Danfoss ECL Comfort 210 / 296 / 310, A232 Operating instructions

Type
Operating instructions
OperatingGuide
ECLComfort210/296/310,applicationA232/A332
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................14
2.3Mounting...........................................................21
2.4Placingthetemperaturesensors................................25
2.5Electricalconnections.............................................27
2.6InsertingtheECLApplicationKey..............................36
2.7Checklist............................................................42
2.8Navigation,ECLApplicationKeyA232/A332................43
3.0Dailyuse.........................................................56
3.1Howtonavigate...................................................56
3.2Understandingthecontrollerdisplay..........................57
3.3Ageneraloverview:Whatdothesymbolsmean?...........61
3.4Monitoringtemperaturesandsystem
components........................................................62
3.5Influenceoverview................................................63
3.6Manualcontrol.....................................................64
3.7Schedule............................................................65
4.0Settingsoverview............................................66
5.0Settings...........................................................69
5.1IntroductiontoSettings..........................................69
5.2Flowtemperature/Inlettemperature.........................70
5.3Roomlimit..........................................................74
5.4Returnlimit.........................................................77
5.5Surfacelimit........................................................84
5.6Optimization........................................................87
5.7Controlparameters................................................93
5.8Application.......................................................100
5.9Optionalfunction................................................110
5.10Alarm..............................................................114
5.11Alarmoverview..................................................117
5.12Anti-bacteria......................................................118
6.0Commoncontrollersettings............................120
6.1IntroductiontoCommoncontrollersettings’..............120
6.2Time&Date.......................................................121
6.3Holiday............................................................122
6.4Inputoverview...................................................124
6.5Log.................................................................125
6.6Outputoverride..................................................126
6.7Keyfunctions.....................................................127
6.8System.............................................................129
7.0Miscellaneous................................................136
7.1ECA30/31setupprocedures.................................136
7.2Overridefunction................................................144
7.3Severalcontrollersinthesamesystem......................147
7.4Frequentlyaskedquestions....................................150
7.5Definitions........................................................153
7.6Type(ID6001),overview.......................................157
7.7ParameterIDoverview..........................................158
©Danfoss|2018.11VI.JM.G3.02|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyA232
(ordercodeno.087H3812).
TheECLApplicationKeyA232contains5subtypes:
A232.1(applicableinECLComfort210and310)
A332.1A332.4(applicableinECLComfort310)
A232.1isheating/coolingrelatedapplication,onecontrol
valve
A332.1islikeA232.1andhasadditionalreturntemperature
limitation
A332.2isheating/coolingrelatedapplication,twocontrol
valvesandreturntemperaturelimitation
A332.3islikeA332.2andhasadditionaladvancedDHWcircuit
control
A332.4islikeA332.1andhasspecialoverridefunctionalities
ThedescribedfunctionsarerealizedinECLComfort210forbasic
solutionsandinECLComfort310foradvancedsolutions,for
exampleM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyA232complieswithECLComfort210and
ECLComfort310controllersasofsoftwareversion1.11(visible
atstart-upofthecontrollerandin‘Commoncontrollersettings
in‘System’).
ARemoteControlUnit,ECA30orECA31,canbeconnectedand
thebuilt-inroomtemperaturesensorcanbeutilized.Whenusing
theECA31,therelativehumiditysignalisusedforpreventing
condensation(dew)whenincoolingmode.
TheapplicationA332.3workswiththeInternalI/OmoduleECA
32(ordercodeno.087H3202).
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32canalsobeusedforextradatacommunication
toSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Products&Solutions>DistrictHeating
andCooling>Tools&Software>ECLTool.
TheURLis:
https://www.danfoss.com/en/service-and-support/downloads
ECLComfort210isavailableas:
ECLComfort210,230volta.c.(087H3020)
ECLComfort210B,230volta.c.(087H3030)
2|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
ECLComfort310isavailableas:
ECLComfort310,230volta.c(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheremotecontrolunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartsforECLComfort:
forECLComfort210,230volt(087H3220)
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort210and310,modules
andaccessoriesisavailableonhttp://heating.danfoss.com/.
DocumentationforECLPortal:Seeecl.portal.danfoss.com.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
VI.JM.G3.02
©Danfoss|2018.11|3
OperatingGuideECLComfort210/296/310,applicationA232/A332
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfortinstallationismax.10Atypically.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort210/310:0-55°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted(asofcontrollerversion1.11(ECL210/310)andversion
1.58(ECL296)).Thefollowinganimationwillbeshownwhenthe
softwareisbeingupdated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
4|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-
Circuit1Parameterno.
12174
1
2
174
-
Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
VI.JM.G3.02
©Danfoss|2018.11|5
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.0Installation
2.1Beforeyoustart
TheApplicationKeyA232contains5applications,allrelatedto
floorheatingandceilingcoolingsystems.Theapplicationsinthe
A232keyofferawiderangeofpossibilities(seetheexamples).
TheapplicationA232.1isveryflexible.Thesearethebasic
principles:
Heating/coolingwithroomtemperaturecontrol:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3isthemost
importantsensor.
ThedesiredflowtemperatureatS3iscalculatedintheECL
controller,basedontheoutdoortemperature(S1)andthedesired
roomtemperature.Thelowertheoutdoortemperature,thehigher
thedesiredflowtemperature(heating).
Oppositely,thehighertheoutdoortemperature,thelowerthe
desiredflowtemperature(cooling).Thechange-overbetween
heatingandcoolingcanbe:
OutdoorANDroomtemperatureor
Roomtemperatureor
Outdoortemperaturerelated.
Bymeansofaweekschedule,thecircuitscanbeinComfortor
‘Savingmode(twovaluesforthedesiredroomtemperature).In
Savingmodetheheatingcanbereducedorswitchedofftotally.
Themotorizedcontrolvalve(M1)isopenedgraduallywhen:
(Heating)theflowtemperatureislowerthanthedesiredflow
temperatureandviceversa.
(Cooling)theflowtemperatureishigherthanthedesiredflow
temperatureandviceversa.
TheON-OFFoutputsX2/X3areactivatedatcooling/heating
demandrespectively.
Roomtemperature:
Ifthemeasuredroomtemperature(S2orECA30/31)doesnot
equalthedesiredroomtemperature,thedesiredtemperatureat
S3canbeadjusted.
Surfacetemperaturelimitation:
Heating
:ThefloorsurfacetemperatureS5canbelimitedtoa
maximuminordertoavoidatoowarmfloor.
Cooling:TheceilingsurfacetemperatureS6canbelimitedtoa
minimuminordertoavoidatoocoldceiling(riskforcondensation).
Override:
WhentheECLcontrollerisinscheduledmode,theS8inputcanbe
usedforoverridingtheScheduletooperateinComfortorSaving
mode.
Coolingmode:
BasedontheRelativeHumidity(RH),measuredbyECA31,the
desiredflowtemperaturecanbeminimumlimitedtoavoiddew
(condensation).
Thecirculationpump,P1,isONatheatingorcoolingdemandor
atfrostprotection.
TypicalA232.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL210
/296/310
ElectroniccontrollerECLComfort210,296or310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor
S4
notused
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
(notillustrated)Overrideinputforstopof
circulationpump
S8
(notillustrated)OverrideinputforComfort/
Saving
P1
Circulationpump(ON/OFF)
X2
Coolingdemand(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedchange-overvalve
*Alternative:ESM-10,roomtemperaturesensor
6|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheON-OFFoutputX4canbesetto
operateasaHumidistator
operateasaswitch,dependingontheoutdoortemperatureor
followSchedule1or
followSchedule2or
followSchedule3or
switchONatcoolingdemand
Alarm(visibleindisplay,nooutput):
Alarmcanbeactivatediftheactualflowtemperaturediffersfrom
thedesiredflowtemperature.
Alarmwillalsobeactivatedif,inheatingmode,theflow
temperatureexceedsasetmax.value.
Safetyfunction,heatingmode:
IftheflowtemperatureS3exceedsasetmax.value,thealarmwill
beactivated.
CirculationpumpP1isswitchedOFFinordertopreventtoohigh
temperaturetobecirculatedinthesystem(forexamplefloor
circuit).
P1isswitchedOFFfor35minutesandthenswitchedONfor30sec.
Iftheflowtemperatureisbelowthesetmax.value,P1remainsON.
Foradescriptionofthechange-overfromheatingtocoolingmode,
pleasereadthesectionA232ingeneral’ .
VI.JM.G3.02
©Danfoss|2018.11|7
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.1isverysimilartotheapplicationA232.1.
ExtrasinrelationtoA232.1:
Returntemperaturelimitation:
ThereturntemperatureS10canbelimited,forexamplenotto
betoohigh(heating)ortoolow(cooling).Ifso,thedesiredflow
temperatureatS3canbeadjusted,forexampleatheatingtoa
lowervalueor,atcoolingtoahighervalue.
Thisresultsinagradualclosingofthemotorizedcontrolvalve.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
TheON-OFFoutputX5canbesetto
followSchedule1or
followSchedule2or
followSchedule3or
switchONatcoolingdemand
AlarmA1:
Analarmactivatesrelay6.
ChangesinrelationtoA332.1:
TheON-OFFoutputX4canbesetto
operateasaHumidistator
operateasaswitch,dependingontheoutdoortemperature
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
TypicalA332.1application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor
S4
notused
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
(notillustrated)Overrideinputforstopofcirculation
pump
S8
(notillustrated)OverrideinputforComfort/Saving
S9
notused
S10Returntemperaturesensor
P1
Circulationpump(ON/OFF)
X2
Coolingdemand(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
X5
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedchange-overvalve
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
8|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.2isbasicallyliketheapplicationA332.1.
ExtrasinrelationtoA332.1:
Heatingandcoolingcircuitshaveseparateflowtemperature
sensorsandcontrolvalves.
Heatingandcoolingcircuitshaveseparatereturntemperature
sensorsandlimitationfunctions.
ChangesinrelationtoA332.1:
P2iscirculationpumpincoolingcircuit
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
TypicalA332.2application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor,heating
S4
Flowtemperaturesensor,cooling
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
(notillustrated)Overrideinputforstopofcirculation
pump
S8
(notillustrated)OverrideinputforComfort/Saving
S9
Returntemperaturesensor,heating
S10
Returntemperaturesensor,cooling
P1
Circulationpump,heating(ON/OFF)
P2
Circulationpump,cooling(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
Multi-functionality
X5
Multi-functionality
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
VI.JM.G3.02
©Danfoss|2018.11|9
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.3isbasicallyliketheapplicationA332.2.
ExtrasinrelationtoA332.2:
TemperaturesensorsS5(heatingcircuit)andS6(coolingcircuit)
canbeusedforeitherreturntemperaturelimitationorsurface
temperaturelimitation.Functionalityselectionisdonebysetting
aninfluencefactor.IfinfluencefactorsaresetforbothReturnand
Surfacelimitation,therewillnotbeanylimitation.
AdvancedDomesticHotWater(DHW)heatingcontrol:
TheDHWtemperatureatS9ismaintainedat‘Comfortlevelata
DHWdraw-off(DHWtapping)(theflowswitchS8isactivated).
IfthemeasuredDHWtemperatureatS9islowerthanthedesired
DHWtemperature,themotorizedcontrolvalveM3isopened
graduallyandviceversa.
TheDHWtemperaturecontrolisinrelationtoactualsupply
temperatureS7.Inordertocompensateforthereactiontime,
themotorizedcontrolvalvecanbepre-activatedatthestartofa
DHWdraw-off.
Anidletemperature(thedesiredSavingtemperature)canbe
maintainedateitherS7orS9whenthereisnoDHWdraw-off.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Savingmode(twovaluesforthedesiredDHWtemperature).
ThereturntemperatureS10canbelimited,forexamplenottobe
toohighortoolow.
Ifso,thedesiredflowtemperatureatS9canbeadjusted,for
exampletoalowervalue.Thisresultsinagradualclosingofthe
motorizedcontrolvalve.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
TypicalA332.3application:
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
ECA32
Built-inextensionmodule
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor,heating
S4
Flowtemperaturesensor,cooling
S5
(Optional)ReturnorFloorsurfacetemperaturesensor
S6
(Optional)ReturnorCeilingsurfacetemperature
sensor
S7
Supplytemperaturesensor,DHW
S8
Flowswitch,DHWdraw-off
S9
Flowtemperaturesensor,DHW
S10Returntemperaturesensor,DHW
P1
Circulationpump,heating(ON/OFF)
P2
Circulationpump,cooling(ON/OFF)
P7
Circulationpump,DHW(ON/OFF)
X3
(notillustrated)Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
X5
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve,heating(3-pointcontrolled)
M2
Motorizedcontrolvalve,cooling(3-pointcontrolled)
M3
Motorizedcontrolvalve,DHW(3-pointcontrolled)
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
10|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
TheapplicationA332.4isbasicallyliketheapplicationA332.1.
Extras/changesinrelationtoA332.1:
Override:
WhentheECLcontrollerisinscheduledmode-
theS7inputcanbeusedforoverridingtoHeatingmode
theS9inputcanbeusedforoverridingtoCoolingmode
Foradescriptionofthechange-overfromheatingtocooling
operation,pleasereadthesectionA232ingeneral’ .
TypicalA332.4application:
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:
ECL310
ElectroniccontrollerECLComfort310
S1
Outdoortemperaturesensor
S2
ECA31RoomtemperatureandRHsensor*
S3
Flowtemperaturesensor
S4
notused
S5
(Optional)Floorsurfacetemperaturesensor
S6
(Optional)Ceilingsurfacetemperaturesensor
S7
OverrideinputforHeatingmode
S8
OverrideinputforComfort/Saving
S9
OverrideinputforCoolingmode
S10Returntemperaturesensor
P1
Circulationpump(ON/OFF)
X2
Coolingdemand(ON/OFF)
X3
Heatingdemand(ON/OFF)
X4
(notillustrated)Multi-functionality
X5
(notillustrated)Multi-functionality
M1
Motorizedcontrolvalve(3-pointcontrolled)
M2
Motorizedchange-overvalve
A1
Alarm
*Alternative:ESM-10,roomtemperaturesensor
VI.JM.G3.02
©Danfoss|2018.11|11
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232,ingeneral
Thefunctionselector:
Eachcircuithasafunctionselector.Theheatingcircuitcanrun,
forexample
Comfortperiodsatadesiredroomtemperatureof21°C
Savingperiodsatadesiredroomtemperatureof16°CorTotal
stop
Thecoolingcircuitcanrun,forexample
Comfortperiodsatadesiredroomtemperatureof24°C
Savingperiodsatadesiredroomtemperatureof30°C
Schedules:
TheA232applicationcontains3weekschedules;oneforthe
heatingcircuitandoneforthecoolingcircuit.Thethirdscheduleis
foruniversaluseandisfoundin'Commoncontrollersettings' .
A232.1:Relay4(X4)canbesettofollowthethirdschedule.
A332.1,A332.2,A332.3andA332.4:Relay5(X5)canbesettofollow
thethirdschedule.
Overridefunctions:
Bymeansofswitches,connectedtodifferentinputs,thefollowing
functionalitiesareavailablewhentheinputinquestionisactivated:
S7S8S9
A232.1
Stopthecirculationpump
OverridetoComfortorSavingmodeNofunction
A332.1
Stopthecirculationpump
OverridetoComfortorSavingmodeNofunction
A332.2
Stopthecirculationpump
OverridetoComfortorSavingmodeNofunction
A332.3
NofunctionNofunctionNofunction
A332.4
OverridetoHeating
OverridetoComfortorSavingmode
OverridetoCooling
12|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232,ingeneral,continued
Shortprocessdescriptions:
Changefromheatingtocooling(outdoorandroomtemperature
based):
1.Heatingactive
2.Outdoorandroomtemperaturerising
3.Heatingstopwhenactualoutdoortemperaturegetshigher
than'Summer,cut-out'(ID1x179)
4.Coolingstartwhen:
Accumulatedoutdoortemperaturevaluegetshigherthan
setlimit('Activation,acc.T',ID12144)
AND
Accumulatedroomtemperaturevaluegetshigherthanset
limit('Act.,acc.roomT',ID12156)
AND
Actualroomtemperaturegetshigherthandesiredroom
temperatureforcoolingoperation.
Changefromheatingtocooling(roomtemperaturebased):
1.Heatingactive
2.Roomtemperaturerising
3.Heatingstopwhenaccumulatedroomtemperaturevaluegets
higherthandesiredroomtemperatureforheatingoperation.
4.Coolingstartwhen:
Accumulatedroomtemperaturevaluegetshigherthanset
limit('Act.,acc.roomT',ID12156)
AND
Actualroomtemperaturegetshigherthandesiredroom
temperatureforcoolingoperation.
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
VI.JM.G3.02
©Danfoss|2018.11|13
OperatingGuideECLComfort210/296/310,applicationA232/A332
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
A232.1,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optional
surfacetemperaturelimitations.
14|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232.1,ex.b:
Controlofflowtemperature(heating/cooling)infloorinrelationtooutdoor,roomanddewpointtemperature.Optionalsurface
temperaturelimitation.
A232.1,ex.c:
Controlofflowtemperature(heating/cooling)toafan-coilinrelationtooutdoor,roomanddewpointtemperature.
VI.JM.G3.02
©Danfoss|2018.11|15
OperatingGuideECLComfort210/296/310,applicationA232/A332
A232.1,ex.d:
Controlofflowtemperature(heating/cooling)toafan-coilinrelationtooutdoor,roomanddewpointtemperature.Heatingsource:
Districtheating.Coolingsource:Coolingmachine.
A232.1,ex.e:
Controlofflowtemperature(heating/cooling)inrelationtooutdoor,roomanddewpointtemperature.Heating/coolingsources:
Districtheating/districtcooling.
16|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.1,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optionalreturn
andsurfacetemperaturelimitation.
AllA232.1examplescanbecontrolledbyA332.1.
A332.2,ex.a:
Separatedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpointtemperature.Optionalreturn
andsurfacetemperaturelimitations.
VI.JM.G3.02
©Danfoss|2018.11|17
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.2,ex.b:
Districtheating/districtcoolingbasedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpoint
temperature.Optionalreturnandsurfacetemperaturelimitations.
18|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.3,ex.aandb:
Separatedcontrolofflowtemperaturesforheating/coolinginrelationtooutdoor,roomanddewpointtemperature.AdvancedDHW
temperaturecontrolatDHWdraw-off.Anti-bacteriatemperaturecontrol.Optionalreturnorsurfacetemperaturelimitations.
VI.JM.G3.02
©Danfoss|2018.11|19
OperatingGuideECLComfort210/296/310,applicationA232/A332
A332.4,ex.a:
Controlofflowtemperature(heatinginfloor/coolinginceiling)inrelationtooutdoor,roomanddewpointtemperature.Optionalreturn
andsurfacetemperaturelimitation.Overridefunctionalitiesforheatingandcoolingmodes.
TheA232.1andA332.1examplescan,ingeneral,becontrolledbyA332.4.
20|©Danfoss|2018.11
VI.JM.G3.02
OperatingGuideECLComfort210/296/310,applicationA232/A332
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163