Kamstrup GSM6i Installation and User Guide

  • Hello! I've reviewed the user guide for the Kamstrup GSM6i module, as well as the Kamstrup 162, 382, and 351 Combi electricity meters, and PLC Concentrator. This document details the installation, operation, and data logging capabilities of the module, including instructions for using SMS commands for remote control and signal testing. I'm ready to answer any questions you might have about these devices and their features.
  • What is the main purpose of the GSM6i module?
    What type of SIM card is required for the GSM6i module?
    Is it necessary to use an external antenna?
    What kind of data can be logged by the GSM6i module?
KamstrupA/S
Industrivej28,Stilling,DK-8660Skanderborg
TEL:+4589931000·FAX:+4589931001
info@kamstrup.com·www.kamstrup.com
Installation and
User Guide for
GSM6i
2
Quick Guide
1. Performasignaltestbyusingthetestbuttononthemodem.
2. Ifthesignalstrengthisbelow12,anexternalantennamustbeinstalled.
3. Theexternalantennamustbeplacedinapositionthatimprovesthesignal
reception.Movetheantennaarounduntiltheoptimalpositionislocated.
Performseveralsignaltestswhilefindingthebestposition.
4. UseNetmonitororequivalenttoolstohelpfindthebestpositionforthe
externalantenna,ifnecessary.
5. Beforeleavingtheinstallation,testthesignalstrengthbysendinganSMS.
MakesureallcabinetsanddoorsareclosedbeforesendingtheSMS.
Hints
• Alwaysinstallanexternalantennawheninstallinginametalcabinet.The
antennamustbeplacedoutsidethecabinet.
• UsedualbandGSMantennasforoptimalperformance.
• Beawarethatfiredoors,concreteandmetalplatesdisturbandattenuatethe
GSMsignals.
• Specialdirectionalantennascanbeorderedforareaswithverypoorsignal
conditions(contactKamstrupfordetails).
SMS
When placing the meter
in a metal cabinet, make
sure to place the antenna
outside the cabinet.
Make sure to close all
doors and cabinets
before sending the SMS.
Fire door
When placing the meter
below the ground (e.g. in
a basement), make sure
to place the antenna
close to a window or
outside the building.
Metal cabinet
3
CONTENTS
1. Description ................................................4
1.1. DescriptionofGSM6i.......................................4
1.2. GSM6iApplication.........................................5
1.3. Technicaldata.............................................5
1.3.1. GSM6i,articleno.6814-xxxxx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2. Mounting ..................................................6
2.1. Mountingorder............................................6
2.2. Start-upsequence..........................................7
2.3. Signaltest................................................8
2.4. Diagramforsignalconversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.5. Light-emittingdiodes..................................... 10
2.6. SIMcard................................................ 10
2.6.1. MountingtheSIMcard....................................10
2.6.2. SIMcardrequirements....................................11
2.7. Kamstrup382-type685-282-zz-zz. . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.8. Kamstrup382-type685-382-zz-zz. . . . . . . . . . . . . . . . . . . . . . . . . . 14
2.9. Kamstrup351Combi-type685-251-xx-xx-xxx. . . . . . . . . . . . . . . . . 15
2.10. Kamstrup351Combi-type685-351-xx-xx-xxx. . . . . . . . . . . . . . . . . 16
2.11. MountingofloadcontrolandStatus/Pulseinput. . . . . . . . . . . . . . . 17
3. Data in the GSM6i Module, Article no. 6814-xxxxx . . . . . . . . . . . . . . . 18
3.1. Datalogger.............................................. 18
3.2. Backup................................................ 18
3.3. Daily/weekly/monthlylogger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4. Loadprofile(minutelogger). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.5. Eventlogger............................................. 21
4. Tariff shifting Function ......................................22
5. Error Detection Help ........................................23
6. SMS commands ............................................24
7. GSM6i Variant Structure .....................................26
4
1. Description
1.1. Description of GSM6i
GSM6i,articlenumber6814-xxxxx,isaGSM/GPRSmodemmodulespecially
designedformountinginKamstrupelectricitymetersandinPLCConcentrators.
Itispossibletoconfigurethemoduleasadatalogger,includingdailyvalues,
loadprofile,andeventlog.
5
1.2. GSM6i Application
TheGSM6imoduleisusedinthefollowingmeters:
Article no. Function Meter types
6814-Txxxx Transparentreadingofmeter
orConcentrator
Kamstrup162
Kamstrup382
Kamstrup351Combi
PLCConcentrator
6814-Dxxxx
CommunicationwithGSM6i
datalogger(Datalogger
mode)
Kamstrup162
Kamstrup382
Kamstrup351Combi
1.3. Technical data
1.3.1. GSM6i, article no. 6814-xxxxx
• DualbandGSM/GPRSmodule
• TobemountedasamoduleintheelectricitymeterorConcentrator
• Dataloggerforloadprofile(5,15,30,60mins.),daily/weekly/monthly
loggerandeventlogger
• Tariffandloadcontrol
• Centraluploadofnewfeatures,e.g.newtariffswitchtimes
• Built-inrealtimeclock(RTC)withminimumbackupfor10days
• ReadingofelectricitymetersandsignalstrengthviaSMS
• StatusLED’sforGSM/GPRSnetworkandantennasignal
• GSM/GPRSsignalindicator
• Controloutputforloadcontrol(230VAC,max100mA)
NOTE: Installation to be carried out by authorized personnel only as it can be
highly dangerous to touch connections and internal parts.
6
2. Mounting
GSM6i,articlenumber6814-xxxxx,is230VACsuppliedandpreparedfor
mountingofanexternalantenna.Pleasealsosee“GSM6iVariantStructure”on
page26
2.1. Mounting order
1. Disconnectthevoltagesupplytotheelectricitymeter.
2. Dismountthetopcoverofthemeter.
3. PlacetheGSM6imoduleinthemeter(pleasecheckthatthesixmodule
pinsareallpluggedin).
4. InsertSIMcard(seeparagraph2.6onpage10).
5. Mountthe230VACsupplymainsasshowninparagraph2.7to2.10-
pleasenotethemetertype.Becarefultoleadthewiresasshownonthe
drawings).
6. Connectthemeter.
7. WhenthediodesontheGSM6imodulestopflashing,thesignalstrengthis
readontheindicator(seeparagraph2.3onpage8).
8. Ifthesignalstrengthisacceptable,mountthetopcoverofthemeterand
makesurethatthewiresarenotjammed.
9. Beforeleavingtheinstallation,checkthesignalstrengthbysendinganSMS
(seeparagraph6onpage24).
Ifthemoduledoesnotindicatenormaloperationconditions(suchassufficient
signalstrength),seechapter5onpage23forerrordetectionhelp.
NOTE: In meters delivered before 2004 it may be necessary to make room
for the module by removing a bit of edge from the module with a knife. Be
careful not to leave sharp edges, which can damage the wires.
7
2.2. Start-up sequence
1. Immediatelyafterstart-up,alltheSignalindicatordiodesandthetest
diodeswitchonbriefly(seefig.1onpage7).
2. ThetwoSignalindicatordiodesatthebottomflashuntilthemodulehas
beeninitialisedcorrectly(approx.5secs.)Whenthediodeatthebottom
stopsflashing,themodulehasbeenconnectedtothenetwork(approx.
5-10secs.).
3. Now,thesignalindicatorwillshowthecurrentsignallevel.
4. IfthemoduleisconfiguredforcommunicationviaGPRS,theGPRSdiode
switchesonassoonasthemoduleisconnectedtotheGPRSnetwork
(approx.20secs.afterstart-up).
5. Alldiodeswillturnoffafter10mins.
Diodesforsignal
strengthindicator
GPRSdiode
Testbuttonfor
alternativesignaltest
Testdiode
Figure1
8
2.3. Signal test
FiveLED’shavebeenmountedontheGSM6imoduletoindicatethecurrent
GSMsignalstrength.
Immediatelyafterstartingupthemodule,itwilltrytoconnecttotheGSM
network,andthesignalstrengthindicatorwillbeactivated(seeparagraph2.3
onpage8).
Ifahigherresolutionofthesignalstrengthisrequired,itispossibletomakea
signaltestwiththetestbutton.
1. Pressthebuttonfor2secs.afterwhichthetest
diodeturnsonandlightsforapprox.10secs.
2. Now,thetestdiodewillindicatethesignalstrength
withflashes.Onelongflashequals10andashort
flashequals1,
3. i.e.twolongflashesandthreeshortflashesequal
asignalstrengthof23.
Seeparagraph2.4onpage9formoredetails.
9
2.4. Diagram for signal conversion
Signal
indicated in
dBm
Signal with
Button test
Signal
Indicator
-113 0 0
-111 1 0
-109 2 0
-107 3 0
-105 4 0
-103 5 0
-101 6 0
-99 7 0
-97 8 0
-95 9 1
-93 10 1
-91 11 1
-89 12 2 GSMminimum
-87 13 2
-85 14 2
-83 15 3
-81 16 3
-79 17 3
-77 18 4
-75 19 4
-73 20 4
-71 21 5
-69 22 5
-67 23 5
-65 24 5
-63 25 5
-61 26 5
-59 27 5
-57 28 5
-55 29 5
-53 30 5
-51 31 5
10
2.5. Light-emitting diodes
Signal Indicator (Green) Indicates the current GSM/GPRS signal strength
LED’s1+2flash Themoduleisstartingup
LED1flashes IsconnectingtotheGSMnetwork
LED’s1to5emitlight Indicatesthecurrentsignallevel
NoLEDemitslight PoorGSMsignal,mountanexternalantenna(note
thatalldiodesturnoffautomaticallyafter10mins.)
GPRS (Orange) Indicates the current GPRS status
LEDturnedoff NoGPRSconnection
Test (Orange) Is used for alternative signal test
LEDemitslightconstantly Emitslightconstantlyforapprox.10secs.
duringsignaltest
LEDflashesconstantly Themodulecannotcommunicate
withtheelectricitymeter
Note that all diodes will turn off after 10 mins.
They can be activated again by pressing the test button for 2 secs.
2.6. SIM card
2.6.1. Mounting the SIM card
TheunitcanbeorderedwiththeSIMcardmountedfromthefactory.Please
checkthatthecardhasbeeninserted.Thetelephonenumberofthecard
appearsfromalabelonthesideoftheGSM/GPRSmodule.Thenumbercanbe
readfromtheoutsidewithoutdismountingthemetercover.
KamstrupA/ScannotbeheldresponsiblefortheftandmisuseofSIMcards
fromGSM6iunits.
11
When the SIM card holder is opened, the connection to the
SIM card is disrupted.
When the SIM card has been inserted correctly and the holder is closed, the
module will restart automatically.
IftheunitissuppliedwithoutaSIMcard,makesurethatitisinsertedbefore
usingtheunit.
TheSIMcardholderisopenedbypushingthebrightholdertowardstheleft
andcarefullytippinguptheholder.PlacetheSIMcardwiththe“cut-off”corner
inthetoprightsideandwiththecontactsfacingtheprint.Pleaserememberto
writethetelephonenumberonalabelplacedontheoutsideoftheunit.
2.6.2. SIM card requirements
TheSIMcardmustfulfilthefollowingrequirements:
GSM/GPRS,DATA/SMS-9.6kbV110,PINcodemustbedisabled,novoiceand
nopre-paidcardcanbeused.
SIMcardholder
12
Mounting of external antenna (to be ordered separately)
Connecttheexternalantennatotheconnectoronthemodule.Becarefulto
heara“click”beforethetwoconnectorsareconnectedcorrectly.Placethe
antennacableinsidetheplasticframeofthemoduleandleaditout,down
throughthecablechannelatthebottomoftheelectricitymeter.Seepicture
below.
IMPORTANT
Toensurethattheexternalantennaismountedinawaythatoptimisesthe
receptionconditions,thesignalindicatoronthemodulemustbefollowed
(seeparagraph2.3onpage8).Turntheexternalantennaarounduntilthebest
positionhasbeenfound.
If an external antenna is mounted, the internal antenna MUST be removed.
Do not mount the external antenna inside cabinets made of
metal or other materials that disturb the signal
Removalofinternalantenna Mountingofexternalantenna
13
2.7. Kamstrup 382 - type 685-282-zz-zz
Togainaccesstothescrewterminals,carefullytipupthemainsupplywires.
Aftermounting,carefullyputthesupplywiresbackintothechannel.
L1 L2 L3
Removetheedgeto
makeroomforthe
module,ifnecessary
Gatherexcessive
cableinthechannel
NOTE:Avoidjamming
thewiresinthecorner
whenmountingthe
topcover
MountthemainsupplywiresofGSM6i
interminals2and8ofthemeter
14
2.8. Kamstrup 382 - type 685-382-zz-zz
Togainaccesstothescrewterminals,carefullytipupthemainsupplywires.
Aftermounting,carefullyputthesupplywiresbackintothechannel.
L1 L2 L3
Removetheedgeto
makeroomforthe
module,ifnecessary
Gatherexcessive
cableinthechannel
NOTE:Avoidjamming
thewiresinthecorner
whenmountingthe
topcover
MountthemainsupplywiresofGSM6i
interminals2and11ofthemeter
15
2.9. Kamstrup 351 Combi - type 685-251-xx-xx-xxx
Togainaccesstothescrewterminals,carefullytipupthemainsupplywires.
Aftermounting,carefullyputthesupplywiresbackintothechannel.
L1 L2 L3
Removetheedgeto
makeroomforthe
module,ifnecessary
Gatherexcessive
cableinthechannel
NOTE:Avoidjamming
thewiresinthecorner
whenmountingthe
topcover
MountthemainsupplywiresofGSM6i
interminals2and8ofthemeter
16
2.10. Kamstrup 351 Combi - type 685-351-xx-xx-xxx
Togainaccesstothescrewterminals,carefullytipupthemainsupplywires.
Aftermounting,carefullyputthesupplywiresbackintothechannel.
L1 L2 L3
Removetheedgeto
makeroomforthe
module,ifnecessary
Gatherexcessive
cableinthechannel
NOTE:Avoidjamming
thewiresinthecorner
whenremountingthe
topcover
MountthemainsupplywiresofGSM6i
interminals2and11ofthemeter
17
2.11. Mounting of load control and Status/Pulse input
Thecontroloutputisconnectedinserieswiththeload.Thecontroloutputmust
bechargedwithamaximumof230VAC,100mA.Anexampleofaconnection
betweenelectricitymeterandrecommendedrelay(typeG2RS,OMRON)is
shownbelow.
Thestatus/pulseinputcanbeusedtoreadthestatusofapotential-freecontact
oraspulseinputfrome.g.awatermeter.Ifitisusedaspulseinput,thepulses
willbecountedinthepulseregisteroftheelectricitymeter.
Loadcontroloutput
(max230VAC,100mA)
Status/Pulseinput
(potential-freecontact)
18 19
3 2
5 1
L1 L2 L3 N
L
N
LOAD
Exampleofaconnectionbetween
electricitymeterandrelay,
OMRONtypeG2RSswitchrelay
18
3. Data in the GSM6i Module, Article no. 6814-xxxxx
3.1. Data logger
Thedataloggerstoresdaily/weekly/monthlyvalues,loadprofiles,andevents.
Allregistersanddataareresetwhenthemoduledetectsanewelectricitymeter
(e.g.inconnectionwithanewinstallationorreplacementofthemeter).
3.2. Backup
Incaseofpowerfailure,therealtimeclockhasa10days’backup,which
meansthatthemoduleisabletocontinuedataloggingoncethepoweris
reestablished.
LoggeddataarestoredintheEEPROMofthemodule,andarethereforenotlost
inconnectionwithpowerfailure.
NOTE: As a precaution, logged data will be deleted if the module is moved
from one meter to another.
OntheGSM6imoduleitselfa6-poleplugcanbeusedforfall-backreadingof
themodule’sdataloggerincaseoferrorsontheGSMnetwork.Pleasecontact
KamstrupA/Sforfurtherdetails.
Fall-back
readingviacable
19
3.3. Daily/weekly/monthly logger
Thedaily/weekly/monthlyloggerconsistsofe.g.registersincludingtariffsand
statusinformationconcerningtherealtimeclock.
Thedailyloggerstoresvalueseveryday(at00:00),onthenightofSundayand
Monday(at00:00)fortheweeklylogger,andforthemonthlyloggerattheturn
ofthemonth(at00:00).
Theloggingdepthis45days,45weeks,and45months,respectively.
Pleasenotethatthedaily,weekly,andmonthlyloggercannotbeactivatedat
thesametime.
Registerstructureofthedaily/weekly/monthlylogger:
Time stamp Register 1 Register 2 Register 3 Register 4 Control
Time stamp
Year Month Day Hour Minute
Register 1 Register 2 Register 3 Register 4
Kamstrup162 Actual
energy,kWh 0 Tariff1,kWh Tariff2,kWh
Kamstrup382 Actual
energy,kWh 0 Tariff1,kWh Tariff2,kWh
Kamstrup351Combi Actual
energy,kWh
Actual
energy,kvarh Tariff1,kWh Tariff2,kWh
Control
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7
Phase1 Phase2 Phase3 Clock
adjusted
Clockadj.
7-15secs
Clockadj.
15-60secs.
Clock
not
valid
Periodic
error
20
3.4. Load profile (minute logger)
Theloadprofileiscomposedof5,15,30,or60minutes’valuesandthe
loggingdepthis1080.
Theloggingdepthfor60minutes’valuesis45days.
Theregisterstructurefortheloadprofile:
Time stamp Register 1 Register 2 Kontrol
Time stamp
Year Month Day Hour Minute
Register 1 Register 2
Kamstrup162 Actualenergy,kWh*0
Kamstrup382 Actualenergy,kWh*0
Kamstrup351Combi Actualenergy,kWh** Actualenergy,kvarh
Control
Bit0 Bit1 Bit2 Bit3 Bit4 Bit5 Bit6 Bit7
Phase1 Phase2 Phase3 Clock
adjusted
Clockadj.
7-15secs
Clockadj.
15-60secs.
Clock
not
valid
Periodic
error
*:Theenergyisregisteredwithtwodecimals.
**:Theenergyisregisteredwithoutdecimalsorasverifiedenergywithtwodecimals.
/