B.E.G. LUXOMAT PD3-1C-Micro Installation and Operating Instruction

Category
Motion detectors
Type
Installation and Operating Instruction

This manual is also suitable for

B.I.T.
Q.C.
PASSED
1
Installation and Operating Instruction for B.E.G. - Occupancy detectors PD3-1C-SM/-FC/-FM and PD3-2C-FC/-FM
2a.
Installation of the LUXO-
MAT
®
PD3-SM
2c.
Installation of the
LUXO-
MAT
®
PD3-FM
LUXOMAT
®
PD3-1C(-Micro)/-2C
2b.
Installation of the
LUXO-
MAT
®
PD3-FC
Sensor and power supply in one case
Power supply: 230V~ +6%/-10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class: SM IP54, FC and FM IP20,
FC with accessory IP23 / II
Settings: locally
Area of coverage: circular 36
Range of coverage Ø H 2.50m / T = 18°C:
seated 2.50m / tangential 10m / radial 6 m
Recommended height for mounting: 2 - 3 m
Light measurement: mixed light, daylight + artificial light
Lux values - Potentiometer: 10 - 2000 Lux
• Channel 1 for light-connection
Type of contact: NOC/with pretravel tungsten contact
Contact load: 2000 W, 230V~, cos(ϕ) =1 /
1000 VA cos (ϕ) = 0.5
Time-settings: 30 sec. - 30 min. / Test
• Channel 2 for HVAC (only PD3-2C)
Contact load: 230 V~, 3 A cos (ϕ) =1
Time-settings: 5 min. - 120min. with time delay of 5 min.
for follow-up time > 15 min.
Dimensions H x Ø [mm] SM FC FM
PD3 52 x 106 84,5 x 80 65x 98
Visible portion when built into ceiling: 34 x 74mm
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC.
4.
Technical data
PD3
5. Trouble shooting
1. Lamp does not light up
Lamp may be defect:
Replace lamps
No mains connection/power:
Check connection and mains fuse by qualied electrician
Incorrect setting of CDS twilight threshold:
Correct setting of CDS threshold
Lens of sensor unit obstructed by dirt or other objects:
Clean lens, remove objects
2. Lamp turns ON too late or detection range too small
LUXOMAT
®
PD3 is mounted too high:
See table of mounting heights.
Correct mounting if required.
3. Lamp stays ON continuously
Continuous thermal activity detected ie fan, central heat-
ing ducts, animals within detection area:
Remove heatsource. Check proper function of LUXOMAT
®
PD3 by covering the fresnel-lens. After expiry of delay
timer, PD3 has to turn OFF lighting.
LUXOMAT
®
PD3 connected in parallel to a manual over-
ride switch:
Connect switch correctly
4. Unintended switching of light
Movement of heat source within detection area:
Check on presence of animals, fans or heaters
The detector can be installed
in conventional inlet-sockets
mounted on the ceiling.
The assembly plate enclosed
must be stripped off prior to
installation and secured to the
ceiling using 4 screws.
Having connected up the
cables in accordance with
regulations, the detector
can be placed in position
as shown in the drawing
opposite and, applying a little
pressure, can then be locked
into position with the assist-
ance of the spring clips.
The detector must be in-
stalled on a solid and level
surface. There is no need
for frames.
For mounting remove lens
(C) (turn anticlockwise).
Fasten the mounting base
to the ceiling.
Having connected up the wires in accordance
with regulations, secure the detector with 2
screws as per the illustration above.
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by qualified
professionals or by instructed persons
under the direction and supervision
of qualified skilled electrical person-
nel in accordance with electrotechni-
cal regulations.
Disconnect supply before installing!
The detector has
been designed
and developed
specifically for instal-
lation in suspended
ceilings.
A circular opening of
diameter 65mm must
be cut into ceiling.
Having connected up the cables in accor-
dance with regulations, the detector is
inserted into the opening as shown in the
drawing above and fixed into position with
the assistance of the spring clips.
e.g. 65 mm
GB
Type SM FC FM
PD3-1C 92190 92196 92186
PD3-1C-Micro 92219 92184
PD3-2C 92198 92188
Accessory:
BSK Ball basket guard 92199
FC-Covering IP23 92206
SM-Blinds 92260
7. Article / Part nr. / Accessory
6. Range of Coverage
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
walking across
walking towards
seated
1
2
10 m
6 m
2.50 m
10 m
360°
2.50 m
1
2
3. Putting into operation / Settings
Follow-up time for device control (PD3-2C)
The time can be set infinitely variably at between
5 and 120 minutes.
Follow-up time for light control
The time can be set infinitely variably at between
30 seconds and 30 minutes.
Symbol
: impulse < 1sec.
Symbol
TEST: Test mode
(Every movement switches on the light for a period of
1 second, switching it off for a period of 2 seconds
after that regardless of the level of brightness.)
Twilight-switch for light control
The switch-on value for the light can be set at
between 10 and 2000Lux. Using the rotary control,
the luminance set points can be set as desired.
Symbol
: Night-time operation
Symbol
: Daytime/Night-time operation
Adjusting sensitivity (PD3-1C)
For sensitivity adjustment of the detector, both in the
interior and the exterior range, the PD3-1C-SM/-FC
is equipped with an additional knob (see pictures)
for excluding sources of interference, e.g. bad
weather conditions or draught air.
Max: for interior use
(recognition of the slightest movements)
Min: for exterior use
(exclusion of sources of interference)
Sound (PD3-1C-Micro)
Max: highest sensitivity
Min: microphone switched off
Intermediate values to be adjusted accordingly to
local conditions. Lighting of the LED means the noise-
detector is functioning and triggers the timer again.
The microphone is active for 9 seconds after the last
movement and time delay completed.
120
60
50
40
30
15
10
A
16
10
5
2
1
30
15
TEST
2000
1200
600
200
40
5
max.
min.
max.
min.
2
4
6
8
12
30
secs
30
mins
1
min
TEST
2000
1200
600
200
40
40
50
60
90
120
5
mins
30
10
15
N
L
'
L
N
'
L
~6 m
6 m 7 m
18m
6 m
~6 m
6 m
12 m
6 m
6 m
4 m
6 m
8. Wiring diagrams
MAN 5789 – 161209-4
9. PD3 - Connections
Connection PD3-1C-SM
NL L'
Connection
PD3-1C-FC/-FM
NL L'N
Connection
PD3-2C-FC/-FM
N LL'
+
R2
10. PD3 - Dimensions
PD3-SM
PD3-FC
PD3-FM
11. Installation examples
Parallel-operation together with stairwell switch.
Alternatively switching by either motion detector or
stairwell switch.
L' N L
Parallel-operation with stairwell switch
Standby,
additionally manual switching is possible.
N
L
L' N L L' N L
Terminal connection voor parallel operation
L' N L
Switching with external switch PD3-1C-FC
L' N L
Permanent light operation with external switch
Standby
Switching is manually possible
(permanent light operation)
L' N L L' N L
Terminal connection for parallel-operation
Parallel switching
Max. 8 occupancy detectors keep settings (Lux and
time) the same.
L' N L
Standard operation with opt. arc extinctions kit
Arc
extinction kit
Standby
Optional extension for switching of parallel
inductors, rocker switches, uorescent lamps etc.
L
N
Terminal connection for parallel-operation PD3-2C-FC
+
dry
contact
Circuit like PD3-1C-FC, but additional with two dry
contact (relay 2).
R L' N L
645
5
15
R L' N L L NO NO
3A
230VAC
50-60Hz
Slave /
Remote
84.5
74
R L' N L L NO NO
3A
230VAC
50-60Hz
Slave /
Remote
98
72
13
13
35
65
16
48x4825 25
14
52
106
  • Page 1 1
  • Page 2 2

B.E.G. LUXOMAT PD3-1C-Micro Installation and Operating Instruction

Category
Motion detectors
Type
Installation and Operating Instruction
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI