- 5 -
Power Input and Relay Output Pinouts
V2+ V2-
V1+ V1-
Shielded
Ground
Power
Power
N.O. Common
N.C.
Power
Power
Specifications
0 to 60°C (32 to 140°F)
Wide Temp. Model:
-40 to 75°C (-40 to 167°F)
36 x 105 x 140 mm (1.42 x 4.13 x 5.51 in)
MGate 4101-MB-PBS Series: 1,537,948 hrs
MGate 4101I-MB-PBS Series: 1,315,666 hrs
1. ATEX Certificate No.: DEMKO 14 ATEX 1311X
2. Protection Method: Ex nA nC IIC T4 Gc
3. IECEx Certificate No: IECEx UL 14.0065X
4. Standards: EN 60079-0:2012+A11:2013; EN 60079-15:2010;
IEC 60079-0 Ed.6; IEC 60079-15 Ed.4.
5. Conditions of safe usage:
• This equipment shall only be used in an area of not more than
pollution degree 2, as defined in IEC/EN 60664-1.
• This equipment shall be installed in an enclosure that provides a
degree of protection not less than IP54 in accordance with IEC/EN
60079-15. The enclosure should only be accessible by using a
tool (wrench, screw driver, etc.).
• Transient protection shall be provided that is set at a level not
exceeding 140% of the peak rated voltage value at the
equipment’s power supply terminals.
6. Ambient Temperature:
-40°C ≤ Tamb ≤ 75°C for MGate 4101X-MB-PBS-T models;
0°C ≤ Tamb ≤ 60°C for MGate 4101X-MB-PBS models.