Danfoss ECL Comfort 210 / 296 / 310, A232 Operating instructions

  • Hello! I am an AI chatbot trained to assist you with the Danfoss ECL Comfort 210 / 296 / 310, A232 Operating instructions. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
OperatingGuide
ECLComfort210/296/310,applicationA232/A332
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................14
2.3Mounting...........................................................21
2.4Placingthetemperaturesensors................................25
2.5Electricalconnections.............................................27
2.6InsertingtheECLApplicationKey..............................36
2.7Checklist............................................................42
2.8Navigation,ECLApplicationKeyA232/A332................43
3.0Dailyuse.........................................................56
3.1Howtonavigate...................................................56
3.2Understandingthecontrollerdisplay..........................57
3.3Ageneraloverview:Whatdothesymbolsmean?...........61
3.4Monitoringtemperaturesandsystem
components........................................................62
3.5Influenceoverview................................................63
3.6Manualcontrol.....................................................64
3.7Schedule............................................................65
4.0Settingsoverview............................................66
5.0Settings...........................................................69
5.1IntroductiontoSettings..........................................69
5.2Flowtemperature/Inlettemperature.........................70
5.3Roomlimit..........................................................74
5.4Returnlimit.........................................................77
5.5Surfacelimit........................................................84
5.6Optimization........................................................87
5.7Controlparameters................................................93
5.8Application.......................................................100
5.9Optionalfunction................................................110
5.10Alarm..............................................................114
5.11Alarmoverview..................................................117
5.12Anti-bacteria......................................................118
6.0Commoncontrollersettings............................120
6.1IntroductiontoCommoncontrollersettings’..............120
6.2Time&Date.......................................................121
6.3Holiday............................................................122
6.4Inputoverview...................................................124
6.5Log.................................................................125
6.6Outputoverride..................................................126
6.7Keyfunctions.....................................................127
6.8System.............................................................129
7.0Miscellaneous................................................136
7.1ECA30/31setupprocedures.................................136
7.2Overridefunction................................................144
7.3Severalcontrollersinthesamesystem......................147
7.4Frequentlyaskedquestions....................................150
7.5Definitions........................................................153
7.6Type(ID6001),overview.......................................157
7.7ParameterIDoverview..........................................158
©Danfoss|2018.11VI.JM.G3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA232
(ordercodeno.087H3812).
TheECLApplicationKeyA232contains5subtypes:
A232.1(applicableinECLComfort210and310)
A332.1A332.4(applicableinECLComfort310)
A232.1isheating/coolingrelatedapplication,onecontrol
valve
A332.1islikeA232.1andhasadditionalreturntemperature
limitation
A332.2isheating/coolingrelatedapplication,twocontrol
valvesandreturntemperaturelimitation
A332.3islikeA332.2andhasadditionaladvancedDHWcircuit
control
A332.4islikeA332.1andhasspecialoverridefunctionalities
ThedescribedfunctionsarerealizedinECLComfort210forbasic
solutionsandinECLComfort310foradvancedsolutions,for
exampleM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA232complieswithECLComfort210and
ECLComfort310controllersasofsoftwareversion1.11(visible
atstart-upofthecontrollerandin‘Commoncontrollersettings
in‘System’).
ARemoteControlUnit,ECA30orECA31,canbeconnectedand
thebuilt-inroomtemperaturesensorcanbeutilized.Whenusing
theECA31,therelativehumiditysignalisusedforpreventing
condensation(dew)whenincoolingmode.
TheapplicationA332.3workswiththeInternalI/OmoduleECA
32(ordercodeno.087H3202).
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32canalsobeusedforextradatacommunication
toSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:
https://www.danfoss.com/en/service-and-support/downloads
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
2|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
ECLComfort310isavailableas:
ECLComfort310,230volta.c(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheremotecontrolunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seeecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
VI.JM.G3.02
©Danfoss|2018.11|3
OperatingGuideECLComfort210/296/310,applicationA232/A332
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
4|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
1
2
174
-
Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.JM.G3.02
©Danfoss|2018.11|5
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.0Installation
2.1Beforeyoustart
TheApplicationKeyA232contains5applications,allrelatedto
floorheatingandceilingcoolingsystems.Theapplicationsinthe
A232keyofferawiderangeofpossibilities(seetheexamples).
TheapplicationA232.1isveryflexible.Thesearethebasic
principles:
Heating/coolingwithroomtemperaturecontrol:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.
ThedesiredflowtemperatureatS3iscalculatedintheECL
controller,basedontheoutdoortemperature(S1)andthedesired
roomtemperature.Thelowertheoutdoortemperature,thehigher
thedesiredflowtemperature(heating).
Oppositely,thehighertheoutdoortemperature,thelowerthe
desiredflowtemperature(cooling).Thechange-overbetween
heatingandcoolingcanbe:
OutdoorANDroomtemperatureor
Roomtemperatureor
Outdoortemperaturerelated.
Bymeansofaweekschedule,thecircuitscanbeinComfortor
‘Savingmode(twovaluesforthedesiredroomtemperature).In
Savingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M1)isopenedgraduallywhen:
(Heating)theflowtemperatureislowerthanthedesiredflow
temperatureandviceversa.
(Cooling)theflowtemperatureishigherthanthedesiredflow
temperatureandviceversa.
TheON-OFFoutputsX2/X3areactivatedatcooling/heating
demandrespectively.
Roomtemperature:
Ifthemeasuredroomtemperature(S2orECA30/31)doesnot
equalthedesiredroomtemperature,thedesiredtemperatureat
S3canbeadjusted.
Surfacetemperaturelimitation:
Heating
:ThefloorsurfacetemperatureS5canbelimitedtoa
maximuminordertoavoidatoowarmfloor.
Cooling:TheceilingsurfacetemperatureS6canbelimitedtoa
minimuminordertoavoidatoocoldceiling(riskforcondensation).
Override:
WhentheECLcontrollerisinscheduledmode,theS8inputcanbe
usedforoverridingtheScheduletooperateinComfortorSaving
mode.
Coolingmode:
BasedontheRelativeHumidity(RH),measuredbyECA31,the
desiredflowtemperaturecanbeminimumlimitedtoavoiddew
(condensation).
Thecirculationpump,P1,isONatheatingorcoolingdemandor
atfrostprotection.
TypicalA232.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210
/296/310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor
S4
notused
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
(notillustrated)Overrideinputforstopof
circulationpump
S8
(notillustrated)OverrideinputforComfort/
Saving
P1
Circulationpump(ON/OFF)
X2
Coolingdemand(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedchange-overvalve
*Alternative:ESM-10,roomtemperaturesensor
6|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheON-OFFoutputX4canbesetto
operateasaHumidistator
operateasaswitch,dependingontheoutdoortemperatureor
followSchedule1or
followSchedule2or
followSchedule3or
switchONatcoolingdemand
Alarm(visibleindisplay,nooutput):
Alarmcanbeactivatediftheactualflowtemperaturediffersfrom
thedesiredflowtemperature.
Alarmwillalsobeactivatedif,inheatingmode,theflow
temperatureexceedsasetmax.value.
Safetyfunction,heatingmode:
IftheflowtemperatureS3exceedsasetmax.value,thealarmwill
beactivated.
CirculationpumpP1isswitchedOFFinordertopreventtoohigh
temperaturetobecirculatedinthesystem(forexamplefloor
circuit).
P1isswitchedOFFfor35minutesandthenswitchedONfor30sec.
Iftheflowtemperatureisbelowthesetmax.value,P1remainsON.
Foradescriptionofthechange-overfromheatingtocoolingmode,
pleasereadthesectionA232ingeneral’ .
VI.JM.G3.02
©Danfoss|2018.11|7
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.1isverysimilartotheapplicationA232.1.
ExtrasinrelationtoA232.1:
Returntemperaturelimitation:
ThereturntemperatureS10canbelimited,forexamplenotto
betoohigh(heating)ortoolow(cooling).Ifso,thedesiredflow
temperatureatS3canbeadjusted,forexampleatheatingtoa
lowervalueor,atcoolingtoahighervalue.
Thisresultsinagradualclosingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
TheON-OFFoutputX5canbesetto
followSchedule1or
followSchedule2or
followSchedule3or
switchONatcoolingdemand
AlarmA1:
Analarmactivatesrelay6.
ChangesinrelationtoA332.1:
TheON-OFFoutputX4canbesetto
operateasaHumidistator
operateasaswitch,dependingontheoutdoortemperature
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
TypicalA332.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor
S4
notused
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
(notillustrated)Overrideinputforstopofcirculation
pump
S8
(notillustrated)OverrideinputforComfort/Saving
S9
notused
S10Returntemperaturesensor
P1
Circulationpump(ON/OFF)
X2
Coolingdemand(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
X5
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedchange-overvalve
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
8|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.2isbasicallyliketheapplicationA332.1.
ExtrasinrelationtoA332.1:
Heatingandcoolingcircuitshaveseparateflowtemperature
sensorsandcontrolvalves.
Heatingandcoolingcircuitshaveseparatereturntemperature
sensorsandlimitationfunctions.
ChangesinrelationtoA332.1:
P2iscirculationpumpincoolingcircuit
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
TypicalA332.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor,heating
S4
Flowtemperaturesensor,cooling
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
(notillustrated)Overrideinputforstopofcirculation
pump
S8
(notillustrated)OverrideinputforComfort/Saving
S9
Returntemperaturesensor,heating
S10
Returntemperaturesensor,cooling
P1
Circulationpump,heating(ON/OFF)
P2
Circulationpump,cooling(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
Multi-functionality
X5
Multi-functionality
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
VI.JM.G3.02
©Danfoss|2018.11|9
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.3isbasicallyliketheapplicationA332.2.
ExtrasinrelationtoA332.2:
TemperaturesensorsS5(heatingcircuit)andS6(coolingcircuit)
canbeusedforeitherreturntemperaturelimitationorsurface
temperaturelimitation.Functionalityselectionisdonebysetting
aninfluencefactor.IfinfluencefactorsaresetforbothReturnand
Surfacelimitation,therewillnotbeanylimitation.
AdvancedDomesticHotWater(DHW)heatingcontrol:
TheDHWtemperatureatS9ismaintainedat‘Comfortlevelata
DHWdraw-off(DHWtapping)(theflowswitchS8isactivated).
IfthemeasuredDHWtemperatureatS9islowerthanthedesired
DHWtemperature,themotorizedcontrolvalveM3isopened
graduallyandviceversa.
TheDHWtemperaturecontrolisinrelationtoactualsupply
temperatureS7.Inordertocompensateforthereactiontime,
themotorizedcontrolvalvecanbepre-activatedatthestartofa
DHWdraw-off.
Anidletemperature(thedesiredSavingtemperature)canbe
maintainedateitherS7orS9whenthereisnoDHWdraw-off.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
ThereturntemperatureS10canbelimited,forexamplenottobe
toohighortoolow.
Ifso,thedesiredflowtemperatureatS9canbeadjusted,for
exampletoalowervalue.Thisresultsinagradualclosingofthe
motorizedcontrolvalve.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA332.3application:
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor,heating
S4
Flowtemperaturesensor,cooling
S5
(Optional)ReturnorFloorsurfacetemperaturesensor
S6
(Optional)ReturnorCeilingsurfacetemperature
sensor
S7
Supplytemperaturesensor,DHW
S8
Flowswitch,DHWdraw-off
S9
Flowtemperaturesensor,DHW
S10Returntemperaturesensor,DHW
P1
Circulationpump,heating(ON/OFF)
P2
Circulationpump,cooling(ON/OFF)
P7
Circulationpump,DHW(ON/OFF)
X3
(notillustrated)Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
X5
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
M3
Motorizedcontrolvalve,DHW(3-pointcontrolled)
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
10|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.4isbasicallyliketheapplicationA332.1.
Extras/changesinrelationtoA332.1:
Override:
WhentheECLcontrollerisinscheduledmode-
theS7inputcanbeusedforoverridingtoHeatingmode
theS9inputcanbeusedforoverridingtoCoolingmode
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
TypicalA332.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor
S4
notused
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
OverrideinputforHeatingmode
S8
OverrideinputforComfort/Saving
S9
OverrideinputforCoolingmode
S10Returntemperaturesensor
P1
Circulationpump(ON/OFF)
X2
Coolingdemand(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
X5
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedchange-overvalve
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
VI.JM.G3.02
©Danfoss|2018.11|11
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232,ingeneral
Thefunctionselector:
Eachcircuithasafunctionselector.Theheatingcircuitcanrun,
forexample
Comfortperiodsatadesiredroomtemperatureof21°C
Savingperiodsatadesiredroomtemperatureof16°CorTotal
stop
Thecoolingcircuitcanrun,forexample
Comfortperiodsatadesiredroomtemperatureof24°C
Savingperiodsatadesiredroomtemperatureof30°C
Schedules:
TheA232applicationcontains3weekschedules;oneforthe
heatingcircuitandoneforthecoolingcircuit.Thethirdscheduleis
foruniversaluseandisfoundin'Commoncontrollersettings' .
A232.1:Relay4(X4)canbesettofollowthethirdschedule.
A332.1,A332.2,A332.3andA332.4:Relay5(X5)canbesettofollow
thethirdschedule.
Overridefunctions:
Bymeansofswitches,connectedtodifferentinputs,thefollowing
functionalitiesareavailablewhentheinputinquestionisactivated:
S7S8S9
A232.1
Stopthecirculationpump
OverridetoComfortorSavingmodeNofunction
A332.1
Stopthecirculationpump
OverridetoComfortorSavingmodeNofunction
A332.2
Stopthecirculationpump
OverridetoComfortorSavingmodeNofunction
A332.3
NofunctionNofunctionNofunction
A332.4
OverridetoHeating
OverridetoComfortorSavingmode
OverridetoCooling
12|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232,ingeneral,continued
Shortprocessdescriptions:
Changefromheatingtocooling(outdoorandroomtemperature
based):
1.Heatingactive
2.Outdoorandroomtemperaturerising
3.Heatingstopwhenactualoutdoortemperaturegetshigher
than'Summer,cut-out'(ID1x179)
4.Coolingstartwhen:
Accumulatedoutdoortemperaturevaluegetshigherthan
setlimit('Activation,acc.T',ID12144)
AND
Accumulatedroomtemperaturevaluegetshigherthanset
limit('Act.,acc.roomT',ID12156)
AND
Actualroomtemperaturegetshigherthandesiredroom
temperatureforcoolingoperation.
Changefromheatingtocooling(roomtemperaturebased):
1.Heatingactive
2.Roomtemperaturerising
3.Heatingstopwhenaccumulatedroomtemperaturevaluegets
higherthandesiredroomtemperatureforheatingoperation.
4.Coolingstartwhen:
Accumulatedroomtemperaturevaluegetshigherthanset
limit('Act.,acc.roomT',ID12156)
AND
Actualroomtemperaturegetshigherthandesiredroom
temperatureforcoolingoperation.
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
VI.JM.G3.02
©Danfoss|2018.11|13
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
A232.1,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optional
surfacetemperaturelimitations.
14|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232.1,ex.b:
Controlofflowtemperature(heating/cooling)infloorinrelationtooutdoor,roomanddewpointtemperature.Optionalsurface
temperaturelimitation.
A232.1,ex.c:
Controlofflowtemperature(heating/cooling)toafan-coilinrelationtooutdoor,roomanddewpointtemperature.
VI.JM.G3.02
©Danfoss|2018.11|15
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232.1,ex.d:
Controlofflowtemperature(heating/cooling)toafan-coilinrelationtooutdoor,roomanddewpointtemperature.Heatingsource:
Districtheating.Coolingsource:Coolingmachine.
A232.1,ex.e:
Controlofflowtemperature(heating/cooling)inrelationtooutdoor,roomanddewpointtemperature.Heating/coolingsources:
Districtheating/districtcooling.
16|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.1,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optionalreturn
andsurfacetemperaturelimitation.
AllA232.1examplescanbecontrolledbyA332.1.
A332.2,ex.a:
Separatedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpointtemperature.Optionalreturn
andsurfacetemperaturelimitations.
VI.JM.G3.02
©Danfoss|2018.11|17
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.2,ex.b:
Districtheating/districtcoolingbasedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpoint
temperature.Optionalreturnandsurfacetemperaturelimitations.
18|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.3,ex.aandb:
Separatedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpointtemperature.AdvancedDHW
temperaturecontrolatDHWdraw-off.Anti-bacteriatemperaturecontrol.Optionalreturnorsurfacetemperaturelimitations.
VI.JM.G3.02
©Danfoss|2018.11|19
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.4,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optionalreturn
andsurfacetemperaturelimitation.Overridefunctionalitiesforheatingandcoolingmodes.
TheA232.1andA332.1examplescan,ingeneral,becontrolledbyA332.4.
20|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
/