2.0Installation
2.1Beforeyoustart
Theapplications(subtypes)intheP370applicationkeyaretobe
usedincombinationwiththeLeanheatMonitor.However,some
applicationshaveextrafunctionswhicharedescribedseparately.
TheECLapplicationkeyP370containsof3subtypes:P370.1,
P370.11andP370.12.
ApplicationP370.1ingeneral:
Thisapplicationissupposedtocontroltwoheatingcircuitsanda
directpreparedDHW.Allcircuitsareseparatewithindividualhex.
TwodigitalinputsS8andS15canbeusedforP2andP3alarm
inputs;inputsaremonitoredonlywhenpumpsareactive.
R4canbeoperatedviainternalschedule.
A01,A02andA03(outputsonECA32)areinparallelcontrolling
M1,M2andM3.Either3-pointoranalogoutputarepossibleas
controlsignals.
S7andS14areusedfor0-10pressureinputsandlogged.Input
scalingisenabled.Alarmloworhighvaluecanbemadeforeach
input.
Thecirculationpump(P2,P3)isONatheatdemandoratfrost
protection.
ThealarmoutputA1ispresentontheseoutputs:
ALARMA1=relay4
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
AlarmA1(=relay4)canbeactivatedif:
•Theactualflowtemperaturediffersfromthedesiredflow
temperature.
•Ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
ModbuscommunicationtoaSCADAsystemcanbeestablished.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkina
master-slavesystem.
Unusedinputscan,bymeansofanoverrideswitchorrelaycontact,
beusedforoverridingthescheduletoafixed'Comfort','Saving',
'Frostprotection'or'Constanttemperature'mode.
P370.1:
Theshowndiagramisafundamentalandsimplifiedexampleand
doesnotcontainallcomponentsthatarenecessaryinasystem.The
numbersincirclesrefertothecircuitnumbers.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:P370.1,sensorsandinputs
ECL310ElectroniccontrollerECLComfort310
S1Outdoortemperaturesensor
S2Returntemperaturesensor,monitoring,circuit2
S3(Mandatory)Flowtemperaturesensor,circuit1
S4(Mandatory)DHWtemperaturesensor,circuit3
S5Returntemperaturesensor,circuit1
S6Returntemperaturesensor,circuit3
S7Pressuresignal,circuit1
S8AlarminputP2
S9(Mandatory)Flowtemperaturesensor,circuit2
S10Returntemperaturesensor,monitoring,circuit2
(S11)Supplyflowpressuresignal
(S12)Supplyreturnpressuresignal
(S13)Returntemperaturesensor,circuit2
(S14)Pressuresignal,circuit2
(S15)AlarminputP3
(S16)Alarminput
Listofcomponents:P370.1,pumpsandactuators
P1DHWcirculationpump,circuit3
P2Heatingcirculationpump,circuit1
P3Heatingcirculationpump,circuit2
M1Motorizedcontrolvalve,circuit3
M2Motorizedcontrolvalve,circuit1
M3Motorizedcontrolvalve,circuit2
A1Alarm
6|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370