frequency)
Size B and C
1 phase 200V drives
20mA AC at 230V, 50Hz (proportional to supply voltage and frequency)
On the VFD67 size D, the internal EMC filter is connected to the -DC Bus.
NOTE
The braking terminals are not available on the size A 110V drive.
NOTE
Fuses/MCB
The AC supply to the drive must be installed with suitable protection against overload
and short circuits. Failure to observe this requirement will cause risk of fire.
WARNING
The drive must be grounded by a conductor sufficient to carry the prospective fault
current in the event of a fault. See also the warning in section 4.2 Ground leakage
relating to ground leakage current.
WARNING
To avoid a fire hazard and maintain validity of the UL listing, adhere to the specified
tightening torques for the power and ground terminals. Refer to the table below.
WARNING
Frame size Maximum power terminal screw torque
A 0.5 N m / 4.4 lb in
B, C and D 1.4 N m / 12.1 lb in
Braking resistor: High temperatures and overload protection
Braking resistors can reach high temperatures. Locate braking resistors so that damage
cannot result. Use cable having insulation capable of withstanding the high temperatures.
It is essential that the braking resistor be protected against overload caused by a failure
of the brake control. Unless the resistor has in-built protection, a circuit like those shown
in
Figure 4-1
and
Figure 4-2
should be used, where the thermal protection device
disconnects the AC supply to the drive. Do not use AC relay contacts directly in series
with the braking resistor circuit, because it carries DC.
WARNING
When connecting single phase to a dual rated 200V unit, use terminals L1 and L3.
NOTE
For control terminal connections, see Pr 05 on page 24.
NOTE
For information on the internal EMC filter, see section 4.3.1 Internal EMC filter .
NOTE
VFD67 Size A to D Getting Started Guide 15
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
3 phase 200V drives
8mA AC at 230V, 50Hz (proportional to supply voltage and frequency)
3 phase 400V drives
8.2mA AC at 415V, 50Hz (proportional to supply voltage and frequency)
Size D
1 phase 200V drives
20.5mA AC at 230V, 50Hz (proportional to supply voltage and frequency)
3 phase 200V drives
8mA AC at 230V, 50Hz (proportional to supply voltage and frequency)
3 phase 400V drives
10.5mA AC at 415V, 50Hz (proportional to supply voltage and frequency)
With internal EMC filter removed
<1mA
4.2.1 Use of earth (ground) leakage circuit breakers (ELCB) / ground fault
circuit interrupter (GFCI) / residual current device (RCD)
There are three common types of ELCB/RCD:
Type AC - detects AC fault currents
Type A - detects AC and pulsating DC fault currents (provided the DC current
reaches zero at least once every half cycle)
Type B - detects AC, pulsating DC and smooth DC fault currents
Type AC should never be used with drives
Type A can only be used with single phase drives
Type B must be used with three phase drives
4.3 EMC
4.3.1 Internal EMC filter
It is recommended that the internal EMC filter is kept in place unless there is a specific
reason for removing it.
If the drive is to be used on an IT supply, then the filter must be removed.
The internal EMC filter reduces radio-frequency emissions into the mains supply. Where
the motor cable is short, it permits the requirements of EN61800-3 to be met for the
second environment.
For longer motor cables, the filter continues to provide a useful reduction in emission
level, and when used with any length of shielded cable up to the limit for the drive, it is
unlikely that nearby industrial equipment will be disturbed. It is recommended that the
filter be used in all applications unless the ground leakage current is unacceptable or
the above conditions are true.
When the internal EMC filter is used on the VFD67 size D, the motor cables (U, V and
The above leakage currents are just the leakage currents of the drive with the internal EMC
filter connected and do not take into account any leakage currents of the motor or motor cable.
NOTE
In both cases, there is an internal voltage surge suppression device connected to
ground. Under normal circumstances, this carries negligible current.
NOTE
When the internal EMC filter is installed, the leakage current is high. In this case, a
permanent fixed ground connection must be provided using two independent conductors
each with a cross-section equal to or exceeding that of the supply conductors. The drive
is provided with two ground terminals to facilitate this. The purpose is to prevent a safety
hazard occurring if a connection is lost. Both ground connections are required to meet
the required european standard.
WARNING
16 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
W) need to be fed twice through a ferrite ring (provided with the drive), so that the drive
meets the requirements of operating in the second environment.
4.3.2 Removing the internal EMC filter
Figure 4-3 Removal and re-fitting of internal EMC filter
4.3.3 Further EMC precautions
Further EMC precautions are required if more stringent EMC emission requirements
apply:
Operation in the first environment of EN 61800-3
Conformity to the generic emission standards
Equipment which is sensitive to electrical interference operating nearby
In this case it is necessary to use:
The optional external EMC filter
A shielded motor cable, with shield clamped to the grounded metal panel
A shielded control cable, with shield clamped to the grounded metal panel
A full range of external EMC filters is also available for use with VFD67.
4.4 Control terminals I/O specification
Internal
EMC filter
Tab fully inserted:
EMC filter fitted
Internal
EMC filter
B
Tab fully extended:
EMC filter disconnected
A
The control circuits are isolated from the power circuits in the drive by basic insulation
(single insulation) only. The installer must ensure that the external control circuits are
insulated from human contact by at least one layer of insulation (supplementary
insulation) rated for use at the AC supply voltage.
WARNING
If the control circuits are to be connected to other circuits classified as Safety Extra Low
Voltage (SELV) (e.g. to personal computer), an additional isolating barrier must be
included in order to maintain the SELV classification.
WARNING
See Pr 05 on page 24 (Drive configuration) for terminal connection / set-up diagrams and
details.
NOTE
The digital inputs are positive logic only.
NOTE
VFD67 Size A to D Getting Started Guide 17
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
0-20: Current input 0 to 20mA (20mA full scale)
20-0: Current input 20 to 0mA (0mA full scale)
4-20: Current input 4 to 20mA with current loop loss (cL1) trip (20mA full scale)
20-4: Current input 20 to 4mA with current loop loss (cL1) trip (4mA full scale)
4-.20:Current input 4 to 20mA with no current loop loss (cL1) trip (20mA full scale)
20-.4:Current input 20 to 4mA with no current loop loss (cL1) trip (4mA full scale)
VoLt: 0 to 10V input
The analog inputs are unipolar.
NOTE
T1
0V common
T2
Analog input 1 (A1), either voltage or current (see Pr 16)
Voltage: Current input 0 to 10V / mA as parameter range
Parameter range 4-20, 20-4, 0-20, 20-0, 4-.20, 20-.4, VoLt
Scaling
Input range automatically scaled to Pr 01 Minimum set
speed / Pr 02 Maximum set speed
Input impedance 200Ω (current) / 100kΩ (voltage)
Resolution 0.1%
T3
+10V reference output
Maximum output current 5mA
T4
Analog input 2 (A2), either voltage or digital input
Voltage: Digital input 0 to +10V / 0 to +24V
Scaling (as voltage input)
Input range automatically scaled to Pr 01 Minimum set
speed / Pr 02 Maximum set speed
Resolution 0.1%
Input impedance 100kΩ (voltage) / 6k8 (digital input)
Normal threshold voltage (as digital input) +10V (positive logic only)
T5
Status relay - Drive ok (Normally open)
T6
Voltage rating 240Vac/30Vdc
Current rating
2Aac 240V
4Adc 30V resistive load (2A 35Vdc for UL requirements)
0.3Adc 30V inductive load (L/R = 40ms)
Contact isolation 1.5kVac (over voltage category II)
Operation of contact
OPEN
AC supply removed from drive
AC supply applied to drive with drive in tripped condition
CLOSED
AC supply applied to drive with drive in a 'ready to run' or
'running' condition (not tripped)
Provide fuse or other over-current protection in status relay circuit.
WARNING
18 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
If the enable terminal is opened, the drive’s output is disabled and the motor will coast to
a stop. The drive will not re-enable for 1.0s after the enable terminal is closed again.
Following a drive trip, opening and closing the enable terminal will reset the drive. If the
run forward or run reverse terminal is closed, the drive will run straight away.
Following a drive trip and a reset via the stop/reset key, the enable, run forward or run
reverse terminals will need to be opened and closed to allow the drive to run. This
ensures that the drive does not run when the stop/reset key is pressed.
The enable, run forward and run reverse terminals are level triggered apart from after a
trip where they become edge triggered.
If the enable and run forward or enable and run reverse terminals are closed when the
drive is powered up, the drive will run straight away up to a set speed.
If both the run forward and run reverse terminals are closed, the drive will stop under the
control of the ramp and stopping modes set in Pr 30 and Pr 31.
B1
Analog voltage output - Motor speed
Voltage output 0 to +10V
Scaling
0V represents 0Hz/rpm output
+10V represents the value in Pr 02 Maximum set speed
Maximum output current 5mA
Resolution 0.1%
B2
+24V output
Maximum output current 100mA
B3
Digital output - User selectable Pr 35
Voltage range 0 to +24V
Maximum output current 50mA at +24V (current source)
The total available current from the digital output plus the +24V output is 100mA.
NOTE
B4
Digital Input - User selectable
B5
Digital Input - User selectable
B6
Digital Input - User selectable
B7
Digital Input - User selectable
Logic Positive logic only
Voltage range 0 to +24V
Nominal threshold voltage +10V
VFD67 Size A to D Getting Started Guide 19
Issue Number: 1 www.johnsoncontrols.com
Safety
Information
Rating Data
Mechanical
Installation
Electrical
Installation
Keypad and
Display
Parameters
Quick Start
Commissioning
Diagnostics Parameter List
Technical
specifications
UL Listing
Information
5 Keypad and Display
The keypad and display are used for the following:
Displaying the operating status of the drive
Displaying a fault or trip code
Reading and changing parameter values
Stopping, starting and resetting the drive
Figure 5-1 Keypad and display
on the display indicates if motor map 1 or 2 is selected.
5.1 Programming keys
The MODE key is used to change the mode of operation of the drive.
The UP and DOWN keys are used to select parameters and edit their values. In
keypad mode, they are used to increase and decrease the speed of the motor.
5.2 Control keys
The START key is used to start the drive in keypad mode.
The STOP/RESET key is used to stop and reset the drive in keypad mode. It can
also be used to reset the drive in terminal mode.
M
M
It is possible to change parameter values more quickly.
NOTE
20 VFD67 Size A to D Getting Started Guide
www.johnsoncontrols.com Issue Number: 1
5.3 Selecting and changing parameters
Figure 5-2
When in Status mode, pressing and holding the MODE key for 2 seconds will
change the display from displaying a speed indication to displaying load indication and
vice versa.
Pressing and releasing the MODE key will change the display from status mode to
parameter view mode. In parameter view mode, the left hand display flashes the
parameter number and the right hand display shows the value of that parameter.
Pressing and releasing the MODE key again will change the display from parameter
view mode to parameter edit mode. In parameter edit mode, the right hand display
flashes the value in the parameter being shown in the left hand display.
Pressing the MODE key in parameter edit mode will return the drive to the
parameter view mode. If the MODE key is pressed again then the drive will return to
status mode, but if either of the up or down keys are pressed to change the
parameter being viewed before the MODE key is pressed, pressing the MODE
key will change the display to the parameter edit mode again. This allows the user to
very easily change between parameter view and edit modes while commissioning the
drive.
This procedure is written from the first power up of the drive and assumes no terminals
have been connected, no parameters have been changed and no security has been set.
NOTE
M
STATUS MODE
or
PARAMETER VIEW MODE
Select parameter to view
orPress
Parameter number flashing
PARAMETER EDIT MODE
Change parameter value
or
Press
Parameter value flashing
M
M
Press and
hold for 2s
M
M
Parameters
saved
Press and
release
M
Hold
for 2s
4 mins
timeout
/
/
/
Press and
release
Press and
release
Press and
release
M
M
M
M
M
M
M
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52

Johnson Controls VFD67 Series Getting Started Manual

Type
Getting Started Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI