SimTech Maxitrol GV60 Troubleshooting Manual

Category
Fireplaces
Type
Troubleshooting Manual
SimTech Troubleshooting Guide
Surefire & Electronic Ignition Systems
ProFlame 1 / ProFlame 2 / Maxitrol GV60
To be used by FPI trained service technicians
919-758 03.08.17
IMPORTANT
For indoor residential/commercial units the SureFire Electronic Ignition
System is designed to operate on 110/120V power.
Batteries are for back-up purposes only.
WARNING
RISK OF ELECTRICAL SHOCK. USE CAUTION WHEN CONDUCTING TESTS
WARNING
USE CAUTION WHEN TESTING AND OPERATING APPLIANCES. FIRE OR
EXPLOSION HAZARD MAY BE PRESENT
To be used by FPI trained service technicians
2
CONTENTS
Electrical Symbols used in this guide......................... ....................................................... 4
S.I.T. Proflame 1 Troubleshooting Guide...................... ...................................................... 5
S.I.T. ProFlame 1 - Remote Control Functionality ............................................................. 17
S.I.T. Proflame II Troubleshooting Guide...................... ...................................................... 30
S.I.T. ProFlame 2 - Remote Control Functionality ............................................................. 43
Maxitrol GV60 Troubleshooting Guide...................... ......................................................... 53
3
Surere Electronic Ignition System
SIT ProFlame 2
Continuity Volts AC Volts DC Amps
(Ohms) (VAC) (VDC)
ELECTRICAL SYMBOLS USED IN THIS GUIDE
INSPECT
VERIFY TEST
Troubleshooting Motto
4
S.I.T. PROFLAME 1 TROUBLESHOOTING GUIDE
55
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
66
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Turn the main burner switch to
ON. Wait 4-10 seconds
1. Ensure the DFC module is not locked out. Turnswitch off then back on
again. If thereis aspark it was locked out. Remove all power including
batteries. Leavefor 60 seconds, replace power and repeat step 1.
2. Check the 4 xAA batteries are installed correctly. Diagram 3
If correctcheck battery voltage at the whiteplastic harness at CN1 on DFC.
While4.4 vdc is the minvoltage the unit can operateit isrecommended to
change the batteries at 5vdc or less. Check for power at the #1 and #3 at CN1
on the DFC. If an AC adapter is used check for power at the #2 and #3 at CN1
on the DFC. The reading shouldbe approx 7 vdc. If No check power supply, if
Yes replace the DFC. Diagram 4
3. Is there is a "dull" spark sound present? If Yes, the electrodes porcelain
insulator or wiremay be cracked and grounding out. Replacethe electrode if
necessary.Diagram 1 & Diagram 2
4. Confirm igniter wire is connected to CN3 at the DFC. Diagram 2
5. Disconnect the electrode from CN3 and conduct acontinuity test. Placeone
lead to the tip of the electrode and the other to the spade connector. Ifno
continuity replacethe electrode. Ifcontinuity is found attach a jumper to CN3.
Placethe other end of the jumper 1/8" away from ground and switchthe unit
on. If thereis aspark replace the electrode. If no spark replace the DFC.
Diagram 6
6. Confirm yellow ground wire is properly connected. DFC (wire harness)
ground wire connects to the valve. The ground connected to CN2 on the DFC
is connected to the chassis (ground lug) then grounded to the pilot area.
Diagram 5
7. Is aspark visibleat CN3 electrode connection at the DFC module and CN2
ground? Confirm connector isfirmly seated and the connectors arenot bent.
Diagram 1 & Diagram 2
8. Check the On/Off switch for approx 3vdc at the green and whitewires. One
lead to each switch connection whichare connected to the green and white
wires. The switchmust be in the off position. Diagram 7
If no voltage check green and whitewires at DFC harness CN1. Shouldread
approx 3vdc present ifNo check all switchwires and connections. If No voltage
replace the DFC. Diagram 8
**Continue if CPI/IPI switch is inoperable.**
9. Check the continuity of the CPI/IPI switch (Continous Pilot/Intermittent Pilot
Switch). Pilot switch must be in CPI position to show continuity. If No replace
it.
Is there a
spark at the
pilot hood?
1. Confirm Battery voltage (see step 2 above, no spark at pilot hood)
2. Confirm proper grounding (see step 6 above, no spark at pilot hood)
3. Check continuity at the EV1 pilot coil to ground. Should read approx 340
ohms. If no continuity replace the valve. Diagram 11
4. Confirm the orange wire is properly connected to the EV1 pilot coil
5. Check the voltage at EV1 pilot coil to ground. When switched on there
should be 4 to 6 vdc for 2 seconds then it drops to .5 to 1 vdc. If there is no
voltage replace the DFC module. Diagram 12
6. Check the incoming gas pressure working pressure (inches of water column
"WC). If gas pressure is good check pilot orifice for blockage and gas flow. If
no blockage and still no flow replace the gas valve.
Did the
pilot light?
NO
YES
NO
Continue to
the next
page
YES
77
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
6
5
7
9
8
1
2
3
4
1.Ensurethe pilot is engulfingthe flamesensor and it does not shrink away
when there is a call for heat/mainburner.Check working inlet pressureand
adjust the pilot pressureif necessary. See rating platefor minimum required
working pressure(inches of water column "WC)
2.Confirm the flamesensor wireis connected to the DFC module.
3.Confirm proper grounding (See step 6above, no spark at pilot hood).
4.Ensureflamesensor and pilot hood areclean. Useonly steel wool or a
Scotch-Britepad to clean the flamesensor.
5.Confirm the flamesensor has continuity (Ohms), place one lead on the tip
of the sensing end and the other on the female spade at the end of the wire.
If no continuity or high resistance replace the flamesensor. Diagram 13
If found continuity is good check the pilot flamestays steady engulfing the
flame sensor.If pilot is steady replacethe DFC Module.
See Diagram 13A for potential causes for flamesensor not to prove.
Pilot is lit but
Igniter
continues to
spark
YES
1. Confirm battery voltage (See step 2above, no spark at pilot hood)
2. Check continuity at the EV2maincoil to ground. If no continuity replace
the valve. Should read approx 340 ohms. Diagram 14
3. Confirm the green wire is properly connected to the EV2 main burner coil.
4. Confirm proper grounding (see step 6above, no spark at pilot hood).
5. Check the voltage at EV2mainburner coil to ground. When switched on
you should read 4 to 6 vdc for 2 seconds. It will drop to .5 to 1 vdc after the
initial 2 seconds. If no voltage replacethe DFC module. Diagram 15
6. Check the inlet/outlet gas pressureworking pressure(inches of water
column "WC).If the above are correct and no outlet pressure, replacethe
gas valve.
Does the
burner come
on? NO
YES
Unit is
working
properly
NO
Valve Description
1) 6 Stage flame adjustment
2) Pilot adjustment
3) Outlet Pressure Tap
4) Inlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
8) EV1 Pilot Coil
9) EV2 Main Burner Coil
88
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 1
Remove the electrode from the assembly to examine for cracks in the porcelain.
Remove pilot hood ground clip and hood then clean ground contact points from hood to assembly. Examine electrode
wire and connector for breaks or abrasion.
Pilot Ground Clip Clean ground contact points from hood
to assembly
Diagram 2
Conrm the igniter wire is properly connected and check for any breaks in the wire or connector
Check Igniter Wire
Connection
Diagram 3
Check that the batteries are correctly installed in the holder. Push batteries forward towards the (+) positive end. The
holder is very tight and sometimes the batteries will not make a good connection
Pilot hood
Flame Sensor
4 x AA Batteries
Spark Electrode
99
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 4 VOLTS DC TEST (VDC)
Check the battery voltage at the DFC wire harness connection at the #1 and #3 positions.
If the reading is 4.4 vdc or less replace the batteries.
VOLTS DC TEST (VDC)
If the A/C adapter is connected check the #2 red and #3 black positions. The reading should be approximately
7 vdc. If the correct voltage is present replace the DFC.
NOTE: Ensure the A/C adapter has good contact with the DC supply connector
A/C Adapter Connection
1010
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 5
Check the ground connection to the DFC module, the valve and the closest point to the pilot assembly. Do not alter
any ground wires as installed by the manufacturer.
Diagram 6
Remove the spark electrode wire from CN3. Connect a jumper wire to the exposed spade terminal. Hold the opposite
end of the jumper 1/8” away from ground and turn the unit on. If there is a spark replace the electrode, if not replace
the DFC.
Spark Electrode
Connection CN3
Chassis Ground
(Attached to the
ground lug)
Ground to the pilot area or
closest point to pilot
Ground from DFC wire harness to
valve
1111
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 7 VOLTS DC TEST (VDC)
Check voltage at the green and white wires labeled ON/OFF. If a wall switch is used, check voltage at the switch.
(Switch must be in off position). The reading should be approximately 3 vdc. If no voltage proceed to the next step.
Diagram 8 VOLTS DC TEST (VDC)
Check the voltage at the DFC. (Switch must be in the off position). The reading should be approximately 3 vdc.
If there is no voltage replace the DFC.
Check voltage at
wall switch. The
switch is in the off
position
Check voltage at connections
1212
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 9 CONTINUITY TEST (Ohms)
Put the switch in the CPI (constant pilot/closed) position. Disconnect the switch and check for continuity.
Diagram 10 VOLTS DC TEST (VDC)
Check the blue and white CPI/IPI wires for approximately 3 vdc. The switch must be in the IPI (intermittent
pilot/open) position to check.
1313
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 11 CONTINUITY TEST (Ohms)
Check continuity/resistance of the EV1 pilot coil. Disconnect the orange wire from EV1. It should read approxi-
mately 340 ohms (+/- 20 ohms). If there is no continuity or high/low resistance replace the valve.
Diagram 12 VOLTS DC TEST (VDC)
With system complete conduct the following test:
Check voltage at EV1 pilot coil with the orange wire connected to the valve. With the leads in place switch the
unit on. For approximately 2 seconds the voltage should read 4-6 vdc then drops to .5-1 vdc. If there is voltage
replace the valve. If there is not voltage replace the DFC.
EV1 Orange tab-
wire disconnected
Valve Body
(Ground)
EV1 Orange tab-wire
connected
Valve Body (Ground)
1414
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 13 CONTINUITY TEST (Ohms)
Confirm the flame sensor has continuity. If there is no continuity or high resistance replace it. If continuity is
good replace the DFC..
Flame Sensor
Diagram 13A
POTENTIAL CAUSES FOR FLAME SENSOR NOT TO PROVE
Venting Related Issues (See each manual for specific information relating to tested and approved venting
systems)
● Partial Intake Liner - exhaust and intake liner must be of approved size and run continuous to termination
● Unapproved Termination
● Unapproved Vent Configuration
Enclosed Termination
● Incorrect Vent Restrictor Setting
Crossed Liners
● RTV Sealant on Venting (Do not use RTV sealant on units)
If Liners have large sags pull liners tight and keep run as straight as possible
Gas Supply Issues (See each units manuals for required pressure)
Ensure Sediment Trap (Drip Leg) is installed in supply line prior to the gas valve. SIT requirement for iron pipe.
Measure Inlet Gas Pressure with unit off. Make note and then measure gas pressure with the unit turned on (call for
heat)
● Measure Outlet Gas Pressure with unit on(call for heat)
● If inlet working pressure is to low check for blockage or incorrect gas line size
● If outlet working pressure is incorrect and inlet pressure is correct check the following:
Valve Modulator - If an electronic modulator was added see diagram 27-28 to troubleshoot the modulator
Converted Units - ensure factory diaphragm and spring have been removed
Cold Vents/ Cold Start - unit may need to be cycled again to overcome the cold vent/cold start. Turn unit off then back
on to cycle the unit again
Misplaced logs/glass or stone - check manual for correct certified media placement
1515
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 14 CONTINUITY TEST (Ohms)
Check continuity/resistance of the EV2 main burner coil. Disconnect the green wire from EV2. It should read
approximately 340 ohms (+/- 20 ohms). If there is no continuity or high/low resistance replace the valve..
EV2 Green tab-
wire disconnected
Valve Body
1616
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 15 DC VOLTS TEST (VDC)
With system complete conduct the following test:
Check voltage at EV2 main burner coil with the green wire connected to the valve. With the leads in place
switch the unit on. For approximately 2 seconds the voltage should read 4-6 vdc then drops to .5-1 vdc. If there
is voltage replace the valve. If there is not voltage replace the DFC.
Diagram 16
9 8 7 6 5 4 3 2 1
CN1 Nine Pin
Molex connector
locations num-
bered right to left
Second lead goes
to valve body
(or Ground)
EV2 (Green
Tab) This wire
must stay con-
nected for this
test.
CN4 Flame Sensor
(Red Sleeve)
CN3 Spark Electrode
(Black Sleeve)
CN 2 Ground
1717
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Press On/Off
button (handheld)
Does pilot light
and burner come
on?
1. Check to ensure the receiver switch is set to remote (Center position). Check
system is not in lock out. Press On/Off button 2 times. Diagram 17
2. Check to ensure the remote handheld is turned on. If not press the ON/OFF key again.
**An audible beep should be heard from the receiver** Diagram 18
3. If no beep is heard ensure handheld and receiver are "coded". Place receiver switch in the
remote position, using a paperclip or similar object insert the end into the hole marked PRG
on the reciever front cover. The receiver will beep 3 times indicating it is ready to be coded.
Using the handheld press the ON/OFF key and the receiver will beep 4 times to indicate they
are coded. Diagram 17 & Diagram 18
4. Check batteries in the receiver and remote handheld. Diagram 21
Check that the 4 x AA batteries are installed correctly into the receiver. Ensure the DC supply
is connected to the DFC supply. The AC adapter connects to the FCM com wire. If correct
check the battery voltage at the plastic harness CN1 on the DFC. Set multi-meter to volts DC,
Place one lead at the #2 Red and one lead to #3 Black. While 4.4 vdc is the min voltage to
operate it is recommended to change the batteries at 5 vdc or less. Diagram 22
Remote handheld has a low battery indicator. Diagram 20
Replace batteries if screen is blank. Replace handheld if screen stays blank. Replace receiver
if still no audible beeps are heard.
5. Check that the remote wire harness, green and white wires are properly connected to the
units main wire harness green and white wires and the remote wire harness molex connector
to the keyed backside of the receiver. Diagram 23 & Diagram 24
6. Is thermostat mode on? If yes, raise the temperature set point higher
than the room temperature or press the thermostat key until the icon shows off, then you are
in manual position. Diagram 25
Use the UP/ Down arrow to control the burner on/off and
height if system is GTM,GTMF or
GTMFS
7. If burner still does not come on set your multi-meter to ohms. Disconnect green and white
wires. Place one lead to the green wire and one to the white wire, on the remote wire harness
side. When the burner is signaled to come on the meter will show continuity. Diagram 26.
If no continuity found, follow previous troubleshoot flow chart. No Remote, check the DFC and
valve.
Continue to
the next
page
NO
YES
S.I.T. PROFLAME 1 - REMOTE CONTROL FUNCTIONALITY
1818
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Does flame
modulate
H
igh to Low
?
1. Flame modulation is not an option on some models. GTM, GTMF,GTMFS systems are
compatible with a modulator.
2. Check to see if modulator is installed and properly connected to the wire marked motor. If
not install one and make the connection. Diagram 27
3. Is the Smart stat on? If yes, turn off Smart Stat by pressing thermostat key until the
thermostat icon display shows OFF. Now the flame can be manually modulated.
4. Check modulator for continuity. Disconnect the black plug marked (Motor) from wiring
harness. On the back side of plug place one lead on the orange wire and one on the yellow
wire. Reading should be approximately 26 ohms. Also check continuity between black and
brown wires. It should also be approximately 26 ohms. If no continuity or high resistance,
replace the modulator. Diagram 27
1. A fan is not an option selected, be sure the handheld is GTMF or GTMFS.
2. Is the Fan Control Module (FCM) plugged in and is there power to this receptacle.
3. Is the fan plugged into the FCM in the outlet marked Fan?
4. Is the remote wiring harness from the receiver connected to the FCM marked COM?
The connector is keyed and will go in one way only.
5. Is the FCM switch turned ON?
6. Ensure the remote control is set for the fan to come on. Diagram 19
7. There is a fan snap disk that must be hot enough to activate the fan. Is it hot enough?
8. Check the fan snap disk. It is normally open, when hot, there should be continuity.
9. ensure power is getting to the fans. If not, check the FCM fan outlet for 120 vac. If there
is no power out, check the fuse mare F3 in the FCM. Replace fuse if required (Part #
910-978).
10. Check the fan rheostat, if applicable.
11. Check fan, place fan wiring plug directly into 120 vac receptacle. Replace the fan if it
does not come on.
Unit is operating
Does the
Fan come
on?
YES
NO
NO
YES
1919
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
SIT Pro-Flame Remote
Download Video of Pro-Flame
Features
2020
SUREFIRE ELECTRONIC IGNITION SYSTEM
S.I.T. PROFLAME 1 TROUBLESHOOTING
SimTech Proflame I
Diagram 18
Check to ensure the remote handheld is turned on. The photo on the left shows Manual Mode on high. The photo on
the right shows Manual Mode on flame level 4.
Diagram 17
Check to ensure the receiver switch is set to the remote position (In center).
Set to Remote Position
(In Center)
Receiver Front Cover
Receiver Switch
Hole marked “PRG”
Coding Button
Thermostat Display Off
Indicates
Manual Mode
Remote
Handheld
On/Off Button
Up/Down Arrow
Key for Burner or
Fan
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72

SimTech Maxitrol GV60 Troubleshooting Manual

Category
Fireplaces
Type
Troubleshooting Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI