DISPLACEMENT FLOW IN-WALL DIFFUSER
2priceindustries.com | DISPLACEMENT FLOW IN-WALL DIFFUSER - Manual
INSTALLATION INSTRUCTIONS
4. After the drywall has been installed
and finished as required around the
plenum, apply a bead of caulking
along plenum wall and drywall edge
to minimize air leakage.
5. Insert the diffuser face into the
plenum. Use the supplied screws
to mount the diffuser face to
the plenum (Figure 3). For units
supplied with a secondary baffle
see Figure 4 to determine proper
baffle orientation.
6. NOTE: Standard screws issued
with DFW displacement unit are
3/4" self-drilling. These will work
with 1/2" thick drywall. If drywall is
thicker than 1/2", a different length
screw must be requested at time of
ordering.
7. Care should be taken not to over
tighten the screws (Item 3).
1
2
3
NOM HEIGHT
2 X 4
Figure 1
OPEN FACE
PLENUM
1/2" DRYWALL
NOM WIDTH
2
X 4
Figure 3
OPEN
DIFFUSER FACE
Figure 2
FLOOR
PLENUM
Box
1/2" DRYWALL REF
1/2" DRYWALL REF
HEIGHT TO BOTTOM
OF DIFFUSER FACE + 3/8”
2X4
STUD REF
2X4
STUD REF
MIN 1/8"
MAX 1/4"
RECOMMENDED:
ADD BEAD OF CAULKING
TO SEAL PLENUM
MAKE SURE THAT THE SECONDARY
BAFFLE IS POINTING DOWN AWAY
FROM THE INLET. SECONDARY
BAFFLE IS AVAILABLE ON UNITS
THAT ARE GREATER THAN 30 IN.
WIDE AND HAVE A HEIGHT OF 24 IN.
WIDTH
HEIGHT
2.000
Figure 4
CONNECT DUCT TO
DIFFUSER INLET
1
2
3
NOM HEIGHT
2 X 4
Figure 1
OPEN FACE
PLENUM
1/2" DRYWALL
NOM WIDTH
2
X 4
OPEN
DIFFUSER FACE
Figure 2
FLOOR
PLENUM
Box
1/2" DRYWALL REF
1/2" DRYWALL REF
HEIGHT TO BOTTOM
OF DIFFUSER FACE + 3/8”
2X4
STUD REF
2X4
STUD REF
MIN 1/8"
MAX 1/4"
RECOMMENDED:
ADD BEAD OF CAULKING
TO SEAL PLENUM
MAKE SURE THAT THE SECONDARY
BAFFLE IS POINTING DOWN AWAY
FROM THE INLET. SECONDARY
BAFFLE IS AVAILABLE ON UNITS
THAT ARE GREATER THAN 30 IN.
WIDE AND HAVE A HEIGHT OF 24 IN.
WIDTH
HEIGHT
2.000
Figure 4
CONNECT DUCT TO
DIFFUSER INLET
1
2
3
NOM HEIGHT
2 X 4
Figure 1
OPEN FACE
PLENUM
1/2" DRYWALL
NOM WIDTH
2
X 4
Figure 3
OPEN
DIFFUSER FACE
Figure 2
FLOOR
PLENUM
Box
1/2" DRYWALL REF
1/2" DRYWALL REF
HEIGHT TO BOTTOM
OF DIFFUSER FACE + 3/8”
2X4
STUD REF
2X4
STUD REF
MIN 1/8"
MAX 1/4"
RECOMMENDED:
ADD BEAD OF CAULKING
TO SEAL PLENUM
MAKE SURE THAT THE SECONDARY
BAFFLE IS POINTING DOWN AWAY
FROM THE INLET. SECONDARY
BAFFLE IS AVAILABLE ON UNITS
THAT ARE GREATER THAN 30 IN.
WIDE AND HAVE A HEIGHT OF 24 IN.
HEIGHT
Figure 4
CONNECT DUCT TO
DIFFUSER INLET
FIGURE 2
FIGURE 3
FIGURE 4