Panduit CJS5E88TGY Datasheet

Category
Cable interface/gender adapters
Type
Datasheet
TX6 PLUS
and
TX5e
Shielded Jack Modules
Part Numbers: CJS688TG, CJS688TGY, CJS5E88TG, CJS5E88TGY
Page 1 of 2
INSTALLATION INSTRUCTIONS PN399A
©Panduit Corp. 2006
For Technical Support: www.panduit.com/resources/install_maintain.asp
2.0 in
(50.8 mm)
.5 in
(12.7mm)
Drain wire
Conductors
Overall Foil
Screen
FTP / ScTP
Cable
End 1
Cable
End 2
3
1
2
2
"
"
"
"
4
Cable End 1
Cable End 2
6
Pr1
Pr2
Pr3
Pr4
Pr4
Pr1
Pr2
Pr3
TERMINATION STEPS
5
1
S-FTP
2.0 in
(50.8 mm)
.5 in
(12.7 mm)
CWST
Braid
Conductors
Overall Foil
Screen
Jack
Wire Cap
Strain Relief
Collar
White -
TX6 PLUS
Red -
TX5e
STP / PIMF
Braid
Conductors
Individual Foil
Pair Screen
.5 in
(12.7 mm)
2.0 in
(50.8 mm)
CWST
Trim pair separator and/or rip cord if
present.
Page 2 of 2
INSTALLATION INSTRUCTIONS PN399A
For Instructions in Local Languages
and Technical Support:
http://www.panduit.com/resources/install_maintain.asp
E-mail:
Fax:
(708) 444-6993
www.panduit.com
Cable End 1
Cable End 2
Cable End 1
Cable End 2
7
T568B
T568A
A
B
A
B
A
B
1
2
1
3
1
2
3
1
2
3
See note 4.
CWST
8
9
EGJT
10
EGJT
11
CJSGK-X
KIT
1
2
REMO
VAL STEPS
3
Notes:
1. For specified performance, follow TIA/EIA 568-B installation guidelines.
2. Jack Modules can terminate PVC or LSZH rated 22-26 AWG solid or stranded IWC cable with 0.048 inch (1.2 mm)
maximum insulated conductor outside diameter.
3. Jack Modules may be re-terminated a minimum of 20 times.
4. On cable end 2 for A & B wiring and cable end 1 of A wiring, wrap the designated pairs around the proper center dividing post (A or B) and terminate
in the proper location.
5. CJSGK-X Grounding Kit is REQUIRED for all
M
INI
-C
OM
Modular Patch Panels, but is optional for
M
INI
-C
OM
All Metal Shielded Modular Patch Panels.
6. For technical and performance information, consult
PANDUIT
Technical Support.
As with all Wiring Accessories, the following statements apply:
1. Never install communications wiring during a lightning storm.
2. Never install communications wiring in wet locations unless the jack is specifically designed for use in wet locations.
3. Never touch uninsulated communications wiring or terminals unless the communication line has been disconnected at the network interface.
4. Use caution when installing or modifying communication wiring.
See note 5.
12
2
  • Page 1 1
  • Page 2 2

Panduit CJS5E88TGY Datasheet

Category
Cable interface/gender adapters
Type
Datasheet

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI