Mammoth R6GP Product information

Type
Product information

This manual is also suitable for

3 Phase 60 Hz.
4. For supply wire ampacities and overcurrent protection, see unit
rating label.
5. On ā€œCā€ Series Models only. For 208V operation remove wire from
230V tap and place on 208V tap.
6. This wire replaced by auto transformer when used.
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
WIRING DIAGRAM
R6GP Series 6-10T
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. If any of the original wire as supplied with the furnace must be replaced,
it must be replaced with wiring material having a temperature rating of
at least 105C and 600V.
CCH - Crankcase Heaters, Stage 1&2 Compressor
CC1&2 - Contactor, Stage 1&2 Compressor
E - Economizer
LVT - Low Voltage Terminal
OFC - Contactor, Outdoor Fan
IBC - Contactor, Indoor Blower Motor
IC - Integrated Control
L1
L2
L3
GND
Compressor 1
T2
T1
T3
CC1
Aux.
Switch
(N.C.)
CC1
CCH1
Field Supplied
Disconnect
(3Phase Power Only)
For supply connections use
copper conductors only.
Unit
Terminal
Block
24V Hot
High
Pressure
Switchs
Evap.
Freezestats
Low
Pressure
Switchs
Y1
Factory
Jumper
LVT-C (24V COM.)
LVT-R
CC1
LVT-Y1(Stage 1 Cool)
LVT-Y2(Stage 2 Cool)
LVT-G
LVT-W1(Heat)
LVT-W2(Heat)
E-1
E-9
E-8
E-2
E-4
E-5
OFC
CC1
Aux. Switch
(N.O.)
IBC
Aux. Switch
(N.O.)
CC2
Aux. Switch
(N.O.)
Y2
Factory
Jumper
WH BK
Inducer Motor
208-230/460 Volt
1
3
1
3
Max
Temp.
Limit
24V Common
Flame
Rollout
Switch
Upper
Scndry
Limit
P1-2
P1-8
P1-3
P2-3
K2
S1
S2
UTEC
IGNITION
CONTROL
G
C
R
L
COM
NC
NO
BLOWER
TIME
DELAY
K1
P2-4
W1
W2
HV
TRANSFORMER
FS
P2-1
COM
P1-9
P1-6
GAS VALVE
INDUCER MTR
CENTRIFUGAL
SWITCH
SPARK
IGNITOR
FLAME
SENSOR
GND
High
Limit
Input
Rollout Switch
Input
C
IBC
T2
T3
T1
IBC
Transformer
24V Sec.
Primary
Indoor Fan Motor
See Note 5
OFC
4 Amp
Circuit
Breaker
Auto Transformer
460V Units Only
L3 L2
See Note 6
P1-7
P1-4
24 VAC
P2-2
R
IC-IND
K4-IC
IC-L1
Status Light
(Red)
Ignition Control Failure Code
Steady On
2 flashes
Operation Normal
3 flashes
4 flashes
5 flashes
6 flashes
7 flashes
8 flashes
9 flashes
10 flashes
Pressure/centrifugal switch open with inducer on
Lockout from too many failed ignition tries
Lockout from too many flame losses
High temperature switch open
Rollout switch open
Flame present with gas off`
Exceeded max limit trips in one call for heat (5)
Gas Valve Fault
Pressure/centrifugal switch closed with inducer off
R
C
Outdoor Fan Motor
Outdoor Fan Motor
S
R
C
S
See Alternate
OD fan wiring
Diagram B
T2
T3
T1
CC2
Compressor 2
Aux. Switch
(N.C.)
CC2
CCH2
711153B
06/11
(Replaces 711153A)
- Indicates plug connection.
Letter Indicates which plug.
Number indicates pin location.
2 Stage Equipment Only
- Indicates screw connection.
CC2
  • Page 1 1