SPECIFICATIONS
Electrical Characteristics
External Supply Voltage 18 – 30 VDC
Remote Reset Time External monitor must be pulled low for a minimum of 100 msec
Power Reset 1 sec
Relay Contact Ratings 3.0A @ 30VDC, 0.5A @125VAC
Environmental Ratings
Operating Temperature 32°F (0°C) to 100°F (38°C) – Factory tested to 131F (55C)
Sampled Air Temperature -4°F (-20°C) to 140°F (60°C)
Humidity 10 to 95% non-condensing
IP Rating IP30
9440X FAAST
Fire Alarm Aspiration Sensing Technology
®
INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-6500-000
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
The purpose of this document is to provide practical information for
mounting and connecting to FAAST XT PRO. For full product informa-
tion, which includes installation guidelines, instructions for safe use,
smoke sector identification procedures, and warranty and safety informa-
tion, refer to the FAAST XT PRO Comprehensive User Guide available at
systemsensor.com/iFAASTXTPROuserguide or by scanning the QR code.
ITEMS INCLUDED WITH UNIT
FAAST XT PRO (9440X) unit
Mounting bracket and hardware
Installation and Maintenance Instructions
USB interface cable
PipeIQ® software, comprehensive manual, and other helpful documents
may be downloaded at systemsensor.com/faast
CONNECTING TO FAAST XT PRO
FAAST XT PRO requires a configuration download from PipeIQ in order to ini-
tialize. This connection can be achieved using either the USB port located on
the front of the device, or the Ethernet port located inside the wiring cabinet.
CONNECTING TO FAAST XT PRO VIA USB
NOTE: In order to connect your computer to the FAAST XT PRO using a USB
connection, a USB driver must first be installed. The driver installation oc-
curs during the installation of PipeIQ version 2.0 or later. Once the driver is
installed, connect to the device using the following steps.
1. Launch PipeIQ. (Download from systemsensor.com/faast.)
2. Create a new project and select FAAST XT PRO device, or open an existing
project.
3. Expand the tree view in the left side navigation pane to reveal the device.
4. Right click on the device and select ‘Connect Device’.
5. Select ‘Admin’ and enter the password – the default password is ‘pass
-
word’ – then click ‘Connect’.
6. Upon connection, a green dot will appear on the device icon in the navi
-
gation tree.
CONNECTING TO FAAST XT PRO VIA ETHERNET
Default Device IP Configuration
IP Address: 192.168.1.10
Subnet Mask: 255.255.255.0
Default Gateway: 192.168.1.1
Primary DNS: 0.0.0.0
Secondary DNS: 0.0.0.0
CONFIGURE YOUR PC
Your PC will need to be sitting on the same local area network as the FAAST XT
PRO device in order to establish communication. Change your PC’s IP address
to 192.168.1.15 by:
1. Accessing your network setting in your PC’s control panel.
2. Open ‘Local Area Connection’ settings and select ‘Properties’.
3. Select ‘Internet Protocol Version 4 (TCP/IPv4) and then select ‘Properties’.
4. Select ‘Use the following IP address and enter 192.168.1.15. If the sub
-
net mask does not automatically populate, enter 255.255.255.0 into the
subnet mask field.
5. Click OK, and close out of the network menus.
Important Note: Before changing your PC’s IP address, be sure to take note of
whether your IP is currently dynamically set, or is a static IP address. If your PC is
assigned a static IP address, make note of the IP address and subnet mask so that
you can change back to the proper settings after the FAAST XT PRO is configured.
CONNECT USING PIPEIQ
1. Launch PipeIQ. (Download from systemsensor.com/faast.)
2. Create and save a new project, or open an existing project.
3. Expand the tree view in the left side navigation pane to reveal the device
4. Right click on the device and select ‘Connect Device’.
5. Select Host/IP and type in the device’s IP address - default is 192.168.1.10.
6. Select ‘Admin’ and enter the password – the default password is ‘pass
-
word’ – then press ‘Connect’.
7. Upon connection, a green dot will appear on the device icon in the navi
-
gation tree.
INSTALLATION
This equipment must be installed in accordance with all local and national
codes and regulations.
PIPE INSTALLATION
The pipe layout is designed using the PipeIQ software package. Refer to the
Comprehensive Instruction Manual to design the pipe network. All pipe must
be installed in accordance with local and national codes and regulations. The
pipe network should be complete before proceeding with the physical and
electrical system installation.
2 I56-6500-000
10-05
PHYSICAL UNIT INSTALLATION
WARNING
Make sure that there are no pipes or electrical wires within the wall before
drilling any mounting holes
SECURING THE MOUNTING BRACKET
The typical mounting location for the FAAST XT PRO unit is on the wall. The
unit is mounted to the wall using the enclosed mounting bracket. Figure 1
shows the wall mounting bracket. For easier access to the FAAST XT PRO
unit, it is preferred to position the mounting bracket in an easily accessible
location.
1. Place the mounting bracket on the wall in the desired location and use it
as a template to locate the necessary mounting holes.
2. Mark the hole locations and remove the bracket. It is recommended to
secure the bracket using the 3 outer mounting holes.
3. Using a drill and the proper size bit for your mounting hardware, drill
the necessary holes.
4. Use appropriate fasteners to accommodate the mounting surface and
FAAST XT PRO device weight.
5. Secure the bracket to the wall.
MOUNTING THE DETECTOR TO THE BRACKET
Once the mounting bracket is attached, the unit is ready to be mounted on to
the bracket. Perform the following procedure to mount the unit.
1. Before installing the unit onto the bracket, remove the appropriate con
-
duit caps from the top or bottom left side of the unit to match the orien-
tation of the wiring.
2. Line up the unit with the three mounting clips and the mounting studs
on the left side.
3. Push the unit down onto the mounting clips and secure it with the sup
-
plied washer and nut on the mounting studs protruding through the
mounting slots shown in Figure 2.
CONNECTING THE AIR SAMPLING PIPE
ATTENTION
Detailed pipe network information and best practices can be found in the Pipe
Installation Guide, available for download at systemsensor.com/faast
The input and output ports are designed to accept nominal one inch pipe
(25mm). The input and output ports are tapered to provide fast, easy, pushfit
connection of the sampling pipe to the unit. Perform the following procedure
to connect the air sampling pipe to the unit.
1. Square off and de-burr the end of the sampling pipe. Ensure that the pipe
is free from any particles that might interfere with the pipe connection.
2. Remove the input plug from the input port being used (either the top or
bottom of the unit).
3. Insert the air sampling pipe into the port, ensuring a snug fit. DO NOT
glue these pipes.
EXHAUST PIPE
The device should always be exhausted in to the space that it is monitoring.
There are some circumstances where it may be necessary to connect a pipe to
the exhaust port to divert the exhaust away from the location of the unit. Add-
ing as little as 2ft of exhaust pipe also acts as a muffler for the fan – ensuring
quieter operation. The output ports are tapered the same as the input ports, to
provide fast, easy, push-fit connection of an exhaust pipe to the unit. Perform
the following procedure to connect the exhaust pipe to the unit.
1. Square off and de-burr the end of the exhaust pipe. Ensure that the pipe
is free from any particles that might interfere with the pipe connection.
2. Remove the plug from the exhaust port being used (either the top or
bottom of the unit).
3. Insert the air exhaust pipe into the port, ensuring a snug fit. DO NOT
glue these pipes.
FIGURE 1: WALL MOUNTING BRACKET
11.15in (28.3cm)
11.17in (28.4cm)
3.23in (8.2cm)
3.23in (8.2cm)
.300 ± .010 (.76cm ± .3cm)
ASP115-01
FIGURE 2: MOUNTING SLOTS FOR MOUNTING STUDS
ASP116-00
3 I56-6500-000
10-05
WIRING
WARNING
Before working on the FAAST XT PRO system, notify all required authorities
that the system will be temporarily out of service. Make sure all power is
removed from the system before opening the unit. All wiring must be in ac-
cordance with local codes.
POWER CABLES
Use the power ratings of the unit to determine the required wire sizes for each
connection. Use the power ratings of the connected products to determine the
wire size.
CONDUIT USAGE
If electrical conduit is used for system wiring, terminate the conduits at the
cable entry ports on the top or bottom of the unit, using the appropriate con-
duit connectors.
1. Run all wiring, both power and alarm, through the conduit and into the
left side of the unit enclosure, as seen in Figure 3.
2. Attach the appropriate wires to the supplied Euro connector. Follow
appropriate local codes and electrical standards for all cabling.
3. Plug the appropriate connector into the mating connector on the unit.
CABLING REQUIREMENTS
The FAAST XT PRO system provides a series of Euro style pluggable terminals,
located behind the left side door of the unit. Refer to Table 1 for the proper
electrical connections to the unit. Refer to Figure 4 for a typical connection for
monitoring the FAAST XT PRO system at a Fire Alarm Control Panel (FACP).
FIGURE 3. POWER AND ALARM CONNECTION BLOCK FIGURE 4. FACP WIRING DIAGRAM
TABLE 1. TERMINAL DESIGNATIONS
TERMINAL
BLOCK
T1
External Power – Powers Aspirating Smoke Detector
T2
Not used.
T3
RS 485 Rx
Rx and Tx can be wired in a half duplex configuration
T4
RS 485 Tx
Rx and Tx can be wired in a half duplex configuration
T5
Alert Relay – Maintains state on loss of power
T6
Action1 Relay – Maintains state on loss of power
T7
Action2 Relay – Maintains state on loss of power
T8
Fire1 Relay – Maintains state on loss of power
T9
Fire2 Relay – Maintains state on loss of power
T10
Minor Fault Relay – Maintains state on loss of power
T11
Urgent Relay – Always reverts to reset on loss of power
T12
Isolate Relay – Maintains state on loss of power
T13
External Monitor
N.C.
N.O.
C.
Fire2 Relay
Contacts
(T9)
Fire Panel (FACP) typical connection
FAAST XT
Fire Alarm Aspiration Sensing Technology®
for monitoring of device
Alarm
Short = Fire
Open = Fault
EOL
N.C.
N.O.
C.
Fire1 Relay
Contacts
(T8)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Action2
Relay
Contacts
(T7)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Action1
Relay
Contacts
(T6)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Alert Relay
Contacts
(T5)
Alarm
Short = Fire
Open = Fault
N.C.
N.O.
C.
Isolate Relay
Contacts
(T12)
Supervisory
Short = Isolate
Open = Fault
N.C.
N.O.
C.
Urgent Relay
Contacts
(T11)
Short = Urgent Fault
Open = Fault
N.C.
N.O.
C.
Minor Relay
Contacts
(T10)
Short = Minor Fault
Open = Fault
FACP
Supervisory
Supervisory
EOL
EOL
EOL
EOL
EOL
EOL
EOL
External
Monitor
(T13)
N.C.
B.
B.
A.
N.O.
(Reset)
Panel
Remote
Reset
C.
47kΩ
ASP114-01
ASP18-24
4 I56-6500-000
©2016 System Sensor. 10-05
System Sensor®, PipeIQ®, and FAAST Fire Alarm Aspiration Sensing Technology® are registered trademarks of Honeywell International, Inc.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa
-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
This Class B digital apparatus complies with Canadian ICES-003.
FCC STATEMENT
System Sensor warrants its enclosed smoke detector to be free from defects in materials
and workmanship under normal use and service for a period of three years from date
of manufacture. System Sensor makes no other express warranty for this smoke detec
-
tor. No agent, representative, dealer, or employee of the Company has the authority to
increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of the smoke
detector which is found to be defective in materials or workmanship under normal use
and service during the three year period commencing with the date of manufacture.
After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
Authorization number, send defective units postage prepaid to: Honeywell, 12220 Rojas
WARRANTY
Drive, Suite 700, El Paso, TX 79936, USA. Please include a note describing the malfunc-
tion and suspected cause of failure. The Company shall not be obligated to repair or
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
This aspiration detector does not produce any hazardous laser radiation and is certified
as a Class 1 laser product under the U.S. Department of Health and Human Services
(DHHS) Radiation Performance Standard according to the Radiation Control for Health
and Safety Act of 1968. Any radiation emitted inside the smoke detector is completely
within the protective housings and external covers.
The laser beam cannot escape from the detector during any phase of operation.
The Center of Devices and Radiological Health (CDRH) of the U. S. Food and Drug
Administration implemented regulations for laser products on August 2, 1976. These
regulations apply to laser products manufactured after August 1, 1976. Compliance is
mandatory for products marketed in the United States.
LASER SAFETY INFORMATION
The use of all FAAST products (configuration, design, use and maintenance) must be performed in accordance with the technical documentation, General Terms and Conditions and
local regulations and/or directives for design, installation and maintenance of fire alarm systems. Product Manuals, User Guides, White Papers, CAD Drawings, Datasheets, Engineering
specifications are available from www.systemsensor.com/faast. The performance of this system is dependent upon the pipe network. Any extensions or modifications to the designed
installation may cause improper operation. The operational effects of such changes shall be verified. A design tool is available from System Sensor webpage.
Class 1, Div 2 - RJ45 Connector is for maintenance use only and shall not be used while in a Hazardous Location unless power has been removed or the area is known to be non-
hazardous. These units are tested and regulatory approved to allow the pipe networks to be installed in corrosive or hostile environments. The aspiration unit itself should operate in
a controlled environment as per the specifications listed in the manual. The detector unit is not suitable to be installed in hostile environments.
Exposure of the detector to silicone vapor must be avoided as it may permanently inhibit the pipe identification sensor from detecting fire gases. Sources of silicone vapor include
furniture polish, spray lubricants, and flexible uncured gaskets and sealants.
Avoid installing the detector in areas that have elevated levels of organic chemical vapors such as alcohol, as this will affect the baseline of the channel identification sensors. Other
gases known to have an effect on MOS sensors that FAAST XT PRO uses for identifying the smoke in individual inlets, are oxidizing agents such as chlorine, ozone, nitrogen oxides.
While these gases will not permanently damage the sensors and will not have an impact on the overall smoke detection, they may impair the ability to identify the inlet affected by
smoke.
GENERAL WARNINGS
SYSTEM POWERING
The following procedure describes how to initially power up the FAAST XT PRO
system.
1. Unplug the unit’s power connector to the unit before turning on the
power.
2. Turn on the power.
3. Check the voltage at the connector. Make sure it is within the required
voltage range.
4. If wiring is not connected to the external monitor terminal, install a
47k resistor (provided with the unit) into the terminal block and fit it
into the T6 terminal.
5. If the voltage is within the proper range, reconnect the power connector
to the unit.
6. Verify the system fan starts up and air begins to flow out of the exhaust
port. The user interface will provide the device status.
7. Connect a computer, with PipeIQ installed, to the unit using either the
USB connection on the front of the device, or the Ethernet port located in
the left side wiring door. (See ‘Connecting to FAAST XT PRO’ for detailed
connection instructions.)
8. Use the PipeIQ software to set up the unit configuration required for the
particular application.
9. The PC may now be disconnected unless a permanent networked con
-
nection is desired.
10. The device will establish an airflow baseline during the first five minutes
of operation after powering on, following the successful download of a
configuration to the device from PipeIQ, or after initiating Baseline Reset
from Functions menu on the unit’s display. During the initial baseline
period the LCD will display Baseline message.
The calculated baseline is stored in the device’s non-volatile memory and
is used to monitor changes in the system’s airflow that may be caused
my dust build up, broken piping, clogged holes, etc. Therefore, it is im
-
portant to verify that the system is setup and installed per the PipeIQ
design file and meets the requirement of the local codes and authorities.
The Baseline message is also displayed after power on reset, following
the initial baseline period. During the five minutes after power up the
device is monitoring the system to determine the current airflow baseline
of the system. Once the current airflow baseline is established, it is com
-
pared to the initial baseline stored in non-volatile memory to determine
the overall health of the system.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4

System Sensor FAAST XT Pro I56-6500 User manual

Category
Fire protection
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI