Selec EM306A Operating instructions

Type
Operating instructions
0.01
0.1
1
10
Ø
Ø
Ø
User programmable CT primary and CT secondary.
Memory retention.
Potential free Pulse output for energy.
DISPLAY
BURDEN
MEASUREMENT
segment LED display, Height 0.5”
3Ø 4wire,3Ø-3wire,2Ø-3wireand
1Ø-2wiresystem
11to300VAC(L-N);19to519VAC(L-L)
InstallationCategory
45-65Hz
Nominal5A AC(Min-11mA,Max-6A)
1A/ 5A to 10,000A(Programmable for anyValue)
1A to 10,000A if CT secondary is 1 else CT
primary is 5Ato 10,000A
1A or5A (programmable)
Less than 8VA
Class 1
Voltagerange:External 4VDCmax.
Currentcapacity:100mA max
100ms 50ms.
1000pulses/kWh
6 digit 7
0.5 VA@5Aper phase
kWh (resettable)
WIRING INPUT
RATEDINPUTVOLTAGE
FREQUENCY RANGE
RATEDINPUTCURRENT
CT PRIMARY
Note :
CTSECONDARY
POWER CONSUMPTION
ACCURACY
OUTPUT
PulseOutput
PulseWidth :
INT :
-
±
III
:2
selec
EM306A
OperatingInstructions
FEATURES
SPECIFICATIONS
ENVIRONMENTAL CONDITIONS
MOUNTING
WEIGHT
-Indooruse
-Altitudeofupto2000meters
-Pollutiondegree
Temperature :
Humidity : Upto85%non-condensing
Panelmounting
340gms
II
° °
° °
Operating :-10 Cto55 C
Storage :-20 Cto75 C
96x96
N
S2S1S2S1S2S1 V1
N
L
O
A
D
I1
V2 V3
L1
L2
L3
I2I3
PULSE
OUTPUT
L
N
+
CONNECTIONSDIAGRAM
TERMINALCONNECTIONS
FRONTPANELDESCRIPTION
OP348-V02
EM306A
PRG
selec
INT
kWh
REV x10
1000
Impulse
/kWh
CONFIGURATION
Thereare4dedicatedkeyswithsymbolsmarkedas,
,,.Usethese4keystoenterintoconfiguration
menu/changesetting.
Thesettingsshouldbedonebyaprofessional
aftergoingthroughthisusersmanualandafterhaving
understoodtheapplicationsituation.
Fortheconfigurationsettingmode:
Note: ,
!Use()and()keysfor3sec.toenterorexitfrom
configurationmenu.
Use()and()keysforincreasinganddecreasing
parametersvaluerespectively.
Use ()keytogobacktopreviouspage.
Use ()keytosavethesettingandmoveonnextpage.
!
!
!
Function
Rangeor
Selection
Config
page.
Factory
Setting
Password
ChangePassword
NewPassword
NetworkSelection
CT Secondary
CT Primary
10
10
No
3P4W
1
1.1
2
3
45
5
0000to9998
No/Yes
3P3W/3P4W
1A or5A
1A,5A to
10,000A (10.0kA)
0000to9998
Forresettingenergyparametersuserwillbepromptedfor
password.Ifcorrectpasswordisentered,theuserwillbe
abletoresetallenergyparameters.Thispasswordwillbe
valuewhichwillbegreaterthantheconfigurationpassword
by1.
FactoryDefault
ResetEnergy
Password
ResetActiveEnergy
5.02
5
5.1
5.01
11
No
No
No
No/Yes
No/Yes
0001To9999
No/Yes
<15
<150
<1500
£2000
Pulseoutput
(kWh/pulse)
CTRatio kWh
0.01
0.1
1
10
RESOLUTION:
INT : The INT LED provides optical output for calibration
verification as well as visual indication of energy
integration. The pulse rate is 1000 Pulses/kWh.
X10 : X10 LED ON when the resolution is 10. It is the
indication of count reading which must be multiplied by
10togetactualkWhconsumed.
REV : REV LED gives the indication of reversal of two
or more CT connections presence of
In such cases meter may not
indicate the correct energy consumption. The CT shoul
be connectedtothe meterwithcorrectpolarities
or negative power
in any or all phases.
d
.
USERGUIDE
LEDINDICATIONS
110VAC, 20%,50/60Hz±
230VAC, 20%,50/60Hz±
Product
ORDERCODEINFORMATION
Supply
EM306A
EM306A-110V
InstallationCategory III
1. This equipment, being built-in-type, normally becomes a
part of main control panel and in such case the terminals
do not remain accessible to the end user after installation
and internal wiring.
2. Conductors must not come in contact with the internal
circuitry of the equipment or else it may lead to a safety
hazard that may in turn endanger life or cause electrical
shock to the operator.
3. Circuit breaker or mains switch must be installed
between power source and supply terminals to facilitate
power 'ON' or ‘OFF’ function. However this switch or
breaker must be installed in a convenient position
normally accessible to the operator.
4.
5. The equipment shall not be installed in environmental
conditions other than those mentioned in this manual.
. The equipment does not have a built-in-type fuse.
Installation of external fuse of rating 275V AC / Amp for
electrical circuitry is highly recommended.
Before disconnecting the secondary of the external
current transformer from the equipment, make sure that
the current transformer is short circuited to avoid risk of
electrical shock and injury.
6
0.5
/ battery
INSTALLATIONGUIDELINES
CAUTION:
SAFETYPRECAUTIONS
All safety related codifications, symbols and
instructions that appear in this operating manual or on
the equipment must be strictly followed to ensure the
safety of the operating personnel as well as the
instrument.
If the equipment is not used in a manner specified by
the manufacturer it might impair the protection provided
by the equipment.
Do not use the equipment if there is any mechanical
damage.
Ensure that the equipment is supplied with correct
voltage.
1. Read complete instructions prior to installation and
operation of the unit.
2. Riskofelectricshock.
3. The equipment in its installed state must not come in
close proximity to any heating sources, oils, steam, caustic
vapors or other unwanted process by products.
CAUTION:
WIRINGGUIDELINES
WARNING :
1. To prevent the risk of electric shock, power supply to the
equipment must be kept OFF while doing the wiring
arrangement.
2. Wiring shall be done strictly according to the terminal
layout. Confirm that all connections are correct.
3. Use lugged terminals.
4. To reduce electromagnetic interference use of wires with
adequate ratings and twists of the same in equal size shall
be made with shortest connections.
5. Layout of connecting cables shall be away from any
internal EMI source.
6. Cable used for connection to power source, must have a
Thesewires shall have current carryingcapacityof 6A.
7. Copper cable should be used
8. Before attempting work on device, ensure absence of
voltages using appropriate voltage detection device.
2 2
cross section of 0.5mm to 2.5mm ( 20 to 14AWG ; 75 C(min)).
0
(Stranded or Single core cable).
OUTLINE
Dimensions(inmm)
PANELCUTOUT
(inmm)Dimensions
90.5
99
99
550 91.5
91.5
For installing the meter
1. Prepare the panel cutout with proper dimensions s shown
below.
a
2 meter. Push the meter into the panel cutout. Secure the in
its place by fitting the clamp on the rear side. Fit clamps on
both sides in diagonally opposite location for optimum
fitting.
3. For proper sealing, tighten the screws evenly with required
torque.
Terminal screw tightening torque :
0.68 N-m to 0.79 N-m ( 6.018 In-Lb to 6.992 In-Lb )
Screw clamp tightening torque : 0.1N-m (0.885 Lb-inch)
MECHANICALINSTALLATION
MAINTENANCE
1. The equipment should be cleaned regularly to avoid
blockage of ventilating parts.
2. Cleantheequipmentwithacleandryordampcloth.
Donotuse anycleaningagentotherthanwater.
Doc.name:OP INST EM306A OP348-V02A(Page1of2)
NETWORKSELECTIONANDWIRINGINPUT
Networkselectionin
configurationmode Wiring
3P4W
3P3W
3P4W,2P3W,1P2W
3P3W
TYPICALWIRINGDIAGRAM
3PHASE4 WIRE (CommonlyUsed) 2PHASE-3WIRE
1PHASE-2WIRE
Allfusetypes:0.5A classCCUL type; 0.5A fastacting600V
#
LOAD
LINE
L1
L2
L3
N
LOAD
LINE
L1
L2
N
LOAD
LINE
L1
N
S2S1 S2S1 S2S1 V1N V2 V3
I1I2I3
S2S1 S2S1 S2S1 V1N
PULSE
O/P
+
-
V2 V3
+
EM306A
I1I2I3
L
N
LN
#
#
PULSE
O/P
+
-
LOAD
LINE
L1
L2
L3
+
EM306A
L
N
LN
#
#
Doc.name:OP INST EM306A OP348-V02A/d(Page2of2)
3PHASE-3WIRE
S2S1 S2S1 S2S1 V1N
PULSE
O/P
+
V2 V3
+
EM306A
I1I2I3
L
N
#
#
L
N
PULSE
O/P
+
+
EM306A
#
#
S2S1 S2S1 S2S1 V1N V2 V3
I1I2I3
Pulseoutputfrommetercanbeinterfacedintoa
processthroughaPLCforonlinecontrolofenergy
contentintheprocess.
IfthePLChasaselfexciteddigitalinput,externalDC
supplyisnotneeded.
ThekWhpulseisalsousedtoderiveaveragekWh
informationatthePLC.
PROCESSINTEGRATION
Pulse output from meter can be used as alarm generator
or total energy controller by interfacing it with Pre
settable counter and control circuits (Contactors, Relay,
Trip Circuit).
The counter is loaded with the maximum energy
consumption. When count reaches setpoint it provides
output to control circuit to take appropriate action.
ENERGYCONTROLLER
APPLICATIONOFPULSEOUTPUT
S2S1 S2S1 S2S1 V1N V2 V3
I1I2I3
EM306A
EM306A
PULSE
O/P
+
L
N
24VDC
maximum
P
L
C
+
#
S2S1 S2S1 S2S1 V1N V2 V3
I1I2I3
PULSE
O/P
+
L
N
12/24VDC
+
#
To
Control
Circuit
COUNTER
+
I/P
O/P
Press()keyfor3sec.todisplayserialnumber.
SERIAL NUMBER DESCRIPTION
Allfusetypes:0.5A classCCUL type
0.5A fastacting600V
#
(Specificationssubjecttochangeasdevelopmentisacontinuousprocess.)
SelecControlsPvt.Ltd.,India
FactoryAddress:
91-22-28476443/1882
I
EL-27/1,ElectronicZone,TTCIndustrialArea,
MIDC,Mahape,NaviMumbai-400710,INDIA.
Tel.No.:+
FaxNo. :+91-22-28471733I Tollfree :1800227353
Website:www.selec.com Email:[email protected]
Disclaimer :"ThisproductisstrictlyforindustrialuseandforsaleinnonEuropeancountriesonly"
  • Page 1 1
  • Page 2 2

Selec EM306A Operating instructions

Type
Operating instructions

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI