Potter SHB/SLB24-75 Indoor Outdoor Strobe Horn Strobe Combination Fire Alarm provides audible and visual signals for fire and burglar alarm protection systems. It features synchronization with other Amseco strobes using the SMD10-3A Sync Module. With a wide operating voltage range of 16-33V DC or FWR, it offers flexible installation options. The strobe delivers a powerful 75 candela output, while the horn ensures a minimum sound output of 83 dBA, meeting safety standards. Its rugged construction with indoor/outdoor capability makes it suitable for various applications.

Potter SHB/SLB24-75 Indoor Outdoor Strobe Horn Strobe Combination Fire Alarm provides audible and visual signals for fire and burglar alarm protection systems. It features synchronization with other Amseco strobes using the SMD10-3A Sync Module. With a wide operating voltage range of 16-33V DC or FWR, it offers flexible installation options. The strobe delivers a powerful 75 candela output, while the horn ensures a minimum sound output of 83 dBA, meeting safety standards. Its rugged construction with indoor/outdoor capability makes it suitable for various applications.

SHB/SLB24-75
INDOOR/OUTDOOR STROBE/
HORN/STROBE COMBINATION
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 • www.amseco-kai.com
MKT. #8850019 - REV B
9/07 PAGE 1 OF 2
PRINTED IN USA
A Brand
• Unit by itself is UL Listed for outdoor use
• Low current consumption
• Wide operating voltage range
AWG #12-18 lead wire connection
Clear lens only
Synchronization requires the SMD10-3A Sync Module
• Capable synchronization with other Amseco strobes
Mounts to SBX-1 outdoor box or SBP-1 plastic mounting plate
Available in red and gray housing
Amseco’s SHB/SLB indoor and outdoor strobe and horn/strobes are designed to provide audible and/or visible signals for re and burglar alarm
protection systems and noti cation signals for the purpose of life safety and protection. They meet or exceed NFPA/ANSI Standards. The unit
by itself is approved as an outdoor appliance under UL 1638 (strobe) and UL 464 (horn).
The SHB/SLB24-75 Series operates on 24V system panels having an output voltage of either DC or FWR between 16-33V. These audible/
visual signals can be connected either independently or in unison. It can be synchronized by using the Amseco Sync Module SMD10-3A. The
horn for the SHB24 can be silenced while the strobe remains ashing.
The SLB24-75 Series is a high performance, high intensity, solid state, indoor/outdoor, 24V DC strobe.
Model Number Input
Voltage
Operating
Voltage
Range
Strobe
Output (cd) Installation Flash
Rate Mounting
Type Sync
Module
Operating
Temperature
Range
SHB24-75C Regulated
24V DC/
FWR
16-33 VDC
16-33 VFWR 75
Indoor
(Fire/ADA) 60 times/
min. Wall SMD10-3A -31°F - 150°F
(-35°C - 66°C)
SLB24-75C Indoor/outdoor
(General)
Engineering Speci cations
The indoor/outdoor audible and visual alarm indicating appliance shall be Amseco model SHB24-75 or equivalent device. The indoor/outdoor
visual alarm indicating appliance shall be Amseco model SLB24-75 or equivalent device. The horn/strobe shall be listed under UL 1971
Standard for signaling devices for the hearing impaired and shall be approved for re protective service. The horn/strobe and strobe shall be
listed in compliance with UL 1638 Visual Appliance Private Mode Emergency and General Utility for use in indoor/outdoor applications. The
candela ouptut shall be eld 75cd intensity output. The signaling strobe shall operate on 24V DC from a non-coded, regulated DC supply or
full-wave recti ed, un ltered supply. The horn may operate on 24V DC coded system. The strobe shall be designed to produce one signal ash
per second with continuously applied minimum voltage. The strobe/horn may have a SPC-1 universal back mounting plate, capable of wall
mounting to a SBX-1 weather-proof back box. When strobe synchronization is required, the strobe/horn shall be compatible with the Amseco
SMD10-3A (daisy chain) or other source of Amseco sync protocol. Audible and visual signaling devices shall be installed in accordance with
current NFPA guidelines.
Ordering Information
Installation Single Gang Box
4” Standard Box
SBX-1
Mounting
Screw Covers
Conduit Connector
and Pipe
firealarmresources.com
MKT. #8850019 - REV B
9/07 PAGE 2 OF 2
PRINTED IN USA
A Brand
Dimensions: inches (mm)
Speci cations
Under CAN/
ULC 525/526 ULC Current (mA)
24V DC 24V FWR
SHB24-75 144 185
SLB24-75 110 155
Wiring Diagram
Maximum RMS Operating Current (mA) Minimum Sound Output
(dBA @ 10 ft per UL 464) Light Output
on Axis (cd)
SHB24-75 Regulated 24V DC Regulated 24V FWR Non- Temporal Temporal 16V 33V
Horn 36 34 83 79
104 118
Horn and Strobe 195 (typical 145) 254 (typical 204)
Strobe 175 239 - -
SLB24-75
Strobe 167 223 - -
SHB/SLB24-75
INDOOR/OUTDOOR STROBE/
HORN/STROBE COMBINATION
Red
Black
White
Orange
Red
Black
White
Orange
Red
Black
Wire Color Horn: 2 - Orange (+) 2 - White (-) Strobe: 2 - Red (+) 2 - Black (-)
SLB24
SHB24
WIRING 4 Wiring Diagram for Audible Strobe Class "B" Circuit with Audible
Silence Feature (SHB24)
WIRING 3 Wiring Diagram for Audible Strobe Class "B" Circuit without Audible Silence Feature
White
Orange
Red
Black
Horn
Strobe
SHB24
WIRING 2
Strobe and Horn
Independently
SHB24
WIRING 1
Strobe and Horn
in Unison
SHB24
White
Orange
Red
Black
Control
Panel
F.A.C.P.
Strobe Signal
Circuit
To Next
Device or
End-of-Line
Resistor
OUTPUT
INPUT
Sync Module
SMD10-3A
HH
To Next
Device or
End-of-Line
Resistor
F.A.C.P.
Horn Signal
Circuit
F.A.C.P.
Strobe Signal
Circuit
F.A.C.P.
Signal Circuit OUTPUT
INPUT
HH
Sync Module
SMD10-3A To Next
Device or
End-of-Line
Resistor
To Next
Device or
End-of-Line
Resistor
F.A.C.P.
Horn Signal
Circuit
To Next
Device or
End-of-Line
Resistor
0.41 (10)
3.38 (85.7)
3.28 (83.5)
3.38 (85.7)
6.50 (165)
5.13 (130)
0.66 (16)
SBP-1 Plate SBX-1 Surface Mount Back Box
2-7/8 (22)
21/32 ( 17 )
1 31/32 (50)
3/16 (4.7) 2-3/8 (60)
6
(152)
3-7/32 (5.6)
3-
9/32 (83.5)
5-
27/32 (148)
2-3/8 (60)
2-1/8 (3.4)
Front View
SBP-1 Plate Side View Back View Bottom View
firealarmresources.com
  • Page 1 1
  • Page 2 2

Potter SHB/SLB24-75 Indoor Outdoor Strobe Horn Strobe Combination Fire Alarm Owner's manual

Category
Fire protection
Type
Owner's manual

Potter SHB/SLB24-75 Indoor Outdoor Strobe Horn Strobe Combination Fire Alarm provides audible and visual signals for fire and burglar alarm protection systems. It features synchronization with other Amseco strobes using the SMD10-3A Sync Module. With a wide operating voltage range of 16-33V DC or FWR, it offers flexible installation options. The strobe delivers a powerful 75 candela output, while the horn ensures a minimum sound output of 83 dBA, meeting safety standards. Its rugged construction with indoor/outdoor capability makes it suitable for various applications.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI