Eaton C441S User manual

Type
User manual
C441 PROFIBUS Module (C441Q, C441S, C441QS, C441SS)
User Manual
Effective July 2015
New Information
C441Q & C441S
C441QS & C441SS
C441 PROFIBUS Module User Manual
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com i
Disclaimer of Warranties and Limitation of Liability
The information, recommendations, descriptions and safety notations in this document are
based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all
contingencies. If further information is required, an Eaton sales office should be consulted.
Sale of the product shown in this literature is subject to the terms and conditions outlined in
appropriate Eaton selling policies or other contractual agreement between Eaton and the
purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR
MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING
CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE
OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME
PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including
negligence), strict liability or otherwise for any special, indirect, incidental or consequential
damage or loss whatsoever, including but not limited to damage or loss of use of equipment,
plant or power system, cost of capital, loss of power, additional expenses in the use of
existing power facilities, or claims against the purchaser or user by its customers resulting
from the use of the information, recommendations and descriptions contained herein. The
information contained in this manual is subject to change without notice.
Cover Photo: C441 PROFIBUS Module.
C441 PROFIBUS Module User Manual
ii C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Support Services
The goal of Eaton is to ensure your greatest possible satisfaction with the operation of our
products. We are dedicated to providing fast, friendly, and accurate assistance. That is why
we offer you so many ways to get the support you need. Whether it’s by phone, fax, or email,
you can access Eaton’s support information 24 hours a day, seven days a week. Our wide
range of services is listed below.
You should contact your local distributor for product pricing, availability, ordering, expediting,
and repairs.
Website
Use the Eaton website to find product information. You can also find information on local
distributors or Eaton’s sales offices.
Website Address
www.eaton.com/electrical
EatonCare Customer Support Center
Call the EatonCare Support Center if you need assistance with placing an order, stock
availability or proof of shipment, expediting an existing order, emergency shipments,
product price information, returns other than warranty returns, and information on local
distributors or sales offices.
Voice: 877-ETN-CARE (386-2273) (8:00 am–6:00 pm EST)
FAX: 800-752-8602
After-Hours Emergency: 800-543-7038
(6:00 pm–8:00 am EST)
Technical Resource Center
Voice:
877-ETN-CARE (386-2273) (8:00 am–5:00 pm EST)
FAX: 828-651-0549
C441 PROFIBUS Module User Manual
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com iii
Table of Contents
SAFETY
Definitions and Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
Hazardous High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
Warnings and Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi
OVERVIEW
PROFIBUS Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION
RATINGS
MOUNTING AND DIMENSIONS
C441Q and C441S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
CONNECTIONS AND SWITCH SETTINGS
Connecting the C441, C440, S611 and S811+ to a PROFIBUS Network . . . . . 9
Setting the PROFIBUS Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power and I/O Wiring Diagrams for the C441Q and C441S Modules . . . . . . . . 11
Power and I/O Wiring Diagrams for the C441QS and C441SS Modules . . . . . . 13
PROFIBUS Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Connecting and Disconnecting a C441 PROFIBUS Module from
the C440, C441, S611, S811+ or as a Stand-Alone I/O Module . . . . . . . . . . . 14
CONFIGURATION USING THE PROFIBUS CONFIGURATION FILE
C441 Motor Insight Overload Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . 16
C440 Overload Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
S611 Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
S811+ Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
PROFIBUS I/O PARAMETERS
Cyclic IO Data for C441, C440, S611, S811+ and Stand-Alone I/O . . . . . . . . . . 25
C441 Motor Insight Overload Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . 26
C440 Overload Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
S611 Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
S811+ Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
PROFIBUS DIAGNOSTIC TELEGRAMS
C441 Motor Insight Overload Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . 36
C440 Overload Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
S611 Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
S811+ Soft Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
APPLICATION EXAMPLE: OPERATING A C441 MOTOR INSIGHT WITH
ASIEMENSPLCONPROFIBUS-DP
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Creating a Project in Siemens Simatic Software . . . . . . . . . . . . . . . . . . . . . . . . 45
Setting up the Configuration File in the Simatic Software . . . . . . . . . . . . . . . . . 55
Assigning Tag Names to C441 Motor Insight I/O Addresses . . . . . . . . . . . . . . 56
Downloading the Program to the Siemens S7 PLC . . . . . . . . . . . . . . . . . . . . . . 60
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Additional Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
C441 PROFIBUS Module User Manual
iv C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
List of Figures
Figure 1. Installation Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2. C441Q and C441S Product Dimensions (Attached to C441 Base Unit) . . . . . 6
Figure 3. Mounting of Stand-Alone Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 4. Stand-Alone Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 5. C440 to a C441QS/SS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 6. S611 to a C441QS/SS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 7. Pin Out for PROFIBUS DB9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 8. Power and Modbus RS-485 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 9. C441Q: 24 Vdc Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 10. C441S: 120 Vac Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 11. C441QS—24 Vdc Input Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 12. C441SS—120 Vac Input Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 13. DIP Switch Service 3 Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
C441 PROFIBUS Module User Manual
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com v
List of Tables
Table 1. PROFIBUS Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table 2. Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 3. Environmental Ratings of the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 4. Approvals and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 5. Input Power Supply Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 6. Environmental Ratings of the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 7. EMC Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 8. Input Power Supply Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Table 9. Material Requirement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 10. 120 Vac Input Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 11. 24 Vdc Input Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 12. Relay Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 13. Pilot Duty Relay Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 14. 24 Vdc Supply Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Table 15. PROFIBUS DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 16. PROFIBUS Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 17. C441 Motor Insight Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 18. C440 Overload Supported Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 19. S611 Soft Starter Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 20. S811+ Soft Starter Configuration File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 21. C441 Motor Insight Available IO Data for Cyclic Polling . . . . . . . . . . . . . . . . . 26
Table 22. C441 Motor Insight Available IO Data for Cyclic Polling (PROFIBUS) . . . . . . . 26
Table 23. C440 Available IO Data for Cyclic Polling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 24. S611 Available IO Data for Cyclic Polling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 25. S811+ Available IO Data for Cyclic Polling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 26. C441 Diagnostic Telegram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 27. C440 Diagnostic Telegram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 28. Ext Diag Bit Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 29. S611 Diagnostic Telegram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 30. S811+ Soft Starter Diagnostic Telegram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 31. Ext Diag Bit Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
C441 PROFIBUS Module User Manual
vi C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Safety
Definitions and Symbols
WARNING
This symbol indicates high voltage. It calls your attention
to items or operations that could be dangerous to you
and other persons operating this equipment. Read the
message and follow the instructions carefully.
This symbol is the “Safety Alert Symbol.” It occurs with
either of two signal words: CAUTION or WARNING, as
described below.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, can result in minor to moderate injury, or serious
damage to the product. The situation described in the
CAUTION may, if not avoided, lead to serious results.
Important safety measures are described in CAUTION (as
well as WARNING).
Hazardous High Voltage
WARNING
Motor control equipment and electronic controllers are
connected to hazardous line voltages. When servicing
drives and electronic controllers, there may be exposed
components with housings or protrusions at or above
line potential. Extreme care should be taken to protect
against shock.
Stand on an insulating pad and make it a habit to use only
one hand when checking components. Always work with
another person in case an emergency occurs. Disconnect
power before checking controllers or performing
maintenance. Be sure equipment is properly grounded. Wear
safety glasses whenever working on electronic controllers or
rotating machinery.
Warnings and Cautions
This manual contains clearly marked cautions and warnings
which are intended for your personal safety and to avoid any
unintentional damage to the product or connected
appliances.
Please read the information included in cautions and
warnings carefully.
Overview
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 1
Overview
The C441 PROFIBUS communication adapter is a DPV0
slave device used to connect the C441 Motor Insight
®
and
C440 protective relay and S611 and S811+ soft starters to a
PROFIBUS network. The C441Q/S PROFIBUS adapter
connects to the side of the Motor Insight and the S611 soft
starter, and allows the user to access setup parameters and
IO data of the Motor Insight and the S611 over a PROFIBUS
network.
The C441QS/SS is a stand-alone PROFIBUS adapter that
connects to the C440, S611 and S811+ via hardwired
connections (DO/DI) and allows the user to access setup
parameters and IO data of the C440, S611 and S811+ over
a PROFIBUS network.
The C441QS/SS can also be used as a 4 digital input, 2 relay
output stand-alone IO module on a PROFIBUS network.
The C441 PROFIBUS communication adapters provide the
user with the ability to:
Configure C441 Motor Insight, C440 OL relay, S611 and
S811+ soft starter and stand-alone IO setup parameters
over a PROFIBUS network
Create custom IO assemblies based upon their
applications needs
Exchange IO between a master and slave over a
PROFIBUS network
Read out diagnostic information concerning the health
of the devices connected to the C441 PROFIBUS
interface modules
PROFIBUS Specifications
Table 1. PROFIBUS Specifications
Item Specification
PROFIBUS Communications DPV0
Vendor Identification Number 0x019D
PNO Identification Number 0x0C98
Maximum IO Modules 28
Maximum Input Data 100 bytes
Maximum Output Data 20 bytes
Max Diagnostic Message length 21 bytes
Supported PROFIBUS Data rates 9.6 k, 19.2 k, 45.5 k, 93.75 k, 187.5 k,
500 k, 1.5 M, 3 M, 6 M, 12 M
Optional Features Freeze; Sync; and Fail-safe supported
GSD File 019D0C98.gsd @ www.eaton.com
Introduction
2 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Introduction
The C441 PROFIBUS modules enable PROFIBUS
communications for the following Eaton devices.
C441 Motor Insight overload and monitoring relay
C440 Overload and monitoring relay
S611 Soft Starter
S811+ Soft Starter
The device can also be used stand-alone as a PROFIBUS
I/O block.
The table below describes the products covered in this
manual and their primary usage.
Table 2. Product Selection
The PROFIBUS module provides the following key features.
Supports PROFIBUS protocol
4 Discrete Input Points and 2 Output relays
Catalog
Number Description Use With
C441Q Plug-In PROFIBUS Module with 120 Vac Inputs
and Relay Outputs
C441 Motor Insight, S611 Soft Starter
C441S Plug-In PROFIBUS Module with 24 Vdc Inputs
and Relay Outputs
C441 Motor Insight, S611 Soft Starter
C441QS Stand-alone PROFIBUS Module with 120 Vac
Inputs and Relay Outputs
C440 Overload, S611 Soft Starter,
I/O Block, S811+ Soft Starter
C441SS Stand-alone PROFIBUS Module with 24 Vdc
Inputs and Relay Outputs
C440 Overload, S611 Soft Starter,
I/O Block, S811+ Soft Starter
Ratings
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 3
Ratings
The following ratings apply to the C441Q and C441S.
Table 3. Environmental Ratings of the Module
Table 4. Approvals and Certifications
Table 5. Input Power Supply Requirements
The following ratings apply to the C441QS and C441SS.
Table 6. Environmental Ratings of the Module
Table 7. EMC Requirement
Table 8. Input Power Supply Requirements
Description Rating
Transportation
and Storage
Temperature –40 °C to +85 °C (–40 °F to +185 °F)
Humidity 5–95% noncondensing
Operating Temperature –20 °C to +50 °C (–4 °F to +122 °F)
Humidity 5–95% noncondensing
Altitude Above 2000 m (6600 ft), consult factory
Shock IEC
60068-2-27
15 G any direction for 11 milliseconds
Vibration IEC
60068-206
5–150 Hz, 5 G, 0.7 mm maximum
peak-to-peak
Pollution Degree 3
Electrical/EMC Rating
ESD Immunity (IEC61000-4-2) ±8 kV Air, ±4 kV contact
Radiated Immunity (IEC61000-4-3) 10 V/m 80–1000 MHz, 80% amplitude
modulation @ 1 kHz
Fast Transient (IEC61000-4-4) ±2 kV using direct method
Surge (IEC61000-4-5) ±2 kV line-to-ground
RF Conducted (IEC61000-4-6) 10 V, 0.15–80 MHz
Ingress Protection Code IP20
Radiated and Conducted Emissions EN55011 Class A
Agency Certifications UL
®
508
cUL
®
(CSA® C22.2 No. 14)
CE (Low Voltage Directive)
Description Requirement
Voltage Range 18–30 Vdc
Current Draw (Maximum) 30 mA
Description Rating
Transportation
and Storage
Temperature –40 °C to +80 °C (–40 °F to +176 °F)
Humidity 5–95% noncondensing
Operating Temperature –40 °C to +55 °C (–40 °F to +131 °F)
Humidity 5–95% noncondensing
Altitude Above 2000 m (6600 ft), consult factory
Shock IEC
60068-2-27
15 G any direction for 11 milliseconds
Vibration IEC
60068-206
10–150 Hz, 3 G, 0.3 mm maximum
peak-to-peak
Pollution Degree Pollution III
Polar Draw <30 mA Steady State from 24 Vdc
Dielectric
withstand
Equipment rating volts more than 50 V,
potential volts AC 1000+2*V (max marked
voltage)
Item Rating
Agency Certifications cULus by UL to UL 508, CSA C22.2 No. 14
CE (Low Voltage Directive, EMC Directive)
C-TICK
Radiated and Conducted
Emissions
EN 55011 Class A
Electrical/EMC
ESD Immunity (IEC61000-4-2) ±8 kV Air, ±4 kV contact
Radiated Immunity (IEC61000-4-3) 10 V/m 80–1000 MHz,
80% amplitude modulation at 1 kHz
Fast Transient (IEC61000-4-4) ±2 kV supply and IO
±1 kV communications
Surge (IEC61000-4-5) ±2 kV Line to PE and ±1 kV Line-to-Line
RF Conducted (IEC61000-4-6) 10 V, 0.15–100 MHz
Magnetic Field (IEC61000-4-8) DNA
Voltage Dips (IEC61000-4-11) DNA
Protection Degree (IEC60947-1) IP20
Electrical/EMC Rating
Voltage Range 18–30 Vdc
Current Draw (Maximum) 30 mA
Ratings
4 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Table 9. Material Requirement
The C441Q and C441QS provide connection for four
AC input points. The ratings for these inputs are:
Table 10. 120 Vac Input Specification
The C441S and C441SS provide connection for four DC input
points. The ratings for these inputs are:
Table 11. 24 Vdc Input Specification
The C441Q, C441S, C441QS and C441SS provide two
output relays. The ratings of the relay outputs are:
Table 12. Relay Specification
Table 13. Pilot Duty Relay Requirements
Note: Any UL Listed power supply with an isolated 24 Vdc
voltage output can be used provided that a UL listed
or recognized fuse rated no more then 4 A maximum
is installed.
WARNING
Only apply 24 Vdc to the C441 communication module
power supply connector. use of any other voltage may
result in personal injury, property damage and damage
to the module.
Description Requirement
Certification of Compliance to
the EU Directive 2011/65/EU
(RoHS 2.0)
Yes
Reach Yes
PCB Laminate Manufactured by a UL Recognized
(ZPMV2) printed wiring board
manufacturer, which meets the
requirements in UL 508, paras. 15.1, 15.3,
36.12, & 39.4(b). CB to be marked with
Vendor UL-ID code, Vendor Date Code,
material, flammability rating. Polarized
components shall be marked so polarity
can be verified after assembly
Specification Value
Number of Inputs 4
Voltage Category 120 Vac
Operating Range 80–140 Vac
Operating Frequency 50/60 Hz
Signal Delay Max 30 ms
Off State Voltage 0–30 Vac
On State Voltage 79–140 Vac
On State Current Max 15 mA
Supply External Supply
Specification Value
Number of Inputs 4
Supply Voltage 24 Vdc
Type Current Sinking
On State Voltage 15–30 Vdc
Steady State Current Max 15 mA
Off State Voltage 0–5 Vdc
24 Vdc source current limit 50 mA
Isolation Voltage 250 Vac
Specification Value
Number of Contacts 2 independent relays
(one Form A, one Form C)
Thermal Contact 5 A
Rated Insulation Voltage 300 Vac
Operating Voltage 240 Vac
Operating AC Current (Rated) 3 A at 120 Vac; 1.5 A at 240 Vac
Operating DC Current (Rated) 0.24 A at 110 Vdc, 0.1 A at 220 Vdc
Min Operating Current 10 mA at 5 Vdc
Resistive Load Rating 5 A at 240 Vac, 5 A at 30 Vdc
Inductive Loading 2 A at 240 Vac, 2 A at 30 Vdc
Specification Value
Pilot Duty Rating B300
Thermal Continuous Test Current 5 A
Maximum Current
(120 Vac)—Make/Break
30 A / 3 A
Maximum Current
(240 Vac)—Make/Break
15 A / 1.5 A
Max VA (Volt-Amperes)—
Make/Break
3600 VA / 360 VA
Mounting and Dimensions
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 5
Mounting and Dimensions
C441Q and C441S
Mounting
The C441 PROFIBUS adapters are designed to be installed
on the right side of the Motor Insight base unit or the S611.
Figure 1. Installation Diagram
1. Align module with side of Motor Insight base unit or
the S611.
2. Slide module bottom pegs into appropriate slots.
3. Rotate module up and gently click the base unit and
module together.
4. Connect 24 Vdc power, PROFIBUS cable, and IO
connector if desired.
Note: For S611 Soft Starter applications, it is recommended
to mount a C441QS or C441SS module beside the
S611 and wire the D0/D1 terminals between the two
devices. More information on this is provided later in
this document.
Mounting and Dimensions
6 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Dimensions
Figure 2. C441Q and C441S Product Dimensions (Attached to C441 Base Unit)
Mounting and Dimensions
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 7
Mounting
C441QS and C441SS
The modules are designed to be installed on the DIN rail or
panel surface by screw. Screw fixing dimensions reference
below.
Figure 3. Mounting of Stand-Alone Model
DIN rail width is 35 mm.
Mounting and Dimensions
8 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Dimensions
Figure 4. Stand-Alone Dimensions
Connections and Switch Settings
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 9
Connections and Switch Settings
Connecting the C441, C440, S611 and S811+
to a PROFIBUS Network
Connecting a C441Q/C441S to a C441 Motor
Insight or S611 Soft Starter
The C441Q and the C441S modules connect to the C441
Motor Insight and S611 Soft Starter by plugging these
PROFIBUS modules into the side of the C441 Motor Insight
and S611. As an option, the C441QS and C441SS may also
be wired to the S611 soft starter via the DO/DI terminals on
each product as shown below.
Connecting a C441QS/C441SS to a C440 Overload,
S611 Soft Starter or S811+ Soft Starter
The C441QS/SS modules communicate to the C440, S611
and S811+ by wiring the D0 terminal on the C441QS/SS to
the D0 terminal on the C440, S611 and S811+ and the D1
terminal on the C441QS/SS to the D1 terminal on the C440,
S611 and S811+. The C440 requires a C440-XCOM to be
added to the C440 per the following. The D0/D1 terminals for
the C440 are on the C440-XCOM module. All the other
devices listed above have D0/D1 terminals on a connector
directly attached to each product.
Figure 5. C440 to a C441QS/SS
Figure 6. S611 to a C441QS/SS
S811+ to the C441QS/SS
The D0/D1 terminals are on a separate terminal strip from
where the 24 Vdc terminals are located on the S811+.
Connect D0 on the S811+ to D0 on the C441QS/SS and D1
on the S811+ to D1 on the C441QS/SS.
PROFIBUS Connection
The PROFIBUS port uses the standard DB9 PROFIBUS
connection. Refer to the figure below for details on the pin
out of this connector.
Figure 7. Pin Out for PROFIBUS DB9
24 Vdc Power
The C441 PROFIBUS adapter is powered from an external
24 Vdc supply wired into the 5-pin black header (J2) located
on the top of the adapter next to the 8 pos DIP switch.
Note: Connections to pins 2 and 4 for the C441Q/S modules
are only required if Modbus communications are to be
implemented.
Connections to pins 2 and 4 for the C441QS/SS are
the required communication connections to interface
the C440, S611 and S811+ devices to a PROFIBUS
network.
Table 14. 24 Vdc Supply Connection
C441QS/SS
1 — 5
2 — 4
4 — 2
5 — 1
C441QS/SS
Pin # Circuit Description
1 Common 24 Vdc common input connection
2 D1 Transceiver terminal 1, V1 Voltage, Data + (V1 > V0
for binary 1 [OFF] state)
Connection for Remote Modbus Port
3NC
4 D0 Transceiver terminal 0, V0 Voltage, Data—(V0 > V1
for binary 0 [ON] state)
Connection for Remote Modbus Port
5 +24 Vdc +24 Vdc supply input connection
Connections and Switch Settings
10 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
Figure 8. Power and Modbus RS-485 Connections
Setting the PROFIBUS Address
PROFIBUS Address
The PROFIBUS address is set using the DIP switches
located on the top of the C441 communication adapter. The
address can only be set with the hardware DIP switches. The
address is in binary with the major units numbered to the
right of the switch on the label. Adding up the major units set
to ON will provide the address of the adapter on the
PROFIBUS network.
Notice
The address specified in the switches is only used by the
adapter at the time the adapter is powered on. Changing
these switches during operation will have no affect until the
next power cycle or reset.
Notice
A PROFIBUS address setting of 0 will result in the C441
using the default Station Address of 125. Any PROFIBUS
Station Address setting greater than 125 will result in the
C441 using the default Station Address of 125.
Table 15. PROFIBUS DIP Switch Settings
Example: To set a MAC ID of 25, DIP switches 5, 4, and 1
need to be turned ON, with all others OFF.
DIP Switch Value
764
632
516
48
34
22
11
Connections and Switch Settings
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 11
Power and I/O Wiring Diagrams for the C441Q
and C441S Modules
The C441Q module contains four 24 Vdc inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
24 Vdc Inputs
The 24 Vdc input circuit is capable of both isolated and
unisolated behavior. The isolated inputs share a single
common tie point. A 24 Vdc current limited source/ground is
provided in the situations that require locally supplied input
signal voltage. To use the unisolated inputs, tie the 24 Vdc
ground/common to the isolated common.
Figure 9. C441Q: 24 Vdc Wiring Diagram
Note: Do not connect a 24 Vdc source to pins 6 and 7. The
“I/O Power: 24 Vdc” is to be used only in conjunction
with the inputs. It is a 24 Vdc output intended to only
supply signal power for the inputs. When using the
24 Vdc input supply, pin 6 should only be connected to
pin 5 (24 Vdc input supply common to input common).
See example wiring diagram above. Any device using
the provided 24 Vdc input supply must have 500 V
isolation from ground. Example devices include
pushbuttons and auxiliary contacts.
Pin 1
Pin 12
NET
24 Vdc
+
-
+
I1
I2
I3
I4
C
NO
NO
NC
I1
I2
I3
I4
C
C
Q1
NO
Pin 1
24 Vdc
Pin 12
NET
+
-
+
0V
+
-
24
Example: Isolated 24 Vdc Input Source
- The inputs must be supplied by an
external power source.
- Do not connect the external supply to
terminals 0V and 24.
- Connect isolated power source between
C and Inputs.
Example: Non-Isolated 24 Vdc Input Source
- Input source power is taken from the 5-pin
connector.
- Connect C and 0V together.
- Use 24 to source inputs.
24 Vdc
24 Vdc
I/O Power
AC/DC
AC/DC
24 Vdc
AC/DC
AC/DC
C
Q1
Q2
Q2
I1
I2
I3
I4
C
NO
NO
NC
I1
I2
I3
I4
C
C
Q1
NO
0V
+
-
24
C
Q1
Q2
Q2
Connections and Switch Settings
12 C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com
The C441S module contains four 120 Vac inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
Figure 10. C441S: 120 Vac Wiring Diagram
Example 120 Vac IO Module
- All inputs are isolated.
- All Common terminals are connected
together internally.
AC/DC
AC/DC
120 Vac
Pin 1
Pin 12
NET
24 Vdc
+
-
I1
I2
I3
I4
C
C
C
NO
NO
NO
C
NC
I1
I2
I3
I4
C
C
C
Q1
Q1
Q2
C
Q2
Connections and Switch Settings
C441 PROFIBUS Module User Manual MN042002EN—July 2015 www.eaton.com 13
Power and I/O Wiring Diagrams for the
C441QS and C441SS Modules
The C441QS module contains four 24 Vdc inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
Figure 11. C441QS—24 Vdc Input Specification
24 Vdc Inputs
The 24 Vdc input circuit is capable of both isolated and
unisolated behavior. The isolated inputs share a single
common tie point. A 24 Vdc current limited source/ground is
provided in the situations that require locally supplied input
signal voltage. To use the unisolated inputs, tie the 24 Vdc
ground/common to the isolated common.
The C441SS module contains four 120 Vac inputs and two
relay outputs. The two relay outputs provided are one
form A (NO) and one form C (NO, NC).
Figure 12. C441SS—120 Vac Input Specification
D0 D1
To C440, S611
or S811+
D0 D1
To C440, S611
or S811+
Example: Non-isolating
24 Vdc input source
- Input source power is taken
from 5-pin connector
- Connect C and OV together
- Use 24 to source inputs
24 Vdc
24 Vdc
I/O power
Pin 1
Pin 12
AC/DC
AC/DC
I1
I2
I3
I4
C
OV
24
NO
NO
NO
C
NC
I1
I2
I3
I4
C
+
Q1
Q1
Q2
C
Q2
Example: Isolated 24 Vdc input source
- The inputs must be supplied
by an external power source
- Do not connect the external
supply to terminals OV and 24
- Connect isolated power source
between C and inputs
24 Vdc
24 Vdc
I/O power
Pin 1
Pin 12
AC/DC
AC/DC
I1
I2
I3
I4
C
OV
24
NO
NO
NO
C
NC
I1
I2
I3
I4
C
+
Q1
Q1
Q2
C
Q2
24 Vdc
D0 D1
To C440, S611
or S811+
Example: 120 Vac IO module
- All inputs are isolated
- All common terminals are
connected together internally
24 Vdc
120 Vac
Pin 1
Pin 12
AC/DC
AC/DC
I1
I2
I3
I4
C
C
C
NO
NO
NO
C
NC
I1
I2
I3
I4
C
C
C
Q1
Q1
Q2
C
Q2
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76