2
Details of the product
Logano plus GB312 - Technical specifications are subject to change without prior notice
6
2 Details of the product
These installation and servicing instructions contain
important information regarding the safe and proper
installation, commissioning and servicing of the Logano
plus GB312 gas condensing boiler.
These installation and servicing instructions are intended
for qualified heating contractors, who – as a result of their
technical training and experience – are skilled in dealing
with heating systems and gas installations.
The boiler can be fitted with a programming unit such as
the RC35 (available separately).
Only use the boiler in the combinations and with the
accessories and components that are specified in the
installation and servicing instructions.
Use other combinations, accessories and consumables
only if they are specifically intended for the proposed
application and they do not affect performance character-
istics and safety requirements.
2.1 Intended use
The Logano plus GB312 is designed for heating central
heating system water and, with the use of an indirect tank,
domestic hot water, for instance in apartment buildings.
2.2 Standards, regulations and direc-
tives
2.2.1 National regulations
The heating system must comply with the requirements of
the relevant regulatory authorities or otherwise of the
National Fuel Gas Code, ANSI Z 223.1. In Canada, the
requirements of CAN/CSA-B.149.1 and 2, Installation
Code for Gas Burning Appliances and Equipment, must
be observed.
If specified by the relevant regulatory authorities, the heat-
ing system must comply with the regulations of the Stan-
dard for Controls and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1.
Carbon monoxide detectors must be installed as speci-
fied by the local regulations. The boiler must be serviced
annually.
Boiler operating conditions
The heat exchanger has been designed and certified in
accordance with the ASME Boiler and Vessel Code, Sec-
tion IV.
Maximum boiler temperature: 200 °F
Maximum operating pressure: 50 psi
The hot water piping system must comply with the appli-
cable legislation and regulations. If an existing boiler is
replaced, the complete hot water piping system must be
inspected to ensure that it is in perfect condition to ensure
safe operation.
2.3 Compliance with standards and reg-
ulations
The design and mode of operation of this boiler comply
with the American National Standard ANSI Z21.13/
CSA4.9, latest edition for Gas Fired Low Pressure Steam
and Hot Water Boilers.
Other confirmed approvals and certifications are indi-
cated by stickers on the boiler.
Installation of the boiler must comply with all applicable
codes and regulations imposed by the national, Federal or
local authorities and bodies. If no specific requirements
are defined, in the USA, the latest edition of the National
Fuel Gas Code ANSI Z223.1/NFPA 54 must be complied
with. In Canada, installation must comply in all respects
with the latest edition of the Installation Code for Gas
Burning Appliances and Equipment, CAN/CSA-B.149
and the applicable local regulations and requirements for
the appliance category. The relevant authorities and regu-
latory bodies must be informed before installation starts.
Where required by local regulations, the system must
comply with the American Society of Mechanical Engi-
neers Safety Code for Controls and Safety Devices for
Automatically Fired Boilers (ASME CSD-1).
In the Commonwealth of Massachusetts, this appliance
must be installed by a licensed pipe fitter, taps external to
the boiler must be fitted with T-handles and condensate
piping must be fitted in accordance with the State Plumb-
ing Code.
Observe all standards and guidelines appli-
cable to the installation and operation of this
heating system in your country.