Mitsubishi Heavy Industries eco touch RC-EX1A Installation guide

Category
Space heaters
Type
Installation guide

This manual is also suitable for

eco touch REMOTE CONTROL
RC-EX1A/RC-EX1N
INSTALLATION MANUAL
PJZ012D077
B
1
Contents
1.Safety Precautions …………………2
2. Accessories & Prepare on site ……4
3. Remote control installation
procedure …………………………… 4
Determine where to install the remote control
.. 4
Installation procedure …………………………… 5
Main/Sub setting when more than one remote
controls are used ………………………………… 7
4. Functions and menu items of
Remote control ………………………9
5. The indication when power source
is supplied ………………………… 13
6. Installation settings ……………… 15
7. R/C function settings …………… 20
8. IU settings ………………………… 26
9. Service & Maintenance ………… 38
10. Select the Language …………… 46
2
3
1 . Safety Precautions
This installation manual describes the installation methods and precautions related to the remote control. Use this
manual together with the user’s manuals for the indoor unit, outdoor unit and other optional equipment. Please read
this manual carefully before starting the installation work to install the unit properly.
Safety precautions
Please read this manual carefully before starting installation work to install the unit properly.
Every one of the followings is important information to be observed strictly.
WARNING
Failure to follow these instructions properly may result in serious consequences such as
death, severe injury, etc..
CAUTION
Failure to follow these instructions properly may cause injury or property damage.
It could have serious consequences depending on the circumstances.
The following pictograms are used in the text.
Never do. Always follow the instructions given.
Keep this manual at a safe place where you can consult with whenever necessary. Show this manual to installers
when moving or repairing the unit. When the ownership of the unit is transferred, the “Installation Manual”
should be given to a new owner.
WARNING
Ask a professional contractor to carry out installation work according to the installation manual.
Improper installation work may result in electric shocks, fire or break-down.
Shut OFF the main power supply before starting electrical work.
Otherwise, it could result in electric shocks, break-down or malfunction.
Do not install the unit in appropriate environment or where inflammable gas could generate, flow
in, accumulate or leak.
If the unit is used at places where air contains dense oil mist, steam, organic solvent vapor, corrosive
gas (ammonium, sulfuric compound, acid, etc) or where acidic or alkaline solution, special spray, etc.
are used, it could cause electric shocks, break-down, smoke or fire as a result of significant
deterioration of its performance or corrosion.
Do not install the unit where water vapor is generated excessively or condensation occurs.
It could cause electric shocks, fire or break-down.
Use the specified cables for wiring, and connect them securely with care to protect electronic
parts from external forces.
Improper connections or fixing could cause heat generation, fire, etc.
Seal the inlet hole for remote control cable with putty.
If dew, water, insect, etc. enters through the hole, it could cause electric shocks, fire or break-down.
2
3
When installing the unit at a hospital, telecommunication facility, etc., take measures to suppress
electric noises.
It could cause malfunction or break-down due to hazardous effects on the inverter, private power
generator, high frequency medical equipment, radio communication equipment, etc.
The influences transmitted from the remote control to medical or communication equipment could
disrupt medical activities, video broadcasting or cause noise interference.
CAUTION
Do not install the remote control at following places.
It could cause break-down or deformation of remote control.
(1) Where it is exposed to direct sunlight
(2) Near the equipment to generate heat
(3) Where the surface is not flat
Do not leave the remote control with its upper case removed.
When the upper case is removed, put it in a packing box or packing bag to protect internal PCBs or
other parts from dust, moisture, etc.
4
5
2 . Accessories & Prepare on site
Item name Q’ty Remark
Switch box
For 1 piece or 2 pieces (JIS C8340 or
equivalent)
1
These are not required when installing
directly on a wall.Thin wall steel pipe for electric appliance
(JIS C8305 or equivalent)
As required
Lock nut, bushing (JIS C8330 or equivalent)
As required
Lacing (JIS C8425 or equivalent)
As required
Necessary to run R/C cable on the wall.
Putty Suitably For sealing gaps
Molly anchor
As required
R/C cable (0.3 mm
2
x 2 pcs)
As required
See right table when longer than 100 m
Accessories
R/C main unit, wood screw (ø3.5 x 16) 2 pcs
User’s Manual, Installation Manual
Parts procured at site
When the cable length is longer than
100 m, the max size for wires used
in the R/C case is 0.5 mm
2
. Connect
them to wires of larger size near
the outside of R/C. When wires are
connected, take measures to prevent
water, etc. from entering inside.
< 200 m 0.5 mm
2
x 2-core
< 300 m 0.75 mm
2
x 2-core
< 400 m 1.25 mm
2
x 2-core
< 600 m 2.0 mm
2
x 2-core
3. Remote control installation procedure
Determine where to install the remote control
Installation “Using a switch box”
“Installed directly on a wall”
Wiring direction “Backward”
“Upper center”, “Upper left”
Cautions for selecting installation place
(1) Installation surface must be flat and sufficiently strong.
R/C case must not be deformed.
(2) Where the R/C can detect room temperatures accurately.
This is a must when detecting room temperatures with
the temperature sensor of R/C.
· Install the R/C where it can detect the average tempera-
ture in the room.
· Install the R/C separated from a heat source sufficiently.
· Install the R/C where it will not be influenced by the
turbulence of air when the door is opened or closed.
Select a place where the R/C is not exposed to direct
sunlight or blown by winds from the air conditioner or
temperatures on the wall surface will not deviate largely
from actual room temperature.
Installation space
30mm
30mm
30mm
120mm
R/C temperature sensor
Wiring
Secure minimum spaces for
disassembling the case.
Upper left and Upper right sides
……30mm or more
Bottom side…120mm or more
If using L-shaped
screwdriver, 50mm or
more is available.
4
5
Request
Be sure not to install R/C at a place where temperatures around the installation surface of R/C may differ largely from
actual room temperature.
Difference between detected temperature and actual room temperature could cause troubles.
The correction for detected temperature by the R/C cannot offset such temperature difference because it corrects the
detected temperatures itself.
Request
Do not install the R/C at a place where it is exposed to direct sunlight or where surrounding air temperature exceeds 40°C
or drops below 0°C.
It could cause discoloration, deformation, malfunction or breakdown.
Installation procedure
Dimensions (Viewed from front)
Take care to protect the removed upper case
from moisture or dust.
PCB side (Viewed from rear)
To remove the upper case from the bottom cases of R/C
· Insert the tip of flat head screwdriver or the like in the
recess at the lower part of R/C and twist it lightly to
remove.
Connect wires from X and Y terminals of R/C to X and Y
terminals of indoor unit.
R/C wires (X, Y) have no polarity.
In case of embedding wiring
(When the wiring is retrieved “Backward”)
Embed the switch box and the R/C wires beforehand.
Seal the inlet hole for the R/C wiring with putty.
If dust or insect enters, it could cause electric shocks,
fire or breakdown.
8
50
200
Wall
Conduit
Locknut
Switch box
Seal with putty
R/C cable
Wiring hole on bottom case
Bushing
Sensor
USB port
Terminal Block
37 23 23
Fixing holes
18.383.5
120
19
120
6
7
When wires are passed through the bottom case, fix the bottom case at 2 places on the switch box.
Switch box
for 1 pc
Switch box
for 2 pcs
Wire outlet
Downside
Upper side
Bottom case
Downside
Upper side
Bottom case
Wire outlet
Cut out the thin
wall part at the
screw mounting
section with a
knife or the like
before tightening
the screw.
Wire outlet
Downside
Upper side
Bottom case
Downside
Upper side
Bottom case
Wire outlet
Cut out the thin
wall part at the
screw mounting
section with a
knife or the like
before tightening
the screw.
When fixing the bottom case diagonally at 2 places, cut out the
thin wall section on the case.
Fix wires such that the wires will run around the terminal screws
on the top case of R/C.
Install the upper case with care not to pinch wires of R/C.
In case of exposing wiring
(When the wiring is taken out from the “upper center” or “upper left” of R/C)
Cut out the thin wall sections on the cases for the size of wire.
Upper center
Upper left
Upper case
Bottom case
When taking the wiring out from the upper center,
open a hole before separating the upper and
bottom cases. This will reduce risk of damaging
the PCB and facilitate subsequent work.
When taking the wiring out from the upper left,
take care not to damage the PCB and not to
leave any chips of cut thin wall inside.
Cautions for wire connection
Use wires of no larger than 0.5 mm
2
for
wiring running through the remote
control case, Take care not to pinch
the sheath.
Tighten by hand (0.7 N·m or less)
the wire connection. If the wire is
connected using an electric driver, it
may cause failure or deformation.
6
7
If the hole is cut too large, moisture, dust or insects may enter.
Seal gaps with putty or the like.
Fix the bottom R/C case on a
flat surface with wood screws.
In case of the upper center,
pass the wiring behind the
bottom case. (Hatched section)
Fix wires such that the wires
will run around the terminal
screw of the top case of R/C.
Install the top case with care
not to pinch wires of R/C.
120mm
(for retrieving
wire from
upper left)
190mm
(for retrieving wire
from upper center)
Main-Sub setting for use of two or more R/C
Up to two units of R/C can be used at the maximum for 1 indoor unit or 1 group.
One is main R/C and the other is sub R/C.
Operating range is different depending on the main or sub R/C.
R/C function Main Sub
Run/Stop, setting temperature, fan speed and flap
direction operations
High power and energy-saving operations
Energy-saving setting
R/C sensor
Test run menu operation
Room temperature range setting
Indoor unit settings
Individual flap control
Operation data display
Error history display
Indoor unit
R/C cable (No polarity)
R/C
“Main”
R/C
“Sub”
Set the “Main” and “Sub” as described at Section 7.
Main/Sub setting when more than one remote control are used
8
9
Note: Connection to personal computer
It can be set from a personal computer via the USB port (mini-B).
Connect after removing the cover for USB port of upper case.
Replace the cover after use.
If dust, insect, etc. enters, it could cause electric
shocks or breakdown.
Special software is necessary for the connection.
For details, view the web site or refer to the engineering data.
Do not connect to a personal computer
without using the special software.
Do not connect the personal computer to the USB
simultaneously with other USB devices.
It could cause malfunction or breakdown of R/C or
personal computer.
USB port
Cover
Note: Initializing of password
Administrator password (for daily setting items) and service password (for installation, test
run and maintenance) are used.
The administrator password at factory default is “0000”. This setting can be changed
(Refer to User's Manual). When the administrator password is forgotten, it can be
initialized, if the [Highpower] and the [Energy-saving] buttons are pushed simultaneously
for 5 seconds on the administrator password input screen.
Service password is “9999”, which cannot be changed.
When the administrator password is input, the service password is also accepted.
8
9
switch
One push on the button starts operation and
another push stops operation. (
)
switch
Pushing this button starts the high-power operation.
(
)
switch
Pushing this button starts the energy-saving
operation. (
)
Operation lamp
This lamp lights in green (yellow-green) during
operation. It changes to red if any error occurs.
LCD (With backlight)
A touch on the LCD lights the backlight.
The backlight turns off automatically if there is no
operation for certain period of time.
Duration of the backlight lighting can be changed.
(
)
When the backlight is setting ON, if the screen is
tapped while the backlight is turned off, the
backlight only is turned on. (Operations of switches
,
and
are excluded.)
USB port
USB connector (mini-B) allows connecting to a
personal computer.
For operating methods, refer to the User's manual
attached to the software for personal computer
(Utility software of Eco-touch remote control RC-
EX1 series)
See User's manual for details.
Touch panel system, which is operated by tapping the LCD screen with a finger, is employed for any operations
other than the
Run/Stop,
High power and
Energy-saving switches.
LCD display (With backlight)
4.
Functions and menu items of Remote control
Names and functions of sections on R/C (Operating section)
switch
Operation lamp
USB port (mini-B)
switch
switch
Request
· When connecting to a personal computer, do not connect
simultaneously with other USB devices.
Please be sure to connect to the computer directly, without
going through a hub, etc.
10
11
Clock, R/C name display
Displays the current time (
) and the name of R/C
(
)
Icon display
Each icon is displayed when one of following
settings is going on.
When the peak-cut timer
is set.
 
When setting is made
from the sub R/C.
(
)
When the central control
(Optional) is running.
 
When the periodical
inspection is necessary.
(
)
During the ventilation
operation
(
)
 
When ”filter sign” is up.
(
)
When the Permission/
Prohibition setting is made.
(
)
 
When the weekly timer
is set.
(
)
When the paek-cut timer is set.
(
)
Menu button
When setting or changing other than the following
, touch the menu button. When menu items
are displayed, select one and set.
Change operation mode button (
)
Displays the operation mode which is selected
currently. Tap this button to change the operation
mode.
Change set temp button
(
)
Displays the temperature which is set currently.
Tap this button to change the set temperature.
Flap direction button
(
)
Displays the flap direction which is selected
currently. Tap this button to change the flap direction.
Fan speed change button
(
)
Displays the fan speed which is selected currently.
Tap this button to change the fan speed.
Timer button
(
)
Displays simplified contents of the timer which is
set currently.
(When two or more timers are set, a content of the
timer which will be operated immediately after is
displayed.)
Tap this button to set the timer.
Message display
Operation status of air conditioner and messages
related to R/C operations, etc, are displayed.
See User's manual for details.
* All icons are shown for explanation.
Clock, R/C name display
Change operation
mode button
TOP screen
Timer button
Icon display
Menu button
Change set temp
button
Change flap
direction button
Change fan speed
button
Message display
Names and functions of sections on R/C (Display)
10
11
Menu item
Main menu
Basic operation
……………………………………………
Energy-saving setting
……………………………………………
……………………………………………
Ventilation
……………………………………………
……………………………………………
Filter sign reset
Individual ap control
Run/Stop …………………………………
Change operation mode …………………
Change set temp …………………………
Change ap direction ……………………
Change fan speed ………………………
High power operation ……………………
Energy-saving operation…………………
Sleep timer ………………………………
Peak-cut timer ……………………………
Automatic temp set back ………………
Timer
……………………………………………
Set ON timer by hour ……………………
Set OFF timer by hour……………………
Set ON timer by clock ……………………
Set OFF timer by clock …………………
Conrm ……………………………………
Initial setting
……………………………………………
Clock setting ………………………………
Date & time display ………………………
Summer time………………………………
Contrast ……………………………………
Backlight …………………………………
Controller sound …………………………
……………………………………………
Weekly timer
……………………………………………
Home leave mode
Administrator settings
……………………………………………
Permission/prohibition setting …………
Silent mode timer …………………………
Setting temp range ………………………
Temp increment setting …………………
R/C display setting ………………………
Change administrator password ………
Change set temp display ………………
Please refer to
User’s manual
12
13
Main menu
R/C settings ( )
…………………………………………………………………… 20
Main/Sub of R/C ………………………………………………… 21
Return air temp…………………………………………………… 22
R/C sensor ……………………………………………………… 22
R/C sensor adjustment ………………………………………… 22
Operation mode ………………………………………………… 23
˚C / ˚F ……………………………………………………………… 23
Fan speed ………………………………………………………… 23
External input …………………………………………………… 24
Ventilation setting………………………………………………… 24
Flap control ……………………………………………………… 24
Auto-restart ……………………………………………………… 24
Auto temp setting………………………………………………… 25
Auto fan speed …………………………………………………… 25
IU settings ( )
…………………………………………………………………… 26
High ceiling ……………………………………………………… 28
Filter sign ………………………………………………………… 29
External input 1…………………………………………………… 29
External input 1 signal …………………………………………… 29
External input 2…………………………………………………… 29
External input 2 signal …………………………………………… 29
Heating thermo-OFF temp adjustment ……………………… 30
Return air sensor adjustment…………………………………… 30
Fan control in cooling thermo-OFF …………………………… 30
Fan control in heating thermo-OFF …………………………… 30
Anti-frost temp …………………………………………………… 31
Anti-frost control ………………………………………………… 31
Drain pump operation …………………………………………… 31
Residual fan operation in cooling ……………………………… 31
Residual fan operation in heating ……………………………… 32
Intermittent fan operation in heating…………………………… 32
Fan circulator operation ………………………………………… 32
Control pressure adjust ………………………………………… 32
Auto operation mode …………………………………………… 33
Thermo. rule setting……………………………………………… 36
Auto fan speed control ………………………………………… 37
IU overload alarm………………………………………………… 37
…………………………………………………………………… 38
Service & Maintenance ( )
IU address ………………………………………………………… 39
Next service date ………………………………………………… 39
Operation data …………………………………………………… 40
Error display ……………………………………………………… 41
Saving IU settings ……………………………………………… 42
Special settings ………………………………………………… 44
…………………………………………………………………… 46
Select the language
Installation settings ( )
…………………………………………………………………… 15
Installation date ………………………………………………… 16
Company information …………………………………………… 16
Test run …………………………………………………………… 17
Static pressure adjustment …………………………………… 18
Change auto-address …………………………………………… 18
Address setting of main IU ……………………………………… 18
IU back-up function ……………………………………………… 19
(
) It is necessary to input the Service password for menu items showing.
12
13
[Main]
[Sub]
5.
The indication when power source is supplied
Power on and initial setting
Power on and initial setting
Set the main and sub R/C units according to the display at the power on.
(1) When the main and sub are not yet set,
Main/sub input screen is displayed.
When tapping the [Main] or [Sub] button, initial setting starts.
If any wrong button has been tapped by mistake, the setting can be changed after the end of the initializing
operation.
(2) When the main and sub R/C units have already been set,
Ackowledge screen to continue setting is displayed.
(3) When using 2 units of RC-EX1 as the main and sub, if the first one is set for the main, the second is set for the
sub automatically.
· When only one unit of R/C is used, tap the
Main
button.
In the state of initial setting, if either one of buttons ([Main]/[Sub]) is not tapped, it keeps the
screen unchanged.
When two R/Cs are used, if either one of them is set for the main, the other is set for sub
automatically.
Caution
Start screen
Min/sub set input
IU search on
IU info acquisition on
14
15
[Yes] Continue
[No] Change
If the screen is not tapped for more than 15 seconds, the [Yes] (Continue) is
selected and the display changes to the screen of
.
[Yes]
[No]
After the initializing, it returns to the default state.
TOP screen
Set continue acknowledge
Initialize acknowledge
Initialize set on
14
15
Tap the
Menu
button on the TOP screen.
6. Installation settings
Installation settings cover the following items.
(1) Installation date: Register the date when the unit was installed.
(2) Company information: Enter the information of contact for service.
(3) Test run: Cooling test run, drain pump test run or compressor Hz fixed operation is performed.
(4) Static pressure adjustment: Static pressure is adjusted in case of connecting the duct type IU equipped with
the external static pressure adjustment function.
(5) Change auto-address: In case of the Multi Series (KX) models, the IU address can be changed after the auto-
address setting.
(6) Address setting of main IU: In case of the Multi Series (KX) models, set the address of main/sub IU to prevent
from mixing operation modes (Cooling, heating).
(7) IU back-up function: IU rotation, IU capacity back-up, IU fault back-up are set.
②③
Main menu screen is displayed.
Tap the “Installation settings” button on the menu screen.
Display the service password input screen.
Enter the service password (4-digit number).
The service password is “9999”. (Unable to change)
TOP screen
Menu screen
Menu screen #2
S
ervice password input
16
17
⑤⑥
Display the installation settings screen.
Installation date
Enter the date when the unit was installed.
Select the date with
buttons, and tap the
Set
button.
Installation settings menu
Installation date
Installation settings menu
7
8
11
15
16
19
18
Company information
Enter the company information.
Company
Phone No.
Enter the contact.
Up to 10 1-byte alpha numeric letters can be used.
Tap the
Set
button after the input.
Company information
9
10
Enter the contact
16
17
Enter the Phone No. of the contact.
Tap the
Set
button after the input.
Test run
Select a test run item to be implemented.
(a) Cooling test run: Operation can be made only in cooling mode.
(b) Drain pump test run
(c) Compressor Hz fixed operation: Setting can be made when the unit is
stopped. This operation starts by operation procedure of the unit.
Enter the Phone No. of the contact
Test run
12
13
14
Cooling test run
When the room temperature is too low to start the cooling test run, it operates
for 30 minutes by decreasing the set temperature to 5°C.
Drain pump test run
Drain pump can be operated independently.
Compressor Hz fixed operation
Compressor operation frequency of the inverter outdoor unit can be fixed. It
may not be able to control effectively depending on the outdoor unit models.
Cooling test run
Drain pump test run
Compressor Hz xed operation
18
19
Static pressure adjustment
This is operable in case of connecting duct type IU equipped with the external
static pressure adjustment function.
Operating method is described in the installation manuals for the indoor units
with this function.
Static pressure adjustment
⑯⑰
Change auto-address
In case of Multi series (KX) models, the IU addresses registered with the auto-
address setting method can be changed with this function .
When an indoor unit is selected and the
Change
button is tapped, the display
changes to the Change auto-address screen
. When the address is changed
with
buttons and the
Set
button is tapped, it returns to
the Change auto-address screen
on which the new address is displayed.
Tap the
Finish
button to register the new address.
Address setting of main IU
In case of Multi Series (KX) models, it is possible to let indoor units (Sub IUs)
follow the operation mode (Heating, cooling) of the indoor unit (Main IU).
Set the address of the Main IU to the Sub IUs which shall be followed to the
Main IU by using each R/C connected to each Sub IU.
In case of the single PAC unit, or the plural indoor units connected to one R/C,
it is not available to operate.
Setting can be made from the main R/C of Sub IU only. It cannot be set from
the sub R/C of Sub IU.
Change auto-address
Change auto-address
Address setting of main IU
18
19
IU Back-up function
In case of 2 sets of indoor units connected to one R/C, it is available to
perform back-up operation with them.
IU rotation: Operate 2 sets of indoor units alternately at every set time
of operation interval.
Set the timer for changeover
IU capacity back-up: When the temp difference between the set temp
and the actual room temp is higher than the set temp
diff., 2 sets of indoor units operate. When the temp
difference reaches to the set temp diff. it is switched to
one unit operation.
Set the temp diff. for back-up
󰚜
IU fault back-up: If one of the IU has a fault and stops, the other one
starts operation.
[Enable/Disable] setting of each function can be done.
When [IU rotation] or [IU capacity beck-up] is set [Enable], [IU fault
back-up] is set [Enable] automatically.
Set the timer for changeover
In IU rotation function, the timer to changeover the operation of 2
indoor units is set.
󰚜
Set the temp diff. for back-up
In IU capacity back-up function, the temperature difference between
the temp to start operation of 2 indoor units and the set temp is set.
(Setting range 2-5°C)
IU Back-up function
Set the timer for changeover
󰚜
Set the temp diff. for back-up
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268
  • Page 269 269
  • Page 270 270
  • Page 271 271
  • Page 272 272
  • Page 273 273
  • Page 274 274
  • Page 275 275
  • Page 276 276
  • Page 277 277
  • Page 278 278
  • Page 279 279
  • Page 280 280
  • Page 281 281
  • Page 282 282
  • Page 283 283
  • Page 284 284
  • Page 285 285
  • Page 286 286
  • Page 287 287
  • Page 288 288
  • Page 289 289
  • Page 290 290
  • Page 291 291
  • Page 292 292
  • Page 293 293
  • Page 294 294
  • Page 295 295
  • Page 296 296
  • Page 297 297
  • Page 298 298
  • Page 299 299
  • Page 300 300
  • Page 301 301
  • Page 302 302
  • Page 303 303
  • Page 304 304
  • Page 305 305
  • Page 306 306
  • Page 307 307
  • Page 308 308
  • Page 309 309
  • Page 310 310
  • Page 311 311
  • Page 312 312
  • Page 313 313
  • Page 314 314
  • Page 315 315
  • Page 316 316
  • Page 317 317
  • Page 318 318
  • Page 319 319
  • Page 320 320
  • Page 321 321
  • Page 322 322
  • Page 323 323
  • Page 324 324
  • Page 325 325
  • Page 326 326
  • Page 327 327
  • Page 328 328
  • Page 329 329
  • Page 330 330
  • Page 331 331
  • Page 332 332
  • Page 333 333
  • Page 334 334
  • Page 335 335
  • Page 336 336
  • Page 337 337
  • Page 338 338
  • Page 339 339
  • Page 340 340
  • Page 341 341
  • Page 342 342
  • Page 343 343
  • Page 344 344
  • Page 345 345
  • Page 346 346
  • Page 347 347
  • Page 348 348
  • Page 349 349
  • Page 350 350
  • Page 351 351
  • Page 352 352
  • Page 353 353
  • Page 354 354
  • Page 355 355
  • Page 356 356
  • Page 357 357
  • Page 358 358
  • Page 359 359
  • Page 360 360
  • Page 361 361
  • Page 362 362
  • Page 363 363
  • Page 364 364
  • Page 365 365
  • Page 366 366
  • Page 367 367
  • Page 368 368
  • Page 369 369
  • Page 370 370
  • Page 371 371
  • Page 372 372
  • Page 373 373
  • Page 374 374
  • Page 375 375
  • Page 376 376
  • Page 377 377
  • Page 378 378
  • Page 379 379
  • Page 380 380
  • Page 381 381
  • Page 382 382
  • Page 383 383
  • Page 384 384
  • Page 385 385
  • Page 386 386
  • Page 387 387
  • Page 388 388
  • Page 389 389
  • Page 390 390
  • Page 391 391
  • Page 392 392
  • Page 393 393
  • Page 394 394
  • Page 395 395
  • Page 396 396
  • Page 397 397
  • Page 398 398
  • Page 399 399
  • Page 400 400
  • Page 401 401
  • Page 402 402
  • Page 403 403
  • Page 404 404
  • Page 405 405
  • Page 406 406
  • Page 407 407
  • Page 408 408
  • Page 409 409
  • Page 410 410
  • Page 411 411
  • Page 412 412
  • Page 413 413
  • Page 414 414
  • Page 415 415
  • Page 416 416
  • Page 417 417
  • Page 418 418
  • Page 419 419
  • Page 420 420
  • Page 421 421
  • Page 422 422
  • Page 423 423

Mitsubishi Heavy Industries eco touch RC-EX1A Installation guide

Category
Space heaters
Type
Installation guide
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI