reserved
Document information
File name : ADD_ABB_PVA11-31T_10-20kVA_EN_REV-A.docx
PowerValue 11/31 T 10-20 kVA
Date of issue
: 28.04.2016
Article number : N/A
Document number
: N/A
Revision
: A
Foreword
IMPORTANT
This document is intended to supplement the following user manuals:
• PowerValue 11/31 T 10-20 kVA
version: 4NWP100559R0001_OPM_ABB_PVA31-11-T_10-20kVA_EN_140626
New information include:
• PowerValue 11/31 T 10-20 kVA
version: 4NWP100559R0001_OPM_ABB_PVA31-11-T_10-20kVA_EN_140626
o chapter 6.3.1 addendum (see highlighted in red)
o Appendix A: CS121 SNMP card available parameters
PowerValue 11/31 T 10-20 kVA (version: 4NWP100559R0001_OPM_ABB_PVA31-11-T_10-
20kVA_EN_140626)
Chapter 6.3.1
6.3.1 Installing a Serial Network Management Card (optional)
Each UPS has a communication slot for an optional Serial Network Management (SNMP) Card. After
installing an SNMP card, an environmental monitoring probe can be connected to the UPS.
Note:
The UPS does not have to be shutdown before installing a communication card.
To install the Network Management Card, go through the following steps:
1. Remove the two screws that protect the communication slot of the UPS.
2. Insert the SNMP card into the communication slot.
3. Screw the SNMP card onto the slot using the screws removed in step 1.
Compatible SNMP card: CS121 Basic, CS121 ModBus, CS121 Advanced
For more information on the SNMP Cards, see the SNMP User's Manual.
For more details about
parameters available when using SNMP card with PowerValue 11/31 T 10-20 kVA
, please refer to
Appendix A