Danfoss VLT 5000 Flux (Legacy Product) Operating instructions

Type
Operating instructions
Drives Solutions
www.danfoss.com/drives
Instruction Manual
DeviceNet
VLT
®
5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA
VLT
®
5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA
Instruction Manual
175R5287 MG50H422
XREF__BC
NOT LOADED ON RIP
*MG50H422*
REV. 2003-04-28
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Contents
Introduction to Danfoss VLT series and DeviceNet
...................... 2
Product Overview ................................................................................................... 2
Product and Environment ....................................................................................... 2
Overall Function ..................................................................................................... 2
Network ................................................................................................................. 2
User Profile ............................................................................................................. 2
Data Communication Interface ............................................................................... 2
Initialization of VLT frequency converter Interface .................................................... 2
Network Variable Handling ..................................................................................... 3
Error Handling ........................................................................................................ 3
Overall Function ..................................................................................................... 3
Technical Data .................................................................................................. 5
Identity Object ........................................................................................................ 5
Message Router ..................................................................................................... 5
General Information ................................................................................................ 5
Network Power Supply ........................................................................................... 5
Cable Lengths ........................................................................................................ 6
Cable Specifications ............................................................................................... 6
Cable Cross Section ............................................................................................... 7
Connection of the Cable Screen ............................................................................. 7
Earth Connection ................................................................................................... 7
DeviceNet Connection ............................................................................................ 7
User Interface ......................................................................................................... 8
Understanding Module Configuration Switches ...................................................... 9
EMC Precautions ................................................................................................... 10
Setting the DeviceNet Node Address ..................................................................... 11
Switch Settings for DeviceNet Node Addressing .................................................... 11
Setting the Baud Rate ............................................................................................ 11
VLT Response Time ............................................................................................... 12
General Purpose Discrete I/O ................................................................................. 12
I/O Assembly Instances .......................................................................................... 12
Fieldbus Profile ................................................................................................ 13
Fieldbus Profile ....................................................................................................... 13
Control Word .......................................................................................................... 13
Status Word ........................................................................................................... 15
Control Word under VLT standard .......................................................................... 17
Status Word under VLT standard ............................................................................ 18
Control Word and Status Word under Instance 20/70 ............................................ 19
Programming .................................................................................................... 20
Quick Setup ........................................................................................................... 20
Special Attention .................................................................................................... 20
Warning and Alarm Messages ................................................................................ 26
Factory Settings ..................................................................................................... 27
MG.50.H4.22 - VLT is a registered Danfoss trademark
1
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Product Overview
Product and Environment
The DeviceNet Option Card is an interface between
the DeviceNet serial communication bus and the VLT
frequency converter from Danfoss. The option card
will function as an integrated part of the drive.
DeviceNet is a distributed control network. The
DeviceNet protocolis embedded in the controller option
cardand is acommunication protocol conformingto the
Open DeviceNet Vendor Association (ODVA) standard.
The option card allows DeviceNet compatible
controllers, sensors, and network management tools
to control, monitor, and supervise the VLT frequency
converter. The option is designed to the DeviceNet
System Protocol for Vendors as a slave device.
Overall Function
A DeviceNet compatible device has the ability to
perform the following operations with the VLT frequency
converter over the DeviceNet network:
1. Control speed references and send drive
control commands.
2. Monitor the status of the drive, access alarm
and warning messages, and monitor drive
and motor information.
3. Upload and download drive settings, configure
drives, and also perform the operations
defined in 1 and 2.
Therefore, the level of control and flexibility of the VLT
frequency converter over the network depends on
the capabilities built into the controlling device.
The application program has the following functions:
1. Support interger parameters through the
dual ported RAM.
2. Manipulate the dual ported RAM parameters
to interface with the CAN.
3. Monitor network activity "watchdog" function to
determine Master – Slave communication continuity.
Network
The VLT frequency converter will function as a slave
on the DeviceNet network. All addressing and linking
tonodesisdoneatinstallationtimebyanetwork
manager tool. The network installer and the network
management master have a significant influence on
how the node functions on the network. A DeviceNet
network can support up to 64 nodes.
User Profile
The end-user is a network manager programmer or
a controller who see the DeviceNet control card as
a transparent bridge to the VLT frequency converter.
Control and supervision of the VLT frequency converter
will still be possible through the standard parameter set.
Data Communication Interface
No direct data communication interface (e.g. via a
serial port) other than the DeviceNet interface and the
VLT frequency converter interface is considered.
Initialization of VLT frequency converter Interface
The VLT frequency converter interface is initializ
ed in
three phases. The first two phases are initiated and
controlled by the VLT which will write commands to
the option card through the dual port RAM.
MG.50.H4.22 - VLT is a registered Danfoss trademark
2
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Introduction to
Danfoss VLT series
and DeviceNet
Phase 1:
Is the initialization of the communication system.
During this phase the option card must respond
correctly to the VLT frequency converter initialization
command or else the VLT will not function and
display a "No Option Init" message.
Phase 2:
Is the interface watchdog function performed by
the option card as the first operational action. After
completion of this phase, data can be passed between
the VLT frequency converter and the option card
through the command channel in the dual port RAM.
Phase 3:
TheVLT frequencyconverterwill writeto the Initialization
Channel of the dual port RAM which will set the
displacement values of the various channels (Control
Channel, Status Channel, Command Channel 1,
Command Channel 2, Command Channel 3, Warning
Channel, and Spontan Channel), and the DeviceNet
option card software will read these displacements
and return a response to the VLT frequency converter
notifying that the initialization was successful or an
error was obtained in the process.
During operation (after initialization) the dual port RAM
interface is supervised by a watch-dog in the VLT
frequency converter. The VLT frequency converter will
be kept "alive" by cyclic writing to a channel in the dual
port RAM by the watch-dog handler of the option card.
Network Variable Handling
The parameter access network variable is a structure
containing parameter number, data, value, and a
function code containing a read or write command.
The application program shall receive the data,
validate the data, convert the data to the format of
the VLT frequency converter, process the read or
write of the parameter, then send the information
back in an output network variable of the same
structure. This output variable would contain the
parameter number, error code information in the event
of an exception, and parameter value.
Error Handling
The option card will stop sending a watchdog signal
to the VLT frequency converter when:
1. The node has been disconnected from the network
2. A network management tool has the
Option Card go Off-line
3. A hardware fault on the DeviceNet Option Card
PCB prevents reliable operation
By withholding the watchdog message, the VLT
frequency converter can detect a "Bus Time-out"
and enter secure, pre-defined state.
For recoverable errors such as [1] and [2] the option
card shall re-send the watchdog message when
the fault or condition has disappeared such as after
re-connection of the node to the network.
For unrecoverable errors such as [3] the application
program shall permit logging of network errors
without resetting or restarting the microprocessor.
This will send information to a network management
tool that will allow appropriate actions to be taken.
The only way to recover from a serious error is to
re-initialize the VLT frequency converter DeviceNet
option card by cycling power.
In case of serious VLT frequency converter fault, the
DeviceNet processor shall hold the CAN chip reset,
thereby disabling any communication to the node until
the VLT frequency converter has been re-initialized.
Overall Function
DeviceNet is a low-level network that standa
rdizes
communications between industrial devices (sensors,
limit switches) and high level devices (controllers).
The communication network can be peer to p
eer or
master/slave. DeviceNet uses CAN technology for
Media Access Control and Physical Signaling and it
supports up to 64 nodes. DeviceNet also
defines
device profiles for devices belonging to specific classes.
For other devices, a custom class must be defined in
order to make it DeviceNet com
patible. This further
enhances the interchangeability and interoperability of
the network. Each node on the network has its own
unique media access contro
lidentifier(MACID)to
distinguish it on the network. The MAC ID is stored
in the header of the message which is split into four
different message group
s. However, DeviceNet only
makes use of three message groups keeping the fourth
one for future use. If two nodes attempt to get control
ofthenetworkbussimu
ltaneously, the CAN protocol
MG.50.H4.22 - VLT is a registered Danfoss trademark
3
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
resolves the issue by arbitration. A dominant bit (0)
will win arbitration over a recessive bit (1).
For the VLT frequency converter, the option card
will be slave node on the DeviceNet network. The
option card will be a message server that will request
andsetparametersintheVLTviaadualported
RAM interface. The option card has an embedded
CAN controller that will screen all network messages
with a Mask and Match register. This feature
allows the option card to filter out any unwanted
messages from the network. The option card will
receive group 2 and group 3 messages. Group 2
messages allows the option card to use the predefined
Master/Slave connection set which identifies a use
for all group 2 message identifiers. The ability to
receive Group 3 messages allows the option card to
also be an Unconnected Explicit Message Manager
(UCMM) with the UCMM request and response
message identifier. Explicit message connections
are unconditionally point-to-point. Point-to-point
connections exist between two devices only.
MG.50.H4.22 - VLT is a registered Danfoss trademark
4
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Technical
Data
Technical Data
Identity Object
This object is used to provide identification and
general information about the device. This object
is required by all DeviceNet products.
This object requires no class attributes. Its instance
attributes are the following:
Vendor 97
Device Type 2
Product Code Depends of the Drive
Revision - Major, Minor Depends of option
Status
Serial Number
Product Name VLT 5000
Message Router
The Message Router object provides a messaging
connection point through which a Client may
address a service to
any object class or instance
residing in the physical device.
This object requires no class attributes. Its instance
attributes are the following:
1. Object List - Number of Classes
General Information
Parameter 502 = "BUS".
Otherwise terminals 12 and 27 of the control card
must be connected, before motor start. In parameters
502-508 it is possible to define how to gate the control
commands from the DeviceNet with the equivalent
control commands of the digital inputs.
Network Power Supply
The DeviceNet option is an optically isolated node,
where transceiver power is provided by the network.
External network power supply requirements are:
-11-25VDC
- 70 mA draw per VLT 5000 DeviceNet node
MG.50.H4.22 - VLT is a registered Danfoss trademark
5
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Cable Lengths
Drop LengthBaud Rate Max. total cable length [m]
Maximum Cumulative
125k baud 500 meters (1640 ft.) 156 meters (512 ft.)
250k baud 250 meters (820 ft.) 78 meters (256 ft.)
500k baud 100 meters (328 ft.)
6 meters (20 ft.)
for one drop
39 meters (128 ft.)
Cable Specifications
Physical Characteristi
cs
Specification
Two shielded pairs Common axis with drain wire in center
Overall braid shield 65% coverage 36 AWG Cu braid.
(individually tinned)
Drain wire # 18 (19 x 30 AWG) Copper (individually tinned)
Outside diameter 0.475 ± 0.015 inches (rou
nd),
roundness - radius delta to be within 15% of 0.5 O.D.*
Jacket insulation * 0.040 inches minimum
Jacket marking * VendorName&Part#1Pr18and1Pr15AWG
shielded, additional markings are acceptable
Electrical Characteristics Specification
DRC (braid + tape + drain) 1.75 Ohms/1000 ft. (nom. @ 20°C)
Applicable Environmental Characteristics Specification
Agency Certifications (U.S. and Canada) NEC (UL) type, CL2/CL3 (min.)
Bend radius - installation / fixed 20xdiameter/7xdiameter
Operating ambient temperature -20° to + 6C @ 8 amps; de-rate current linearly to
zero @ 80°C
Storage temperature -40° to + 85°C
Pull tension 190 Ibs max
* Other types of jacket insulation are allowable
provided that internal construction and electrical
charactersitics adhere to this specification.
MG.50.H4.22 - VLT is a registered Danfoss trademark
6
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Technical
Data
Cable Cross Section
Connection of the Cable Screen
The screen of the DeviceNet cable must always
be connected to ground at both ends, that means
the screen must be connected to ground in all
stations connected to the DeviceNet network. It is
veryimportanttohavealowimpedanceground
connection of the screen, also at high frequencies.
This can be obtained by connecting the surface
of the screen to ground, for example by means of
a cable clamp or a conductive cable gland. VLT
frequency converter Series are provided with different
clamps and brackets to enable a proper ground
connection of the DeviceNet cable screen. The
screen connection is shown in the drawing.
Earth Connection
It is important that all stations connected to the
DeviceNet network are connected to the same earth
potential. The earth connection must have a low HF
(high frequency) impedance. This can be achieved
by connecting a large surface area of the cabinet to
ground, for example by mounting the VLT frequency
converter on a conductive rear plate. Especially
when having long distances between the stations
in a DeviceNet network it can be necessary to use
additional potential equalizing cables, connecting the
individual stations to the same earth potential.
DeviceNet Connection
It is essential that the bus line be terminated properly.
A mismatch of impedance may result in reflections on
the line that will corrupt data transmission.
The DeviceNet Option Card is provided with a
pluggable screw connector.
By using a pluggable screw connector as a splice
between two trunk lines, removal of devices will
not sever the network. Strain relief, if required,
must be provided by the developer. In current
installations of this type of connector, the strain
relief is attached to the product.
NOTE
Wires should not be installed while the
network is active. This will prevent problems
such as shorting the network supply or
disrupting communications.
MG.50.H4.22 - VLT is a registered Danfoss trademark
7
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
User Interface
The DeviceNet option card contains two bi-color
(green/red) LEDs for each connector hookup
port, to indicate the state of the device and
network, respectively.
For the device status LED:
1. whentheLEDisoff,thedeviceisoff
2. when the LED is green, the device is operational
3. When the LED is flashing green, the device
is in standby
4. when the LED is flashing red, the device
detects a minor fault
5. when the LED is red, the device detects
an unrecoverable fault
6. when the LED is flashing red/green, the
device is self testing
For the network status LED:
1. when the LED is off, the network is
non-powered/not online
2. when the LED is flashing green, the network
is online but not connected
3. when the LED is green, the network is
online and connected
4. when the LED is flashing red, the network
has a connection time-out
5. when the LED is red, the network has a critical link
failure. No further direct user interface is considered
No further direct user interface is considered.
MG.50.H4.22 - VLT is a registered Danfoss trademark
8
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Technical
Data
Understanding Module Configuration Switches
The DeviceNet Communication modulesDIP
switch settings determine:
DeviceNet node address
DeviceNet baud rate
When you make changes to the switch
settings, use a pointed instrument such
as a ball point pen. DO NOT use a
pencil because damage may occur
Unpredictable operation may occur if
you fail to check connections and DIP
switch settings for compatibility with your
application. Unpredictable operation may result in
death, personal injury, and equipment damage.
Hazard of injury or equipment damage
may occur due to unintended or incorrect
machine motion. When a system
is configured for the first time, the motor must
be disconnected from the machine or process
during initial system testing.
NOTE
When setting the Communication Modules
addressing Dip Switches, you must ensure
that each serial device on the network has a
unique address. Also, all devices connected to the
network must be set at the same baud rate.
MG.50.H4.22 - VLT is a registered Danfoss trademark
9
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
EMC Precautions
EMC precautions The following EMC precautions are
recommended to obtain interference free operation of
the DeviceNet network. Additional information on EMC
can be found in the VLT 5000 Series Instruction Manual.
NOTE
Relevant national and local regulations,
for example regarding protective earth
connection, must be observed
The DeviceNet communication cable must be kept
away from motor and brake resistor cables to avoid
coupling of high frequency noise from one cable
to the other. Normally a distance of 8 inches (200
mm) is sufficient, but it is generally recommended
to keep the greatest possible distance between
the cables, especially where cables are running
in parallel over long distances.
If the DeviceNet cable has to cross a motor
and brake resistor cable they must cross each
other at an angle of 90°.
MG.50.H4.22 - VLT is a registered Danfoss trademark
10
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Technical
Data
Setting the DeviceNet Node Address
Dip switches 6 through 1 set the modulesnode
address using binary addressing.
Switch Settings for DeviceNet Node Addressing
Follow these steps to set the DeviceNet node address:
1. Refer to the table below for the switch settings
of a specific address.
2. Using your finger or a pointed object, slide switches
1 through 6 to the appropriate ON/OFF positions.
DeviceNet
Address
Switch
Settings
1
6
DeviceNet
Address
Switch
Settings
1
6
DeviceNet
Address
Switch
Settings
1
6
DeviceNet
Address
Switch
Settings
1
6
0 000000 16 000010 32 000001 48 000011
1 100000 17 100010 33 100001 49 100011
2 010000 18 010010 34 010001 50 010011
3 110000 19 110010 35 110001 51 110011
4 001000 20 001010 36 001001 52 001011
5 101000 21 101010 37 101001 53 101011
6 011000 22 011010 38 011001 54 011011
7 111000 23 111010 39 111001 55 111011
8 000100 24 000110 40 000101 56 000111
9 100100 25 100110 41 100101 57 100111
10 010100 26 010110 42 010101 58 010111
11 110100 27 110110 43 110101 59 110111
12 001100 28 001110 44 001101 60 001111
13 101100 29 101110 45 101101 61 101111
14 011100 30 011110 46 011101 62 011111
15 111100 31 111110 47 111101 63 111111
Setting the Baud Rate
Dip switches 7 and 8 set the baud rate at which
the Communication Module communicates on the
network. The factory default setting is 125K BPS.
Switch Settings for DeviceNet Module Baud Rate:
Baud Rate Switch Setting
7
Switch Setting
8
125 kBPS 0 0
250 kBPS 1 0
500 kBPS 0 1
125 kBPS 1 1
MG.50.H4.22 - VLT is a registered Danfoss trademark
11
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
VLT Response Time
The update time via the DeviceNet connection
can be divided into two parts:
1. The communication time, which is the time it
takes to transmit data from the master to the
slave (VLT with DeviceNet option).
2. The internal update time, which is the time it takes
to transmit data between the VLT 5000 control
card and the DeviceNet option card.
Communication time (t
com
) depends on the actual
transmission speed (baudrate) and the type of master
in use. More data or lower transmission speed
will increase the communication time.
The internal update time (t
int
) depends on the type of
data in question as there are different channels for
the data transfer where time critical data e.g. control
word has highest priority. The internal update time for
the different types of data are stated below.
Data Update
time, t
int
Control word/Main reference (part of
PPO)
2msec
Status word/Actual output frequency
(part of PPO)
2msec
Parameter read via PCD-part of PPO 2 msec
Parameter write via PCD-part of PPO 83 msec
Parameter read/write via explicite
message
22 msec
General Purpose Discrete I/O
The General Purpose Discrete I/O device I/O
assemblies consist of:
five predefined input assemblies with single
status bits
one product–specific input assembly with
asinglestatusbit
five predefine input assemblies with multiple
status bits
one product–specific input assembly with
multiple status bits
five predefined output assemblies
one product–specific output assembly
I/O Assembly Instances
The I/O Assembly Instance definitions in this section
define the format of the "data" attribute (attribute 3)
for I/O Assembly Instances. I/O Assemblies support
a hierarchy of motor control devices. The device
hierarchy includes motor starters, soft starters, AC
and DC drives, and servo drives. Assembly Instances
are numbered within the hierarchy so that each
device type is assigned a range of Assembly Instance
numbers, with higher functionality devices supporting
higher instance numbers. Devices in the hierarchy
can choose to support instance numbers that are
lower than theirs in the hierarchy. For example an AC
drive may choose to support some I/O Assemblies
in the starter profile to make it easier to interchange
starters and drives within the system.
Parameter
904
Decimal WRITE Decimal READ
PP03 20 CTW SPEED
RPM
70 STW AC
REF
PP01 100 CTW REF 150 STW MAV
PP02 101 CTW REF 915.1 915.2 151 STW MAV 916.1 916.2
PP04 102 915.1 915.2 915.3 915.4 152 916.1 916.2 916.3 916.4
MG.50.H4.22 - VLT is a registered Danfoss trademark
12
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Fieldbus
Profile
Fieldbus Profile
Control Word
C
ontrol Word as per Profidrive standard
(parameter 512 = Fieldbus Profile). The control word is
used for transmitting commands from a master (e.g.
aPC)toaslave(VLTfrequencyconverter).
Bit Bit = 0 Bit =1
00 OFF 1 ON 1
01 OFF 2 ON 2
02 OFF 3 ON 3
03 Motor coasting Enable
04 Quick stop Ramp
05 Freeze output
frequency
Ramp enable
06 Ramp stop Start
07 No function Reset
08 Jog 1 OFF ON
09 Jog 2 OFF ON
10 Data not valid Valid
11 No function Slow down
12 No function Catch
13 Choice of Setup (lsb)
14 Choiceof Setup(msb)
15 No function Reversing
Bit 00, OFF1/ON1:
An ordinary ramp stop which uses the ramp time
in parameters 207/208 or 209/210. Bit 00 = "0"
leads to a stop and leads to output relay 01 or
04 being activated, the output frequency is 0 Hz,
provided Relay 123 has been selected in parameter
323 or 326. Bit 00 = "1" means that the adjustable
frequency drive will be able to start if the other
conditions for starting have been fulfilled.
B
it 01, OFF2/ON2:
Coasting stop. Bit 01 = "0" leads to acoasting stop and
leads to output relay 01 or 04 being activated, when the
output frequency is 0 Hz, provided Relay 123 has been
selected in parameter 323 or 326. Bit 01 = "1" means
that the adjustable frequency drive is able to start
provided the other conditions for starting are fulfilled.
B
it 02. OFF3/ON3:
Quick-stop, which uses the ramp time set in parameter
212. Bit 02 = "0" leads to a quick stop and leads
to output relay 01 or 04 being activated, when the
output frequency is 0 Hz, provided Relay 123 has been
selected in parameter 323 or 326. Bit 02 = "1" means
that the adjustable frequency drive is able to start,
provided the other conditions for starting are fulfilled.
B
it 03, Coasting/enable:
Coasting stop. Bit 03 = "0" leads to a stop. Bit 03 =
"1" means that the adjustable frequency drive is able
to stop, provided the other conditions for starting are
fulfilled. Note: in parameter 502 the choice is made
as to how bit 03 is to be combined (gated) with the
corresponding function in the digital inputs.
B
it 04, Quick-stop/ramp:
Quick-stop which uses the ramp time in parameter
212. Bit 04 = "0" leads to a quick- stop. Bit 04 =
"1" means that the adjustable frequency drive is able
to start, provided the other conditions for starting are
fulfilled. Note: In parameter 503 the choice is made
as to how dit o4 is to be combined (gated) with the
corresponding function on the digital inputs.
B
it 05, Freeze output frequency/ramp enable:
Bit 05 = "0" means that the given output frequency is
maintained even if the reference is changed. Bit 05 =
"1" means that the adjustable frequency drive is again
able to regulate, and the given reference is followed.
B
it 06, Ramp stop/start:
An ordinary ramp stop that uses the ramp time in
parameters 207/208 or 209/210; in addition, output
relay 01 or 04 will be activated when the output
frequency is ) Hz, provided Relay 123 has been
selected in parameter 323 or 326. Bit 06 = "0" leads
to a stop. Bit 06 = 1" means the adjustable frequency
drive is able to start, provided the other conditions for
starting are fulfilled. In parameter 505 the choice is
made as to how bit 06 is to be combined (gated) with
the corresponding function on the digital inputs.
B
it 07, No function/reset:
Reset of trip. Bit 07 = "0" means that there is no
reset. Bit 07 = "1" means that a trip is reset.
MG.50.H4.22 - VLT is a registered Danfoss trademark
13
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Bit 08, Jog 1 OFF/ON:
Activation of pre-programmed speed in parameter
509 (Bus Jog 1). JOG 1 is only possible when
Bit 04 = "0" and bit 00-03 = "1".
B
it 09, Jog 2 OFF/ON:
Activation of pre-programmed speed in parameter
510 (Bus Jog 2). JOG 2 is only possible when Bit
04 = "0" and bits 00-03 = "1". If both JOG 1 and
JOG 2 are activated (bits 08 and 09 = "1"), JOG 1
has the higher priority, which means that the speed
programmed in parameter 509 will be used.
B
it 10, Data not valid/valid:
Used for telling VLT 5000 whether the control word is
to be used or ignored. Bit 10 = "0" means that the
control word is ignored. Bit 10 = "1" means that the
control word is used. This function is relevant because
the control word is always contained in the telegram,
regardless ofthe type oftelegram used, i.e. it is possible
to disconnect the control word if it is not to be used in
connection with updating or reading of parameters.
B
it 11, No function/slow down:
Used for reducing the speed reference by the
value in parameter 219. Bit 11 = "0" means that
thereisnochangeofthereference. Bit11="1"
means that the reference is reduced.
B
it 12, No function/catch-up:
Used for increasing the speed reference by the value of
parameter 219. Bit 12 = "0" means that the refe
rence
is increased. If both slow down and catch-up are
activated (bits 11 and 12 = "1"), slow down has the
higher priority, i.e. the speed reference
is reduced.
B
its 13/14, Choice of Setup:
Bits 13 and 14 are used for choosing among the
four menu Setups in accordance with:
Setup Bit 14 Bit 13
100
201
310
411
This function is only possible if Multi-Setups have
been selected in parameter 004.
NOTE
Parameter 507 is used for choosing how bits
13/14 are to be combined (gated) with the
corresponding function on the digital inputs.
B
it 15, No function/reversing:
Reversing of the direction of rotation of the
motor. Bit 15 = "0" leads to no reversing, bit
15 = "1" leads to reversing.
Note that as a point of departure reversing has
been selected as Digital in parameter 506. Bit 15
only leads to reversing if bus, logical or or logical
and has been selected (logical and, however,
only together with terminal 19).
NOTE
Unless otherwise mentioned, the control
word bit is combined (gated) with the
corresponding function on the digital
inputs as a logical "or" function.
MG.50.H4.22 - VLT is a registered Danfoss trademark
14
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Fieldbus
Profile
Status Word
S
tatus Word (according to Profidrive standard
(parameter 512 = Fieldbus Profile). The status word
is used for informing the master (e.g. a PC) of the
condition of a slave (VLT frequency converter).
Bit Bit = 0 Bit =1
00 Control not ready Ready
01 VLT not ready Ready
02 Motor coasting Enable
03 NO fault Trip
04 ON 2 OFF 2
05 ON 3 OFF 3
06 Start enable Start disable
07 No warning Warning
08 Speed - reference Speed = ref.
09 Local control Bus control
10 Out of operating
range
Freq. limit OK
11 Not running Running
12 VLT OK Stalls, auto-start
13 Voltage OK Above limit
14 Torque OK Above limit
15 Timer OK Above limit
Bit 00, Control not ready/ready:
Bit 00 = "0" means that bit 00, 01 or 02 of the control
word is "0" (OFF1, OFF2 or OFF3), or that the adjustable
frequency drive has tripped. Bit 00 = "1" means that
the adjustable frequency drive is ready, but that there
is not necessarily any supply to the power component
(in case of external 24 V supply to the controls).
B
it 01, VLT not ready/ready:
Samemeaningasbit00;however,thereisalsoa
supply to the mains component, and the adjustable
frequency drive is ready to run when it receives
the necessary start signals.
B
it 02, Coasting/enable:
Bit 02 = "0" means that the control word bit 00, 02
or 03 is "0" (OFF1, OFF2, OFF3 or Coasting), or the
VLT 5000 Series unit has tripped. Bit 02 = "1" means
that the control word bits 00, 01, 02 or 03 are "1"
and that VLT 5000 Series has not tripped.
B
it 03, No fault/trip:
Bit 03 = "0" means that VLT 5000 Series is not in a fault
condition. Bit 03 = "1" means that VLT 5000 Series has
tripped and needs a reset signal in order to run.
B
it 04, ON2/OFF2:
Bit04="0"meansthatcontrolwordbit01="1".Bit
04 ="1" means that control word bit 01 ="0".
B
it 05, ON3/OFF3:
Bit05="0"meansthatcontrolwordbit02="1".Bit
05 -"1" means that control word bit 02 ="0".
B
it 06, Start enable/start disable:
Bit 06 is always "0" if Danfoss has been selected in
parameter 512. If Profidrive has been selected in
parameter 512, bit 06 will be "1" after reset of a trip,
after activation of OFF2 or OFF3 and after connection
of mains voltage. Start disable is reset, setting control
word bit 00 to "0" and bits 01, 02 and 10 to "1".
B
it 07, No warning/warning:
Bit 07 = "0" means that there is no unusual situation.
Bit 07 = "1" means that an abnormal condition has
arisen for the VLT 5000 Series. All warnings described
in the VLT 5000 instruction manual will set bit 07 to "1".
B
it 08, Speed ref/speed. = ref.:
Bit 08 = "0" means that the actual motor speed is
different from the speed reference set. This can be
thecasewhilethespeedisrampedup/downduring
start/stop. Bit 08 = "1" means that the present motor
speed equals the speed reference set.
B
it 09, Local control/Bus control:
Bit 09 = "0" means that VLT 5000 Series has been
stopped by means of the stop key on the control panel,
or that Local operation has been selected in parameter
002. Bit 09 = "1" means that it is possible to control
theadjustablefrequencydriveviatheserialport.
B
it 10, Out of operating range/Freq. limit OK:
Bit 10 = "0" means that the output frequency is
out of the range set in parameter 225 (Warning:
Low frequency) and parameter 226 (Warning: High
frequency). Bit 10 = "1" means that the output
frequency lies within the mentioned range.
B
it 11, Does not run/runs:
Bit 11 = "0" means that the motor is not running. Bit
11 = "1" means that VLT 5000 Series has a start signal
of that the output frequency is greater than 0 Hz.
MG.50.H4.22 - VLT is a registered Danfoss trademark
15
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Bit 12, VLT OK/stalling, autostart:
Bit 12 = "0" means that there is no temporary
overtemperature on the inverter. Bit 12 =1" means that
the inverter has stopped because of overtemperature,
but that the unit has not tripped and will continue,
once the overtemperature stops.
B
it 13, Voltage OK/above limit:
Bit 13 = "0" means that the voltage limits of VLT
5000 Series have not been exceeded. Bit 13 = "1"
means that the DC voltage of the VLT 5000 Series
intermediate circuit is too low or too high.
B
it 14, Torque OK/above limit:
Bit 14 = "0" means that the motor current is
lower than the torque limit selected in parameter
221. Bit 14 = "1" means that the torque limit in
parameter 221 has been exceeded.
B
it 15, Timers OK/above limit:
Bit 15 = "0" means that the timers for the motor thermal
protection and VLT thermal protection, respectively,
have not exceeded 100%. Bit 15 = "1" means that
one of the timers has exceeded 100%.
MG.50.H4.22 - VLT is a registered Danfoss trademark
16
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Fieldbus
Profile
Control Word under VLT standard
(parameter 512 = FC Profile). The control word is
used for sending commands from a master (e.g. a
PC) to a slave (VLT frequency converter).
Bit Bit = 0 Bit =1
00 Preset reference
choice Isb
ON 1
01 Preset reference
choice msb
ON 2
02 DC brake Ramp
03 Coasting Enable
04 Quick stop Ramp
05 Hold Ramp enable
06 Ramp stop Start
07 No function Reset
08 No function Jog
09 Ramp 1 Ramp 2
10 Data not valid Valid
11 No function Relay 01 activated
12 No function Relay 04 activated
13 Choice of Setup (lsb)
14 Choiceof Setup(msb)
15 No function Reversing
Bit 00/01: Bits 00 and 01 are used for choosing among
the four pre-programmed references (parameters
215-218) in accordance with the following table:
Preset ref. Parameter Bit 01 Bit 00
1 215 0 0
2 216 0 1
3 217 1 0
4 218 1 1
NOTE
Parameter 508 is where to choose the way
bits 1/12 are to be combined (gated) with the
corresponding function on the digital inputs.
B
it 02, DC Brake:
Bit 02 = "0" leads to DC braking and stop. Braking
current and duration are set in parameters 125 and
126. Bit 02 = "1" leads to ramping.
B
it 08, Activation of Jog speed in parameter 213:
Bit 08 = "0": Jog speed not activated. Bit 08 = "1"
means that the motor is running at Jog speed.
B
it 09, Choice of ramp 1/2:
Bit 09 = "0" means that ramp 1 is active (parameters
207/208). Bit 09 = "1" means that ramp 2
(parameters 209/210) is active.
B
it 11, Relay 01:
Bit 11 = "0": Relay 01 not activated. Bit 11 =
1: Relay 01 activated, provided Control word bit
has been chosen in parameter 323.
B
it 12, Relay 04:
Bit 12 = "0": Relay 04 has not been activated. Bit 12
= "1": Relay 04 has been activated, provided Control
word bit has been chosen in parameter 326.
See the description of other bits under control
word for Profidrive standard.
NOTE
Unless otherwise mentioned, the control
word bit is combined (gated) with the
corresponding function on the digital
inputs as a logical "or" function.
MG.50.H4.22 - VLT is a registered Danfoss trademark
17
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Status Word under VLT standard
(parameter 512 = FC Profile). The status word is
used for informing the master (e.g. a PC) about the
condition of the slave (VLT frequency converter).
Bit Bit = 0 Bit =1
00 Control not ready Ready
01 VLT not ready Ready
02 Coasting Enable
03 NO fault Trip
04 Reserved
05 Reserved
06 Reserved
07 No warning Warning
08 Speed - reference Speed = ref.
09 Local control Bus control
10 Out of range Frequency OK
11 Not running Running
12 VLT OK Stalling, auto-start
13 Voltage OK Above limit
14 Torque OK Above limit
15 Timer OK Above limit
Bit 00, Control not ready/ready:
Bit 00 = "0" means that the adjustable frequency drive
has tripped. Bit 00 = "1" means that the adjustable
frequency drive controls are ready, but the power
component is not necessarily receiving any power
supply (in case of external 24 V supply to controls).
B
it 02, Coasting/enable:
Bit 02 = "0" means that the control word bit 03 is "0"
(Coasting) or that VLT 5000 Series has tripped.
Bit 02 = "1" means that control word bit 03 is "1"
and that VLT 5000 Series has not tripped.
See the description of other bits under status
word for the Profidrive standard.
B
us reference value:
The frequency reference value is transmitted to the
adjustable frequency drive in the form of a 16-bit word.
The value is transmitted as a whole number (0-32767).
16384 (4000 Hex) corresponds to 100%. (Negative
figures are formatted by means of 2s complement.)
Thebusreferencehasthefollowingformat:
Parameter 203 = "0"
"ref
MIN
-ref
MAX
"
0-16384 (4000 Hex) ~ 0-100% ~ ref
MIN
-ref
MAX
Parameter 203 = "1"
-ref
MIN
-+ref
MAX
- 16384 (...Hex) - + 16384 (4000 Hex) ~
- 1000 - + 100% ~ - ref
MAX
-+ref
MAX
Actual output frequency
The value of the actual output frequency of the
adjustable frequency drive is transmitted in the
form of a 16-bit word. The value is transmitted
as a whole number (0-32767). 16384 (4000 Hex)
corresponds to 100%. (Negative figures are formed
by means of 2s complement).
MG.50.H4.22 - VLT is a registered Danfoss trademark
18
VLT® 5000/ 5000 FLUX/ 6000 HVAC/
8000 AQUA DeviceNet
Fieldbus
Profile
Control Word and Status Word under Instance 20/70
Set parameter 904 PPO type 1(900) to choose
Instance 20/70.
The control word in Instance 20 is defined as
following:
Instance Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
20 0 Fault
Reset
Run
Fwd
1
2 Speed reference (low byte)
3 Speed reference (high byte)
Bit 0, Run Fwd:
Bit 0 = "0" means that the VLT frequency
converter has a stop command.
Bit 0 = "1" leads to a start command and the VLT
frequency converter will start to run the motor.
B
it 2, Fault Reset
Bit 0 = "0" means that there is no reset of a trip.
Bit 0 = "1" means that a trip is reset.
The Speed reference in Instance 20 is defined as a
word. See description by Bus reference Value.
The status word in Instance 70 is defined as following:
Instance Byte 0 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
70 0 Run-
ning
Fault
1
2 Speed actual value (low byte)
3 Speed actual value (high byte)
Bit 0,Fault:
Bit 0 = "0" means that there is no fault on the
VLT frequency converter.
Bit0="1"meansthatthereisafaultonthe
VLT frequency converter.
B
it 2, Running
Bit 0 ="0"means that there isno active start command.
Bit 0 = "1" means that there isan active start command.
The Speed Actual value in Instance 70 is defined as a
word. See description by Actual Output frequency
MG.50.H4.22 - VLT is a registered Danfoss trademark
19
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38

Danfoss VLT 5000 Flux (Legacy Product) Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI