Terra CL 08-33 Technical Documentation Manual

Category
Heat pumps
Type
Technical Documentation Manual
Technical documentation
Planning documentation
Installation instructions
Heat pumps
TERRA CL 08 - 33
Air - water - heat pump
Version 16.09.08
ib_TERRA CL
Page 2
Contents
General information 3
Description 4
Application range 4
Scope of delivery 4
Technical data 5
Design 6
Performance charts 7
Dimensions 9
Interior installation 10
Corner installation 11
Customer preparation 12
Accessories - corner installation 13
Assembly instructions - corner installation 14
Installation - Standard air duct 15
Option 1 16
Option 2 16
Accessories - Standard air duct 17
Customer preparation - Option 1 18
Customer preparation - Option 2 19
Assembly instructions - Standard duct 20
Installation - Flexible air hose 21
Customer preparation - Flexible air hose 22
Accessories - Flexible air hose 23
Assembly instructions - Flexible air hose 24
Conversion from right to left-side connection 25
Exterior installation 26
Customer preparation 26
Accessories - Exterior installation 27
Heating connections 28
Installation diagram 29
Control and regulation 33
Description of control functions 33
General 34
Connection diagram 35
Electrical connection 36
Power supply 36
Actuators - Pumps / valves 37
Sensor systems - sensors / inputs 38
Installing digital offset roomstat RS 40
Installing RFF room sensor 41
Commissioning information 41
Operation 42
Faults 43
Notes 44
Page 3
By purchasing this system you have acquired a modern
and efcient heating system. Ongoing quality controls
and improvements as well as functional checks at the
plant guarantee you technically perfect equipment.
Please read through this documentation carefully. It
contains important information for correct installation and
safe and economical operation of the system.
Safety instructions:
Installation and maintenance work can be hazardous due
to high system pressure, high temperatures and live parts
and may only be operated by specialist staff.
Heat pumps may only be installed by competent specia-
list staff and commissioned by a customer service com-
pany trained to do so by IDM-Energiesysteme GmbH.
When working on the heat pump, the system must be
de-activated and secured against re-activation. In additi-
on, all safety instructions in the relevant documentation,
stickers on the heat pump itself and all other applicable
safety regulations must be observed.
Transport:
During transport, the heat pump must never be inclined
more than 30°. The heat pump must not be transported
on the connection ttings. The transport packaging may
only be removed if the heat pump is located at its installa-
tion location.
Sound emission:
TERRA heat pumps are very quiet in operation thanks to
their design. It is however important that the site of the
heater is situated as far as possible from noise-sensitive
living areas. A noise-insulating door should be tted door.
Construction drying and screed heating
The heat pump is not designed for the increased heat re-
quirements when drying out construction work or heating
plaster or screed. This must be covered by equipment
provided by the customer if required.
Servicing and maintenance:
Regular maintenance as well as checking and servicing
of all system components guarantee its safe and eco-
nomical operation in the long term. To achieve this, we
recommend a maintenance contract with the relevant
customer service company.
Cleaning:
If necessary, the TERRA heat pump can be cleaned with
a damp cloth. The use of cleaning agents is not recom-
mended.
Installing additional components:
The installation of additional components which have not
been tested with the equipment may impair function. No
liability is accepted and the guarantee becomes void in
the event of damage caused for this reason.
Installation area:
- Ensure sufcient ventilation
(according to EN 378 T1-T4)
- No heavy dust formation
- No persistent air humidity
- Frost-proof
Symbols used and their meanings:
Various symbols can be found in these instructions. The
meaning of these symbols is given below.
General instructions for operation
of the heat pump.
Important information on installing and
operating the heat pump. This information
must be observed.
General instructions on installing the
heat pump.
Space for customer service
telephone number
The equipment conforms to the EU Directives:
Applicable EC Directives:
EC Machinery Directive (89/392/EEC)
EC Low Voltage Directive (73/23/EEC)
EC EMC Directive (89/366/EEC)
EC Pressure Equipment Directive
Applicable harmonised EN:
EN 378 EN 60529
EN 292/T1/T2 EN 294
EN 349 EN 60335-1/2-40
EN 55014 EN 55104
Applicable national standards/guidelines:
ÖNORM M 7755-2 (Austria)
DIN 8901 (Germany)
General information
Page 4
Description
The TERRA CL is an air source heat pump with suction
gas scroll compressor with large multi-row Al/Cu, nned
evaporator.
A special speed-controlled radial fan means that large
ow rates can be achieved at low speeds.
A plate heat exchanger is used as the condenser. The
machine frame consists of a steel-reinforced plastic pro-
le. The cover panels are foam-insulated. This means that
the casing is completely protected from cold bridges and
has excellent sound insulation.
The heating controller is a modern controller that fulls all
the functions of standard heating regulation.
The heat pump has a compact design, the evaporator is
ready-tted in the top of the heat pump casing. The heat
pump is lled with refrigerant and is checked in the facto-
ry before shipping for reliable functioning.
Application range
For monovalent heating of single-family and two-family
homes under appropriate environmental conditions. The
building must be equipped with low-temperature heating
(e.g. underoor heating, wall heating, low-temperature
radiator heating).
The lower the maximum heating temperature
is set, the higher the efciency of the heat
pump.
TERRA CL heat pumps work using the R407C safety ref-
rigerant which circulates in a closed circuit when correctly
mounted and commissioned. This minimises its environ-
mental impact.
Scope of delivery
Heat pump unit with suction gas cooled
scroll compressor
Stainless steel plate heat exchanger as condenser
Finned tube Al/Cu evaporator package
Speed-controlled radial fan
Starting current limiter with rotary eld monitoring
Refrigerant collector and dryer
Thermostatic expansion valve
Refrigerant inspection glass
Refrigerant heat exchanger
High pressure and low-pressure limiter
Integrated switching valve for defrosting
Switch cabinet with integrated regulation
Defrost regulator
Inlet air sensor
Thermal relay to protect the compressor
Thermally insulated basic frame
Cladding, insulated against heat and noise
Heating pump (TERRA CL 08-15 only)
Electric heating immerser for any re-heating required
(TERRA CL 08-15 only)
Flexible connection hoses
Starting current limiter
Other accessories:
see also the IDM pricing list
Page 5
Technical data
TERRA CL 08-33
as per EN 14511
Type Unit 8101215222733
Heat output for A2/W35 as per EN 255[kW]8,6 10,5 12,3 15,4 21,2 27,4 33,2
Heat output for A2/W35 [kW] 8,610,412,515,220,926,432,6
Heat output for A7/W35 [kW] 11,1 13,6 16,0 18,9 24,733,039,2
Heat output for A-7/W35[kW]7,3 8,810,412,216,822,828,0
Heat output for A2/W35 EN 255[kW]2,252,763,274,165,587,418,97
Power consumption for A2/W35 [kW] 2,44 2,97 3,57 4,47 5,97 7,76 9,59
Power consumption for A7/W35 [kW] 2,59 3,24 3,85 4,49 6,02 8,04 9,80
Power consumption for A-7/W35[kW]2,372,842,533,945,597,609,33
COP for A2/W35 as per EN 2553,8 3,83,8 3,73,8 3,73,7
COP for A2/W35 3,53,5 3,53,4 3,53,4 3,4
Weight [kg] 240255 290310 395450 480
Dimensions
HxWxD [cm] 153x110x75 153x110x75 163x120x78163x120x78173x120x88193x130x98193x130x98
Condenser
Radiator flow and return pipe R1" AG R1" AG R1" AG R1" AG R 1¼" AG R 1 ½" AG R 1 ½" AG
Max. flow temperature[°C]55555555555555
Max. operational pressure [bar] 3333333
Min. heating circuit water volume [l/h]1500 1800 2200 2650 4000 4850 5650
Pressure loss - heating side [kPa]10111517151718
installed or recommended
UPS 25-60UPS 25-60UPS 25-80 UPS 25-80 UPS 32-80 UPS 32-80TOP S 40/10
Tank-charging pump
installed or recommended [kW] 6666999
Electric heating immerser
Condensate run-offR1" AG R1" AG R1" AG R1" AG R1" AG R1" AG R1" AG
Fan type
Nominal air volume [m³/h] 3500 4000 4500 5500 7500 10000 12000
externally available compression [Pa]
Refrigerant
Filling quantity[kg]3,8 3,94,4 4,56,5 711,2
electrical connection [V]
max. power intake [A]12,214,212,614,517,5 22,527,5
Starting current [A]25,730,73034,841,55465
series connected main current fuse [A]C13 C16C16 C16C20 C25C35
series connected control current fuse [A]C10 C10C10 C10C10 C10C10
series connected electric heating immerser fu
s
[A]C10 C10C10 C10C13 C13C13
Acoustic power level[dB(A)] 61 62 64 65 66 68 69
Sound level in 5 m (internal) [dB(A)]43434546474950
Sound level in 10 m (internal)[dB(A)] 37 37 39 40 41 43 44
3x400V / 50Hz
copper-soldered stainless steel plate heat exchanger
Not included as standard
Not included as standard
radial / speed-controlled
can be freely adjustable using the speed of the fan
R407C
Page 6
Design
The dimensioning of an air/water heat pump should be
such that the bivalence point is between -3 and -10 °C.
This will help ensure that more than 90° of the annual
heating requirement is covered by the heat pump.
The maximum heating output of a building is determined
in the design, including its water consumption require-
ment.
In addition, the standard outside temperature is required.
This is determinated by geographical location and can be
obtained from various institutions.
Example:
Single-family house in Germany
4 persons
Service water consumption requirement:
4 x 0.25 kW = 1 kW
Heating output required:
16 kW
Standard outside temperature for Germany:
- 16 °C
Off-period factor:
1.1
Heating output required:
(service water consumption required + heating output required) x off-period factor = 18.7 kW
0
5
10
15
20
25
30
35
40
45
-20 -15 -10 -5 0 5 10 15 20
W35 EN14511
CL 33
CL 27
CL 22
CL 15
CL 12
CL 10
CL 8
{
{
outside temperature [°C]
heating capacity [kW]
bivalence point of the
particular heatpump
type
standard external temperature
electr. additional heating
at TERRA CL 15
service water required
electr. additional heating
at TERRA CL 22
building- characteristic line
required heating capacity at
standard external temperature
incl. service water required
Page 7
Performance charts
0
5
10
15
20
25
30
35
40
45
-20 -15 -10 -5 0 5 10 15 20
W35 EN14511
CL 33
CL 27
CL 22
CL 15
CL 12
CL 10
CL 8
outside temperature [°C]
heating capacity [kW]
W45 EN14511
Page 8
W55 EN14511
Page 9
Dimensions
Heating supply (exible connection hose)1
Can be used for sensors and control lines2
Can be used for sensors and control lines3
Heating return (exible connection hose)4
Condensation run-off5
d
f
b
h
a
l
k
j
i
g
a d
e
t
m
1
2
3
4
5
Type b h t a d e f g i j k l m
8 1100 1535 750 640
865 690 1035 575 460 350 240 125 125
10 1100 1535 750 640
865 690 1035 575 460 350 240 125 125
12 1200 1635 780 640
965 720 1135 575 460 350 240 125 125
15 1200 1635 780 640
965 720 1135 575 460 350 240 125 125
22 1200 1735 880 740 965 820 1135 675 540 400 260 125 125
27 1300 1935 980 740 1165 920 1235 675 540 400 260 125 125
33 1300 1935 980 740 1165 920 1235 675 540 400 260 125 125
TERRA CL 08-33
All dimensions in mm
Page 10
Interior installation
Installation instructions:
Interior installation of the heat pump is recommended.
This means that the work involved in frost protection
and condensation run-off heating can be avoided. It also
means that the inlet air / outlet air can be conveyed to the
heat pump with the least possible heat losses. Various
installation options are described in detail in the following
chapters.
All components of the heat pump are insulated so that no
condensation is formed on the external parts even at out-
let air temperatures of -20°C. However, it is still advisable
to air the room regularly.
The heat pump is decoupled via vibration dampers. The
installation location should consist of a solid base.
Heating connection:
A exible hose set is included as standard for heating
connections. See technical data for appropriate connec-
tion sizes for specic machines. It is advisable to use air
source heat pumps only in combination with a buffer tank
such as the IDM Hygienik Tank.
Condensation run-off:
Air source heat pumps generate condensation during
operation. With larger machines, up to 50l of water can
be extracted from the ambient air per day. The conden-
sation run-off should be conveyed into the waste water
channel via a siphon using the appropriate pipe diameter
for the machine.
Air routeing:
The various air ducts (see accessories for interior ins-
tallation) and wall openings are designed specically for
the relevant machines in question. Efcient and fault-free
operation can only be ensured if the appropriately sized
connection elements are used.
Even light shafts which are too small
enlarge the pressure loss of the air
routeing. These must therefore be of a
sufcient size.
Light shafts must have a rainwater run-off.
Air inlet / air outlet:
The options for how the air inlet and air outlet are desig-
ned are varied.
The list below provides design guidelines:
Air inlet side and air outlet side should always be on
two different sides of the building.
Openings in the masonry must always be protected
against the penetration of foreign bodies (leaves, small
animals). To do this, mesh grilles should be tted in
light shafts and weather-shield grilles should be ins-
talled on visible walls.
Wall openings must be created as per the specica-
tions and insulated against damp penetration using a
closed-pore insulating material (minimum thickness
50mm).
Noise
Noise level in the installation room depends on various
factors such as room size, absorption capacity, reection,
free noise propagation, etc. For this reason, it is important
that the heat pump is situated as far as possible from
noise-sensitive areas. A noise-insulating door should be
tted.
The night-time reduction in the fan speed means that noi-
se can be reduced by up to 4 dB. Noise level on the inlet
and exhaust air openings are also reduced by approx. 4
dB when using air shafts or ducts.
In case of exterior installation, the installation of the heat
pump in a corner can lead to a higher noise level. Super-
position of the sound waves means that noise level can
increase up to 3 dB.
Page 11
Corner installation
A condensation run-off with siphon must
normally be tted opposite the exhaust
opening for the heat pump.
The ideal position for the heat pump has proved to be in a
corner. Wall openings can be prepared by the customer in
advance. These openings must be insulated with closed
pore insulating material (minimum thickness 50mm).
Space required, accessibility:
To guarantee maintenance and operation of the heat
pump, the following minimum distances must be obser-
ved:
Front side (operation and maintenance side) = 800mm
Maintenance side = 500mm
Observing these distances will help ensure problem-free
system maintenance and operation.
min. 500mm
1
1
Heating connection /
Condensation run-off
Page 12
Exhaust air opening to right Exhaust air opening to left
Based on accessibility, the exhaust air
opening should ideally be on the right-
hand side.
An even, solid installation surface must be selected.
After positioning the heat pump, it must then be made
level. There are adjustable feet on the heat pump for this
purpose.
Customer preparation
Specied dimensions include clearances. A noise-insulating door should be tted. Minimum
thickness of the wall insulation is 50mm.
a
b
d
c
e
e
f
g
a
b
d
c
e
e
f
g
Type abcdefg
81000 830 650 830 90 650 650
10 1000 830 650 830 90 650 650
12 1100 930 680 930 90 650 650
15 1100 930 680 930 90 650 650
22 1100 930 780 930 90 650 650
27 1200 1130 880 1130 90 750 750
33 1200 1130 880 1130 90 750 750
TERRA CL 08-33
All dimensions in mm
Corner installation
Page 13
Accessories - corner installation
Pos. 341
Pos. 342 (343)
Pos. 345 (346)
Pos. 344
T
yp
e 810 12 15 22 27 33
Pos. Accessories Prod. no. Prod. no. Prod. no. Prod. no. Prod. no. Prod. no. Prod. no.
341 Wall connection air inlet
for tight connection
344 Wall connection air outlet 192 364
for tight connection
Pos. Optional accessories Prod. no. Prod. no. Prod. no. Prod. no. Prod. no. Prod. no. Prod. no.
342 Weather-protected inlet grille
Steel, galvanised
343 Wire inlet grille
Steel, galvanised
345 Weather-protected outlet grille 192 365
Steel, galvanised
346 Wire outlet grille 192 366
Steel, galvanised
192 376192 346 192 356
192 375
192 342 192 352 192 372
TERRA CL 08-33
Corner installation
192 341 192 351 192 371
192 343 192 353 192 373
192 344 192 354 192 374
192 345 192 355
Page 14
Assembly instructions - Corner installation
Wall connection is supplied separately. Vertical connec-
tions must be afxed rst. To do this, simply remove the
lm on the rear. The cellular rubber can then be afxed
ush with the external edge of the heat pump.
Additionaly the horizontal elements are also lined on the
front. This will help ensure an optimum seal.
Before the machine is positioned in the corner, a check
should be carried out to ensure that the wall opening
prepared by the customer has been insulated.
The machine can then be moved into the corner.
The heat pump may only be moved with
the panels tted.
If there are any air gaps on the outlet or inlet openings
due to the ground being uneven, this can be corrected
using the adjustable machine feet.
Noise
Noise level in the installation room depends on various
factors such as room size, absorption capacity, reection,
free noise propagation, etc. For this reason, it is important
that the heat pump is situated as far as possible from
noise-sensitive areas. A noise-insulating door should be
tted.
Signicant pressure against the wall
should be avoided.
Page 15
Installation – Standard air duct
If there are no two external walls directly available for
installation, the air ow can be conveyed outwards via
insulated air ducts. Our range includes standard air ducts
which can be connected directly to the heat pump without
adaptation.
There are two ways to do this:
Option 1:
This method is used if there are no two external walls
available. As a short circuit may occur between the sup-
ply and exhaust sides with this method, the inlet and out-
let should be positioned as far apart as possible. The unit
can be separated from any shrubbery by tting dividing
walls if necessary.
Option 2:
This method is equivalent to corner installation. This
method can be used if corner installation is not possible
due to space restrictions or if a gap needs to be bridged
between the heat pump and outlet side.
Air ducts can be connected to the right
and left of the heat pump. Heating and
electrical connections can also be tted
on both sides.
Page 16
Pos. 341
Pos. 342 (343)
Pos. 421 Pos. 423
(424)
Pos. 425 Pos. 426
Pos. 427 (428)
Option 1
Pos. 341
Pos. 342 (343)
Pos. 421 Pos. 423
(424)
Pos. 426
Pos. 427 (428)
Option 2
Page 17
Accessories – Standard air duct
Air ducts are supplied with
mounting materials (screws, washers,
nuts).
Type 8101215222733
Pos. AccessoriesProd. no. Prod. no.Prod. no.Prod. no. Prod. no. Prod. no.Prod. no.
341 Wall connection air inlet
for tight connection
421Outlet panels right/left -
foamed -
423Duct (1000mm) -
insulated - can be cut to length on request -
424Duct (1500mm) -
insulated - can be cut to length on request -
425Bow 90° -
insulated -
426Wall connection -
insulated -
Pos. Optional accessoriesProd. no. Prod. no.Prod. no.Prod. no. Prod. no. Prod. no.Prod. no.
342Weather-protected inlet grille
Steel, galvanised
343Wire inlet grille
Steel, galvanised
427Weather-protected outlet grille-
Steel, galvanised -
428Wire outlet grille -
Steel, galvanised -
388Side panels 192 408
for free cut-out 84
-
-
-
192 351
37
-
-
-
-
192 371
-
192 353
225
192 372
550
192 373
260
192 352
222
192 428
45
Standard duct
-
-
192 341
TERRA CL 08-33
484
192 421 192 431
-
-
-
-
192 424
192 342
121
264
192 425
294
192 426
192 418
9965 73
192 388 192 398
34
120
178
129
192 423
199
118
192 427
192 343
398
Page 18
Customer preparation – Option 1
Specied dimensions include clearances. Wall opening should be thicker around the wall
insulation. Minimum thickness of the wall insulation is 50mm.
a
b
c
d
e
f
g
Type ab c d e fg**
81000 830 500 700 650 720 1100
10 1000 830 500 700 650 720 1100
12 1100 930 500 700 650 770 1100
15 1100 930 500 700 650 770 1100
TERRA CL 08-15
All dimensions in mm
Standard duct - Version 1 (90°)
** for 1000mm duct length / length can be cut to size as required
Page 19
Customer preparation – Option 2
Specied dimensions include clearances. Wall opening should be thicker around the wall
insulation. Minimum thickness of the wall insulation is 50mm.
a
b
c
d
e
f
g
h
Type abcdefg**h
81000 830 500 700 650 720 1100 270
10 1000 830 500 700 650 720 1100 270
12 1100 930 500 700 650 770 1100 270
15 1100 930 500 700 650 770 1100 270
TERRA CL 08-15
All dimensions in mm
Standard duct - Version 2 (180°)
** for 1000mm duct length / length can be cut to size as required
Page 20
Assembly instructions - Standard duct
Air inlet side:
The inlet-side wall connection is supplied separately. Ver-
tical connections must be afxed rst. To do this, simply
remove the lm on the rear side. The cellular rubber can
then be afxed ush with the external edge of the heat
pump.
Additionaly the horizontal elements are also lined on the
front. This will help ensure an optimum seal.
Before the machine is positioned on the inlet opening,
check that the wall opening prepared by the customer
has been insulated.
The heat pump may only be moved with
the panels tted.
If there are any air gaps on the outlet or inlet openings
due to the ground being uneven, this can be corrected
using the adjustable machine feet.
Signicant pressure against the wall
should be avoided.
Outlet panels:
The outlet panel is mounted using the four clamps sup-
plied.
Duct:
Assemble the duct using the screw set supplied. The
tting length should then be checked.
If the straight duct is too long, two rivets can be bored
open on one side so that the ange can be removed. The
duct can then be cut to length using an angle grinder or
a jigsaw with the relevant blade. The ange can then be
re-tted.
Insulation:
The insulation for the straight duct is supplied separately.
This is self-adhesive and needs to be afxed once the
duct has been cut to the correct length.
Wall connection:
The wall connection is sprayed into the wall opening with
assembly foam. The outlet duct must be connected befo-
re the foam hardens.
If two or more ducts are assembled
together, the duct must be supported
(above or below).
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44

Terra CL 08-33 Technical Documentation Manual

Category
Heat pumps
Type
Technical Documentation Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI