Safety Information
Warnings
To prevent damage to the equipment, ensure that the DPU
(power supply) and signal processor are fully interconnected,
before switching on the mains power supply.
Connections to this equipment must be carried out in
accordance with current IEE regulations, and all wiring must
be separated in accordance with IEC1010.
Before installation, check that the model number and supply
voltage suit your application.
This device has mains voltages connected to its terminals. It
is recommended, therefore, that the device is mounted within
a suitable enclosure in order to avoid unintentional contact
with the mains supply.
This product is designed for Installation class II service.
This product is designed for use in Pollution - Degree 2
environments.
Equipment Operation
Use of this instrument in a manner not specied by Land Instruments International may be hazardous.
Electrical Power Supply
Before working on the electrical connections all of the electrical power lines to the equipment must be isolated. All the
electrical cables and signal cables must be connected exactly as indicated in these operating instructions. If in doubt contact
Land Instruments International.
Face and Eye Protection
Suitable face and eye protection must be worn when working on hot vessels and ducts! Special safety measures must be
taken when working on a high-pressure duct.
Protective Clothing
Protective clothing must always be worn when working in the vicinity of hot vessels or ducts.
Storage
The instrument should be stored in its packaging, in a dry sheltered area.
Unpacking
Check all packages for external signs of damage. Check the contents against the packing note.
Return of Damaged Goods
IMPORTANT
If any item has been damaged in transit, this should be reported to the carrier and to the supplier immediately. Damage
caused in transit is the responsibility of the carrier not the supplier.
DO NOT RETURN a damaged instrument to the sender as the carrier will not then consider a claim. Save the packing with the
damaged article for inspection by the carrier.
Return of Goods for Repair
If you need to return goods for repair please contact our Customer Service Department. They will be able to advise you on
the correct returns procedure.
Any item returned to Land Instruments International should be adequately packaged to prevent damage during transit.
You must include a written report of the problem together with your own name and contact information, address, telephone
number, email address etc.
Return of Goods for Repair Form is available for download from our websites.
Lifting Instructions
Where items are too heavy to be lifted manually, use suitably rated lifting equipment. Refer to the Technical Specication for
weights. All lifting should be done as stated in local regulations.
Design and Manufacturing Standards
The Quality Management System of Land
Instruments International is approved to BS
EN ISO 9001 for the design, manufacture
and on-site servicing of combustion,
environmental monitoring and non-contact
temperature measuring instrumentation.
Approvals apply in the USA
This instrument complies with current European directives relating to
Electromagnetic Compatibility 89/336/EEC and Low Voltage Directive
73/23/EEC.
Operation of radio transmitters, telephones or other electrical/electronic devices
in close proximity to the equipment while the enclosure doors of the instrument
or its peripherals are open, may cause interference and possible failure where the
radiated emissions exceed the EMC directive.
The protection provided by both CE and IP classications to this product may
be invalidated if alterations or additions are made to the structural, electrical,
mechanical or pneumatic parts of this system. Such changes may also invalidate
the standard terms of warranty.
Dimensions
Unless otherwise stated, all measurements are given in millimetres and inches.
Copyright
This manual is provided as an aid to owners of Land Instruments International’s
products and contains information proprietary to Land Instruments International.
This manual may not, in whole or part, be copied, or reproduced without the
expressed written consent of Land Instruments International Ltd.
Copyright © 2007 - 2011 Land Instruments International.
Signs and Symbols Used on
Equipment and Documentation
Observe precautions for handling electrostatic discharge sensitive
devices.
Protective Conductor Terminal.
This item or material must be disposed of in accordance
with the Waste Electrical and Electronic Equipment
directive as applied by local regulations.
This item or material can be recycled.
Caution, hot surface.
Caution, attention to possibility of risk of damage to the product,
process or surroundings. Refer to instruction manual.
Caution, risk of electric shock.
Ofce Locations
UK - Droneld
Tel: +44 (0) 1246 417691
Web: www.landinst.com
USA - Pittsburgh
AMETEK Land, Inc.
Tel: +1 412 826 4444
Web: www.ametek-land.com
For further details on all LAND/
Ametek ofces, distributors and
representatives, please visit our
websites.
Important Health and Safety Information
IMPORTANT INFORMATION - PLEASE READ
1 Installation and Removal
1.1 Dimensional information
1 2 3 4 5 6 7 8
L N 11 12 13 14 15 16
55/2.2
75/3.0
110/4.3
All dimensions in millimetres/inches
Fig. 1 DPU dimensions UN970062
1.2 Fitting the unit onto a DIN rail
The Land DPU (DIN Power supply Unit) is designed to be
mounted on a standard DIN rail. To install the unit.
1) Ensure that a suitable DIN rail (DIN EN 50 022) is
available and installed correctly.
2) Refer to Fig. 2. Rest the uppermost groove on the rear
of the DPU on the top lip of the DIN rail.
3) Push the bottom of the unit so that the sliding spring
catch clips onto the DIN rail.
1.3 Removing the unit from a DIN rail
1) Refer to Fig. 3. Insert a screwdriver into the sliding
spring catch via the slot on the underside of the unit.
2) Lever the sliding spring catch downwards so that it
disengages from the DIN rail.
3) Lift the DPU off the DIN rail.
DIN rail
Sliding spring catch
Clip onto DIN rail
Fig. 2 Installing the DPU onto a DIN rail UN970058
Screwdriver
Use screwdriver
to unclip the
spring latch
Fig. 3 Removing the DPU from a DIN rail UN970059
2 Electrical connections
The DPU requires an a.c. mains input. The connections
required are shown in Fig. 4.
Notes
Ensure that the a.c. mains supply matches the
requirements of the DPU (Refer to the instrument
type label on top of the unit).
To prevent damage to the equipment, ensure
that the DPU (power supply) and signal processor
are fully interconnected, before switching on the
mains power supply.
Fig. 4 DPU electrical connections UN970060
Notes
The DPU is designed to be used with the Land Uno
thermometer or the Landmark Basic, Technic and
Probus signal processors. Refer to the relevant User
Guide for more connection information.
1 2 3 4 5 6 7 8
L N 11 12 13 14 15 16
Live
Neutral
AC mains
2.1 DPU to UNO Interconnections
DPU Pin Nº Cable Colour Function
UNO to DPU
connections
1 Yellow 4 to 20mA linear temperature signal drive
2 Blue 4 to 20mA linear temperature signal return
3 White CMD (Command) input
4 Screen Screen
5 Red
23 to 48V, <200mA, dc power (positive)
6 Black
23 to 48V, <200mA, dc power (negative)
7 Green CMD (Command) input
8 N/C No connection
External connections
to DPU
9 Brown AC Mains Live
10 Blue AC Mains Neutral
11 White CMD (Command) input
12 Green CMD (Command) input
13 Screen Screen
14 Yellow 4 to 20mA linear temperature signal drive
15 Blue 4 to 20mA linear temperature signal return
16 N/C No connection
2.2 DPU to Landmark Basic Interconnections
DPU Pin Nº Cable Colour Function
DPU to LM Basic Connections
1 N/C No connection
2 N/C No connection
3 N/C No connection
4 N/C No connection
5 N/C No connection
6 N/C No connection
7 N/C No connection
8 Red +ve supply to LM Basic / Technic / Probus
9 Brown AC Mains Live
10 Blue AC Mains Neutral
11 N/C No connection
12 N/C No connection
13 N/C No connection
14 N/C No connection
15 N/C No connection
16 Black -ve supply to LM Basic / Technic / Probus