  • Hello! I've reviewed the Installation Instructions for the Hubbell Relay Output Interface PD2799. This document details how to install and use the device, which links occupancy sensors to building systems via a dry contact relay. It also outlines safety precautions, specifications and supported features like multiple occupancy sensors and RJ45 communication ports. I'm ready to answer any questions you have about this device.
  • What type of electrical system is this device intended for?
    What safety precaution should be taken before installing or servicing this unit?
    What type of junction box it can be mounted on?
    What is the operating voltage of this device?
PD2799 02/2017 Page 1
Room Controller Relay Output Interface
Installation Instructions
Precautions
READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
CAUTION: For use with Class 2, low voltage systems only. Do not use in high voltage applications.
CAUTION - RISK OF ELECTRICAL SHOCK. To prevent electrical shock, turn OFF power at the circuit breaker
before installing or servicing unit. Never wire energized electrical components.
NOTICE: Do not install if product appears to be damaged.
Be sure to read and understand all instructions before installing or servicing unit
For Indoor use only. Do not use outdoors.
A disconnect switch or circuit breaker must be provided and marked as the disconnecting device.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Confirm that device ratings are suitable for the application prior to installation.
No user serviceable parts contained inside unit. Refer all service related questions to the factory.
All servicing shall be performed by qualified service personnel.
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment
may be impaired.
Do not use this equipment for other than intended use.
Specifications
Mounts to standard 4 11/16” junction box, Hubbell RACO #257 electrical junction box
Removable terminal block for output connection
Supports multiple occupancy sensors in the zone
2 RJ45 room controller communication ports.
Low voltage 1 Form C output relay supports NC and NO operation
Low voltage device: 24 VDC
SAVE THESE INSTRUCTIONS!
Description
The Hubbell Wiring Device-Kellems Output Interface provides a means to link the detected occupancy state of a room controller
zone to HVAC or other building systems using a dry contact relay closure. The internal relay provides NC and NO contacts.
Figure 1
/