Field module with output for EEV for cold locations
4 FKV003-A_V3.60_PI_2022-11_EN
Subject to technical changes
FKV003-A
CAN bus address setting
To correctly register the FKV003-A on the CAN bus, you must assign it a unique CAN bus address
using a coding switch. This is a requirement for functioning communication with the master module.
You can set CAN bus addresses 0...7 with the coding switch. You can thus connect 8 field modules
to the CAN bus.
Fig. 4: Coding switch
1.6 Technical data
NOTICE • Please observe the detailed descriptions in the chapters of the FRIGOLINK system manual.
Power supply
230V~, +10% / -15%, max. 5W
Display 1 x green LED, operating voltage
2 x green LED, CAN bus data traffic (CAN Tx, CAN Rx)
1 x red LED, flashes in case of fault
Communication 3-conductor CAN bus interface, shielded, galvanically isolated,
Screw terminals 2.5mm² / RJ45 socket (2x)
Temperature sensor 4 x TRK277
(standard connection: supply air, return air, defrost limit, suction gas)
Analogue input 4…20mA or 0…10V=, output voltage 22V=,
max. 22mA (humidity sensor)
Digital inputs 24V=, +20% / -10%, approx. 5mA per input,
1 x cold location Off, 1 x 2nd setpoint, 1 x cold room door open
Output relay 1 x cooling, normally closed contact, 230V~, 3(1)A
1 x fan, normally closed contact, 230V~, 3(1)A
1 x defrost, normally open contact, 230V~, 3(1)A
Display / frame heat-
ing connection
1 x socket for pre-assembled line to display DSP002, DSP100, DSP-
LCD, DSP-Booster or for controlling a frame heating via ECA970 (1x)
Analogue output 1 x 0…10V=, non-isolated, max. load 10mA,
for modulating valves
PWM / EEV output 1 x 0…10V=, non-isolated, max. load 10mA,
for control of electronic relays through ATV230
Dimensions (W x H x D) 106 x 90 x 58mm (DIN 43880)
Fastening Top-hat rail TH 35-15 or TH 35-7.5 (DIN EN 60715)
Ambient temperature
Operation: 0...+55°C, storage: -25…+70°C
Weight About 275g
Conformities - 2014/30/EU (EMC Directive)
- 2014/35/EU (Low Voltage Directive)
EAC conformity - TR CU 004/2011
- TR CU 020/2011
RoHS II