Bosch Appliances FPE-1000-CITY User manual

Category
Washer dryers
Type
User manual
City Tie Plug-in Module
FPE-1000-CITY
en Installation Guide
es Guía de instalación
pt Manual de Instalação
th คูมือการดตั้ง
FPE-1000-CITY 3
Bosch Security Systems, Inc. F.01U.078.100 | 04 | 2011.11
en Installation Guide 4
es Guía de instalación 7
pt Manual de Instalação 10
th คูมือการตดตั้ง 13
4 en FPE-1000-CITY
F.01U.078.100 | 04 | 2011.11 Bosch Security Systems, Inc.
Notices
Use these instructions to install the FPE-1000-CITY City Tie Plug-in Module in FPA-1000 Analog Addressable Fire
Panels.
1. Install, test, and maintain the FPE-1000-CITY according to these instructions, NFPA 72, local codes, and the
Authority Having Jurisdiction (AHJ).
2. Follow the procedures in this document to avoid personal injury and damage to the equipment. Failure to follow
these procedures can cause the FPE-1000-CITY to operate improperly. Bosch is not responsible for improperly
installed, tested, or maintained devices.
3. Failure to follow the mounting instructions in this document can damage the fire panel.
4. Refer to the FPA-1000 Installation and Operation Guide for detailed wiring style requirements and complete
programming instructions.
Short Information
The FPE-1000-CITY provides the system with two supervised City Tie Local Energy circuits or Reverse Polarity
circuits. It connects to a Master Box (Local Energy Mode) or Central Station (Reverse Polarity Mode).
Installation
The main board allows for the installation of one FPE-1000-CITY plug-in module. Refer to Figure 2 on Page 5 for the
position of the FPE-1000-CITY City Tie Plug-in Module.The upper two plug-in slots can be used solely for the first and
second FPE-1000-SLC Signaling Line Circuit board.
The plug-in modules connect directly to the main board, and are detected and supervised automatically when power
is applied to the control panel.
FPE-1000-CITY DIP Switch Settings
Note: Before installing the FPE-1000-CITY, set the DIP switches on the module to obtain the desired operation mode
(Local Energy or Reverse Polarity Mode).
Refer to Figure 1 for the location and setting of DIP switches.
Figure 1 DIP Switch Settings on the City Tie Plug-in Module
CAUTION!
Electrostatic discharge!
Ground yourself using a wrist strap or take other suitable actions.
The FPA-1000 mainboard and FPE-1000-CITY plug-in module have static-sensitive components
that could become damaged. Run the ground wire to the enclosure before handling the
mainboard or plug-in modules. Touch ground before unpacking and handling the mainboard or
plug-in modules. This discharges any static electricity in your body. Continue touching the
enclosure while installing the mainboard or plug-in modules.
DANGER!
Before installing the FPE-1000-CITY plug-in module, remove all AC and battery power from the
fire panel.
Legend
S1 Switch 1 Supervisory (SUP)
S2 Switch 2 Fire Alarm (ALM)
1 DIP switch setting for Reverse Polarity Mode
2 DIP switch setting for Local Energy Mode
Reverse
1
ON
S1
Local
2
3
Reverse
1
ON
S2
Local
2
3
BOSCH
S1
S2
1
Reverse
1
ON
S1
Local
2
3
Reverse
1
ON
S2
Local
2
3
2
Reverse
1
ON
S1
Local
2
3
Reverse
1
ON
S2
Local
2
3
FPE-1000-CITY en 5
Bosch Security Systems, Inc. F.01U.078.100 | 04 | 2011.11
Mounting
1. Bring the plug-in module into position with the horizontal terminal lettering facing the front side of the control
panel. Slide the plug-in module carefully into position along the guide rails (refer to Figure 2, Page 5, Item 1)
2. Ensure that the connections seat into the slot properly (refer to Figure 2, Page 5, Item 2).
3. Press down softly until the snap-fit hook locks into place (refer to Figure 2, Page 5, Item 3).
Figure 2 Installing the FPE-1000-CITY City Tie Plug-in Module
To remove a plug-in module, press the snap-fit hook carefully from left to right and pull the board toward the panel
front.
Wiring
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long
as it meets the National Electric Code 760-51 requirements for power-limited fire protective signaling cables.
Observe a maximum circuit resistance of 65 Ω.
Note: Use the appropiate DIP switch setting at the module to obtain the desired operation mode (refer to Figure 1,
Page 4).
Reverse Polarity Mode
The FPE-1000-CITY connects the FPA-1000 Analog Addressable Fire Panel to either a single set or a pair of dual
leased telephone company (telco) lines in NFPA 72 Remote Station applications. The FPE-1000-CITY relays system
alarm status information from the control panel to a monitoring station.
In normal conditions, the FPE-1000-CITY sends a steady current to a monitoring station. In an alarm condition, it
reverses the polarity of the output current. The FPE-1000-CITY signals a trouble condition by interrupting the output
voltage and current.
The default setting is fire alarm for circuit 1 and supervisory for circuit 2.
FPE-1000-CITY
DIP Switches
S1 = SUP S2 = ALM
123123
Reverse Polarity Mode ON ON ON ON ON ON
Local Energy OFF OFF OFF OFF OFF OFF
Note: You may use different operation modes for the circuits. The DIP switch settings 1 to 3 for each switch (S1
and S2) must be set to the same position.
NOTICE!
Intended for connection to a polarity reversal circuit of a remote station receiving unit having
compatible ratings.
Terminal Default setting
Figure 3 Reverse Polarity Mode
ALM - | + Fire Alarm
SUP - | + Supervisory
Legend
M Monitoring Station
@
_
. : ,
?
A a
Gas Alarm
Silenced
Power
Trouble
Fire
Supervisory
DRILL RESET SILENCE ACK
2
1
1
3
ALM
-
+
-
+
SUP
M
6 en FPE-1000-CITY
F.01U.078.100 | 04 | 2011.11 Bosch Security Systems, Inc.
Local Energy Mode
The FPE-1000-CITY connects Local Energy signaling devices to the FPA-1000 fire panel for auxiliary service
operation.
Refer to the FPA-1000 Installation and Operation Guide for a listing of compatible Gamewell devices.
Specifications
Terminal
Figure 4 Local Energy Mode
ALM - | + Connects to Municipal Master Box
SUP - | + Not used
Circuit resistance 65 Ω
Wire gauge
12 to 18 AWG (3.3 mm
2
to 0.8 mm
2
)
Operating temperature 32 °F to 120 °F (0 °C to 49 °C)
Storage temperature -4 °F to 140 °F (-20 °C to 60 °C)
Relative humidity Up to 93%, non-condensing
Reverse Polarity Mode
Nominal Voltage 24 V DC nominal (26.4 V DC maximum), power-limited, supervised
Output current 33 mA maximum
Supervisory/standby current 5 mA
Local Energy Mode
Type of connection In series
Alarm, trip coil 24 V DC
Alarm current 250 mA (momentary, <1 ms)
Supervisory/standby current <50 mA DC
Trip coil resistance 14.5 Ω
Nominal coil voltage 3.65 V DC, power-limited, supervised
ALM -
ALM+
SUP -
SUP+
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450
USA
www.boschsecurity.us
© Bosch Security Systems, Inc., 2011
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Bosch Appliances FPE-1000-CITY User manual

Category
Washer dryers
Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI