Sensor and power supply in one case for onwall-, ceiling-
and flushmounting
Power supply: 230V~ +6 %/-10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class: SM IP54, FC and FM IP20, FC
with accessory IP23 / II
Settings: manually and by remote control
Light values: 20 - 1000 Lux (Remote control)
Extension of the detection area: with Slaves
Area of coverage: square 4 x 90°
Range of coverage Ø H 2,50 m / T = 18°C:
seated 4.20m / tangential 7.50m / radial 4.50 m
Recommended height for mounting: 2 - 3 m
Light measurement: mixed light, daylight + artificial light
Lux values: 10 - 2000 Lux (Potentiometer)
• Relay/Channel 1 for light-connection
Type of contact: dry contact type NO
Contact load: 2300 W cos(ϕ) =1 / 1150 VA cos(ϕ) =0.5
Time-settings: 15sec. - 16 min. (30 min. with remote
control) / Test
• Relay/Channel 2 for HVAC
Contact load: 230 V~, 3 A cos(ϕ) =1
Time-settings: 5 min. - 120 min. with time delay of 5 min.
for follow-up time > 15 min.
Dimensions
H x Ø [mm]
SM FC FM
PD1-M-2C 80 x 98 84 x 98 65 x 98
Visible portion when built into ceiling: 30 x 98 mm
Technical data PD1-Slave
Electrical data same as above, but just one channel for
signaling motion detection
Declaration of Conformity: The product complies with
the low voltage recommendation 2006/95/EC and the
EMV recommendation 2004/108/EC
11.
Technical data PD1-Master-2C
10. PD1-M-2C - Connections
Type SM FC FM
PD1-M-2C (Master) 92177 92174 92170
PD1-S (Slave) 92178 92175 92172
LUXOMAT
®
Remote control:
IR-PD (incl. wall bracket) 92160
IR-PD-Mini 92159
Accessory:
BSK Ball basket guard 92199
Wall bracket for remote control as replacement
92100
Blinds 92260
Occupancy detectors - Covering IP23 92206
SM-Socket for PD1-FM 92171
8. Article / Part nr. / Accessory
MAN 6316 – 211209–1
7. Range of Coverage
5. Fully / Semi automatic mode
(for IR-PD functions see page 1)
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on. Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “R” button input (ON/OFF).
6. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the congured
follow up time.
12. LED-functional indicators, fault-finding
The functional indicators in the case of the LUXOMAT
®
PD1-M-2C (red and green LED‘s)
Red LED indicating self-checking mode (over a period
of 60 seconds following mains‘-supply lock-on)
Flashing at intervals of 1 second
EEPROM/memory empty
Flashing rapidly
EEPROM/memory contains information
Red LED as an indicator of status
Flashing irregularly
Movements are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
Flashing extremely rapidly
Too bright / Too dark / Undefined
Red LED as an acknowledgement of receipt for
commands from the remote control
Illuminated for 2 seconds
Signal validly received
Illuminated for 0.5 seconds
Not-accepted command, detector blocked
Flashing extremely rapidly
Not-accepted command, occurs, for example, when
an attempt is made to input twilight-value are too
bright or too dark
Lights up for 3 seconds
Fully automatic mode
Flashing for 3 seconds
Semi automatic mode
Green LED as an indicator of status (only for status
“Permanent protection against sabotage”)
Flashing irregularly
Movement are detected within the area of coverage
Flashing regularly
Detector identifies bright, light off
(dependent upon operating mode)
Not illuminated
Detector identifies dark, light on
(dependent upon operating mode)
lluminated for 2 seconds
Signal validly received
(dependent upon operating mode)
7.50 m
4.20 m
7.50 m
4 x 90°
2.50 m
1
2
1
Connection PD1-M-2C
NONO
NR L L
SLAVE
L'
3A
2
9. Wiring diagrams
Standard operation, manual switching possible
(NO-contact to be pressed for approx. 1sec.). The
potentiometers not to be set on “Test“ or “Sun“
otherwise the preadjusted values will get lost during
this manual operation.
Master-/Slave-operation, i.e. Masters opera-
te as Slaves but with additional push button
function to switch the light manually. The preset
values will not get lost. The Master is the only unit to
read in the levels and to switch the connected loads.
The Slave units will react on motion only, independ-
ently of the Lux levels, by sending an impulse via the
dry contact, to the Master.
Terminal connection for Master-/Slave-operation
R 2
MASTER MASTER/SLAVE
modus
Master-/Slave-operation with one Master
and several Slaves. The Master is the only unit
to read in the Lux levels and to switch the connected
loads. The Slave units will react on motion only, in-
dependently of the Lux levels, by sending an impulse
via the dry contact, to the Master.
Terminal connection for standard operation
HVAC
MASTER
HVAC
SLAVE
MASTER
Terminal connection for Master-/Slave-operation
Standard operation with external push button
HVAC
MASTER
Standard operation
3
3