Danfoss P370 Operating instructions

Category
Thermostats
Type
Operating instructions
OperatingGuide
ECLComfort310,applicationP370
1.0TableofContents
1.0TableofContents...............................................1
1.1Importantsafetyandproductinformation.....................2
2.0Installation........................................................6
2.1Beforeyoustart.....................................................6
2.2Identifyingthesystemtype......................................16
2.3Mounting...........................................................17
2.4Placingthetemperaturesensors................................21
2.5Electricalconnections.............................................23
2.6InsertingtheECLApplicationKey..............................37
2.7Checklist............................................................44
2.8Navigation,ECLApplicationKeyP370.........................45
3.0Dailyuse.........................................................60
3.1Howtonavigate...................................................60
3.2Understandingthecontrollerdisplay..........................61
3.3Ageneraloverview:Whatdothesymbolsmean?...........66
3.4Monitoringtemperaturesandsystem
components........................................................67
3.5Influenceoverview................................................68
3.6Manualcontrol.....................................................69
3.7Schedule............................................................70
4.0Settingsoverview............................................71
5.0Settings...........................................................74
5.1IntroductiontoSettings..........................................74
5.2Flowtemperature..................................................75
5.3Returnlimit.........................................................80
5.4Flow/powerlimit.................................................86
5.5Optimization........................................................90
5.6Controlparameters................................................97
5.7Pumpcontrol.....................................................103
5.8Refillwater........................................................106
5.9Application.......................................................113
5.10Heatcut-out......................................................120
5.11Alarm..............................................................123
5.12Alarmoverview..................................................134
5.13Anti-bacteria......................................................135
5.14Watermeter......................................................137
6.0Commoncontrollersettings............................138
6.1IntroductiontoCommoncontrollersettings’..............138
6.2Time&Date.......................................................139
6.3Settings............................................................140
6.4Scheduleoutput.................................................141
6.5Holiday............................................................142
6.6Inputoverview...................................................144
6.7Log.................................................................145
6.8Outputoverride..................................................146
6.9Alarm..............................................................147
6.10Keyfunctions.....................................................148
6.11System.............................................................150
7.0Miscellaneous................................................157
7.1ECA30/31setupprocedures.................................157
7.2Overridefunction................................................165
7.3Severalcontrollersinthesamesystem......................168
7.4Frequentlyaskedquestions....................................171
7.5Definitions........................................................175
7.6Type(ID6001),overview.......................................179
7.7Automatic/manualupdateoffirmware.....................180
7.8ParameterIDoverview..........................................181
©Danfoss|2023.04AQ437051327765en-010101|1
1.1Importantsafetyandproductinformation
1.1.1Importantsafetyandproductinformation
ThisOperatingGuideisassociatedwithECLApplicationKeyP370
(ordercodeno.087H3838).
TheECLApplicationKeyP370contains3subtypes,allapplicablein
ECLComfort310:
P370.1:2xHeatinginclusivepressureandreturntemperature
monitoringonheatingsides.
1xDHWinclusivereturntemperaturelimitation/monitoring.
Monitoringofinstallation'ssupplyandreturnpressures.
P370.11:1xHeatinginclusivepressureandreturntemperature
monitoringonheatingsides.
1xdirectDHWinclusivereturntemperaturelimitation/
monitoring.
ThesupplytemperatureS2candeterminethedesiredflow
temperature.
TherefillpumpsP4andP7areoperatedalternately.The
alternationtimecanbesetasseveraldays.
Asolutionwithasinglerefillpumpcanalsobeselected.
P370.12:2xHeatinginclusivepressureandreturntemperature
monitoringonheatingsides.
TherefillvalvesV1andV2areforeachheatingcircuitandP4
pumpiscommon.
M1andM2canbecontrolledwithparalleloutput3-pointor
analogsignalfromECA32.
Asolutionwithasinglerefillpumpcanalsobeselected.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
ThedescribedfunctionsarerealizedinECLComfort310which
includesM-bus,ModbusandEthernet(Internet)communication.
TheapplicationKeyP370complieswithECLComfort310
controllersasofsoftwareversion1.11(visibleatstart-upofthe
controllerandin'Commoncontrollersettings'in'System').
UptotwoRemoteControlUnits,ECA30orECA31,canbe
connectedandthebuilt-inroomtemperaturesensorcanbe
utilized.
TogetherwiththeECLComfort310,theadditionalInternalI/O
moduleECA32(ordercodeno.087H3202)canbeusedforextra
datacommunicationtoSCADA:
Temperature,Pt1000(default)
0-10voltsignals
Theset-upofinputtypecanbedonebymeansoftheDanfoss
Software"ECLTool".
Navigation:Danfoss.com>Serviceandsupport>Downloads>
Tools>Heating>ECLTool.
TheURLis:
https://www.danfoss.com/en/service-and-support/downloads/
TheInternalI/OmoduleECA32isplacedinthebasepartforECL
Comfort310.
ECLComfort310isavailableas:
ECLComfort310,230volta.c.(087H3040)
ECLComfort310B,230volta.c.(087H3050)
ECLComfort310,24volta.c.(087H3044)
2|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
TheB-typeshavenodisplayanddial.TheB-typesareoperatedby
meansoftheRemoteControlunitECA30/31:
ECA30(087H3200)
ECA31(087H3201)
BasepartforECLComfort310:
forECLComfort310,230voltand24volt(087H3230)
AdditionaldocumentationforECLComfort310,modulesand
accessoriesisavailableonhttp://danfoss.com/.
DocumentationforECLPortal:Seehttp://ecl.portal.danfoss.com.
SafetyNote
Toavoidinjuryofpersonsanddamagestothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Necessaryassembly,start-up,andmaintenanceworkmustbe
performedbyqualifiedandauthorizedpersonnelonly.
Locallegislationsmustberespected.Thiscomprisesalsocable
dimensionsandtypeofisolation(doubleisolatedat230V).
AfusefortheECLComfort296/210/310installationismax.
10Atypically.
AfusefortheECLComfort120installationismax.6A.
TheambienttemperaturerangesforECLComfortinoperationare:
ECLComfort120:–5–50°C
ECLComfort210/310:0–50°C
ECLComfort296:0-45°C.
Exceedingthetemperaturerangecanresultinmalfunctions.
Installationmustbeavoidedifthereisariskforcondensation(dew).
Thewarningsignisusedtoemphasizespecialconditionsthatshould
betakenintoconsideration.
Applicationkeysmightbereleasedbeforealldisplaytextsare
translated.InthiscasethetextisinEnglish.
AQ437051327765en-010101©Danfoss|2023.04|3
OperatingGuideECLComfort310,applicationP370
Automaticupdateofcontrollersoftware(firmware):
Thesoftwareofthecontrollerisupdatedautomaticallywhenthekey
isinserted:
ECL210/310,asofcontrollerversion1.11
ECL296,asofcontrollerversion1.58
Thefollowinganimationwillbeshownwhenthesoftwareisbeing
updated:
Progressbar
Duringupdate:
DonotremovetheKEY
Ifthekeyisremovedbeforethehour-glassisshown,youhave
tostartafresh.
Donotdisconnectthepower
Ifthepowerisinterruptedwhenthehour-glassisshown,the
controllerwillnotwork.
Manualupdateofcontrollersoftware(firmware):
Seethesection"Automatic/manualupdateoffirmware"
Thissymbolindicatesthatthisparticularpieceofinformationshould
bereadwithspecialattention.
AsthisOperatingGuidecoversseveralsystemtypes,specialsystem
settingswillbemarkedwithasystemtype.Allsystemtypesareshown
inthechapter:'Identifyingyoursystemtype'.
°C(degreesCelsius)isameasuredtemperaturevaluewhereasK
(Kelvin)oftenisusedfortemperaturedifferences.
4|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
TheIDno.isuniquefortheselectedparameter.
ExampleFirstdigitSeconddigitLastthreedigits
1117411174
-Circuit1Parameterno.
1217412174
-Circuit2Parameterno.
IfanIDdescriptionismentionedmorethanonce,itmeansthatthere
arespecialsettingsforoneormoresystemtypes.Itwillbemarked
withthesystemtypeinquestion(e.g.12174-A266.9).
ParametersindicatedwithanIDno.like"1x607"meanauniversal
parameter.
xstandsforcircuit/parametergroup.
DisposalNote
Thissymbolontheproductindicatesthatitmaynot
bedisposedofashouseholdwaste.
Itmustbehandedovertotheapplicabletake-back
schemefortherecyclingofelectricalandelectronic
equipment.
Disposeoftheproductthroughchannelsprovided
forthispurpose.
Complywithalllocalandcurrentlyapplicablelaws
andregulations.
AQ437051327765en-010101©Danfoss|2023.04|5
OperatingGuideECLComfort310,applicationP370
2.0Installation
2.1Beforeyoustart
Theapplications(subtypes)intheP370applicationkeyaretobe
usedincombinationwiththeLeanheatMonitor.However,some
applicationshaveextrafunctionswhicharedescribedseparately.
TheECLapplicationkeyP370containsof3subtypes:P370.1,
P370.11andP370.12.
ApplicationP370.1ingeneral:
Thisapplicationissupposedtocontroltwoheatingcircuitsanda
directpreparedDHW.Allcircuitsareseparatewithindividualhex.
TwodigitalinputsS8andS15canbeusedforP2andP3alarm
inputs;inputsaremonitoredonlywhenpumpsareactive.
R4canbeoperatedviainternalschedule.
A01,A02andA03(outputsonECA32)areinparallelcontrolling
M1,M2andM3.Either3-pointoranalogoutputarepossibleas
controlsignals.
S7andS14areusedfor0-10pressureinputsandlogged.Input
scalingisenabled.Alarmloworhighvaluecanbemadeforeach
input.
Thecirculationpump(P2,P3)isONatheatdemandoratfrost
protection.
ThealarmoutputA1ispresentontheseoutputs:
ALARMA1=relay4
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationexamplesandelectricalconnections.
AlarmA1(=relay4)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature.
Ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
ModbuscommunicationtoaSCADAsystemcanbeestablished.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkina
master-slavesystem.
Unusedinputscan,bymeansofanoverrideswitchorrelaycontact,
beusedforoverridingthescheduletoafixed'Comfort','Saving',
'Frostprotection'or'Constanttemperature'mode.
P370.1:
Theshowndiagramisafundamentalandsimplifiedexampleand
doesnotcontainallcomponentsthatarenecessaryinasystem.The
numbersincirclesrefertothecircuitnumbers.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:P370.1,sensorsandinputs
ECL310ElectroniccontrollerECLComfort310
S1Outdoortemperaturesensor
S2Returntemperaturesensor,monitoring,circuit2
S3(Mandatory)Flowtemperaturesensor,circuit1
S4(Mandatory)DHWtemperaturesensor,circuit3
S5Returntemperaturesensor,circuit1
S6Returntemperaturesensor,circuit3
S7Pressuresignal,circuit1
S8AlarminputP2
S9(Mandatory)Flowtemperaturesensor,circuit2
S10Returntemperaturesensor,monitoring,circuit2
(S11)Supplyflowpressuresignal
(S12)Supplyreturnpressuresignal
(S13)Returntemperaturesensor,circuit2
(S14)Pressuresignal,circuit2
(S15)AlarminputP3
(S16)Alarminput
Listofcomponents:P370.1,pumpsandactuators
P1DHWcirculationpump,circuit3
P2Heatingcirculationpump,circuit1
P3Heatingcirculationpump,circuit2
M1Motorizedcontrolvalve,circuit3
M2Motorizedcontrolvalve,circuit1
M3Motorizedcontrolvalve,circuit2
A1Alarm
6|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
ApplicationP370.1ingeneral(continued):
HolidayprogramsarepresentforHeatingandDHWcircuits.
Besides,aholidayprogramispresentfortheentirecontroller.
SCADAoverrideispossiblewithanoffsetorabsolutevalue.
Summerandwinterdatesforcut-offareimplementedinthe
standardset-up.
TheapplicationP370requirestheinternalI/OmoduleECA32.
S11andS12measuresupplyflowandreturnpressuresfor
monitoring.
S13measuresreturntemperature.
S14measurespressure,circuit2
S15andS16arealarminputs.
Schedulein"Commoncontroller"isconnectedtotheoutputO1
andcanbeusedforvariousissues.
Heating(circuit1):
P370.11:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.Bymeansofaweek
schedule,theheatingcircuitcanbeinComfort’or‘Savingmode
(twovaluesforthedesiredroomtemperature).InSavingmodethe
heatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
BymeansofthepressuresensorS7theECLcontrollerverifiesthat
thecirculationpumpinquestionisoperating.Ifanacceptable
pressuredifferenceisnotdetected,theECLcontrolleractivates
thealarm.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thecirculationpump(P2)isONatheatdemandoratfrost
protection.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
AQ437051327765en-010101©Danfoss|2023.04|7
OperatingGuideECLComfort310,applicationP370
Heating(circuit2):
Thiscircuitworksaftersameprinciplesascircuit1.
TheflowtemperaturesensorS9isthemostimportantsensor.
Bymeansofaweekschedule(upto3Comfortperiods/day),
heatingcircuit2canbein‘Comfortor‘Saving’mode(twodifferent
temperaturevaluesfordesiredroomtemperature).Themotorized
controlvalveM3controlsthecircuit.
Thereturntemperature(S10)enableslimitationasdescribed
previously.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.Furthermore,the
limitationcanbeinrelationtotheoutdoortemperature.Typically,
thelowertheoutdoortemperature,thehighertheacceptedflow/
power.
Thecirculationpump(P3)isONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
BymeansofthepressuresensorS14theECLcontrollerverifiesthat
thecirculationpumpinquestionisoperating.Ifanacceptable
pressuredifferenceisnotdetected,theECLcontrolleractivates
thealarm.
Heatingcircuit2canbeconnectedafterheatingcircuit1.Ifso,the
desiredflowtemperatureatS3canbeinfluencedbythedesired
flowtemperatureatS9.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
Heatingrelatedcircuits,ingeneral:
Exerciseofcirculationpumpsandcontrolvalvesinperiodswithout
heatingdemandcanbearranged.
8|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
DomesticHotWater(DHW)
P370.11:
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
Theweekschedulecanhaveupto3‘Comfortperiods/day.
AvalueforthedesiredDHWtemperaturecanbesetineachof
themodes.
Thereturntemperature(S6)canbelimitedtoafixedvalue.
ThereturntemperatureS6canmeasure,formonitoringpurpose,
thereturntemperatureonthesecondaryside.Analternative
positionforS6canbeinthereturnontheprimarysideinorderto
limitthereturntemperaturetoafixedvalue.
ThecirculationpumpP1canbecontrolledwithschedule.
ThecirculationpumpinquestionisONatDHWheatingdemandor
atfrostprotection.Thealternationtimecanbesetasanumberof
daysandasettimeontheshiftday.
TheFrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworpowertoasetmaximumvalue.
Overridefunction:
Bymeansofanexternalswitchorarelaycontactthescheduleof
theDHWcircuitcanbeoverriddento
constantComfortmode
constantSavingmode
constantFrostprotectionmode
DHWcircuits,ingeneral
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
Theoutdoortemperature(S1)isusedtoprotectthecirculation
circuit(s)againstfrost.
AQ437051327765en-010101©Danfoss|2023.04|9
OperatingGuideECLComfort310,applicationP370
P370.11ingeneral
TheheatingcircuitcanbegraduallyorfullclosedduringDHW
heating(slidingorfullDHWpriority).
S15andS16areusedfor0–10pressureinputsandlogged.Input
scalingisenabled.Alarmloworhighvaluecanbemadeforeach
input.
A01andA02(outputsonECA32)areinparallelcontrollingM1
andM2.Either3-pointandanalogoutputarepossibleascontrol
signals.
S14,S15andS16pressureinputsarebeinglogged.
BymeansofthepressuredifferenceS7andS8theECLcontroller
verifiesthatthecirculationpumpinquestionisoperating.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkina
master-slavesystem.
Unusedinputcan,bymeansofanoverrideswitch,beused
tooverridethescheduletoafixed'Comfort'or'Saving'mode.
ModbuscommunicationtoaSCADAsystemcanbeestablished.
TheM-busdatacanfurthermorebetransferredtotheModbus
communication.
IncaseofnotreachedpressureatS10withinasettimeanalarm
willbegenerated.
AlarmA1(=relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature
Theactivatedcirculationpumpdoesnotgenerateapressure
difference
Therefillwaterfunctiondoesnotgenerateapressurewithin
apresettime
Ifatemperaturesensororitsconnectiondisconnects/short
circuits.(See:Commoncontrollersettings>System>Raw
inputoverview).
Iftheuniversalalarminput(s)S9/S12areactivated.
P370.11
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:P370.11,sensorsandinputs
ECL310ElectroniccontrollerECLComfort310
ECL32Built-inextensionmodule
S1Outdoortemperaturesensor
S2Supplytemperaturesensor
S3Flowtemperaturesensor,circuit1
S4DHWflowtemperaturesensor,circuit2
S5(Optional)Returntemperaturesensor,circuit1
S6(Optional)DHWreturntemperaturesensor,circuit2
S7Differentialpressureswitch,circuit1
S8Differentialpressureswitch,circuit2
S9Alarminput
S10(Optional)Pressuretransmitterorpressureswitch,circuit1
S11(Optional)Secondarypressuresensor,circuit1.For
monitoringpurpose
S12Alarminput
S13(Optional)DHWcirculationreturnpressuresensor.For
monitoringpurpose
S14(Optional)Coldwatersupplypressuresensor.For
monitoringpurpose
S15(Optional)Primarysupplypressuresensor.Formonitoring
purpose
S16(Optional)Primaryreturnpressuresensor.Formonitoring
purpose
Listofcomponents:P370.11,pumpsandactuators
P1Circulationpump,DHW,circuit2
P2Circulationpump,DHW,circuit2
P3Circulationpump,heating,circuit1
P4Refillwaterpump,circuit1
P5Circulationpump,heating,circuit1
P7Refillwaterpump,circuit1
M1Motorizedcontrolvalve,circuit2
M2Motorizedcontrolvalve,circuit1
V1ON/OFFvalve,circuit1,refillwatervalve
A1Alarm
10|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
Heating(circuit1):
P370.11:
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.Theflowtemperaturesensor(S3)isthemost
importantsensor.ThedesiredflowtemperatureatS3iscalculated
intheECLcontroller,basedontheoutdoortemperature(S1)and
thedesiredroomtemperature.Thelowertheoutdoortemperature,
thehigherthedesiredflowtemperature.Bymeansofaweek
schedule,theheatingcircuitcanbeinComfort’or‘Savingmode
(twovaluesforthedesiredroomtemperature).InSavingmodethe
heatingcanbereducedorswitchedofftotally.
ThemotorizedcontrolvalveM2isopenedgraduallywhenthe
flowtemperatureislowerthanthedesiredflowtemperatureand
viceversa.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.
Thereturntemperature(S5)canbelimited,forexamplenottobe
toohigh.Ifso,thedesiredflowtemperatureatS3canbeadjusted
(typicallytoalowervalue),thusresultinginagradualclosingof
themotorizedcontrolvalve.Furthermore,thereturntemperature
limitationcanbedependentontheoutdoortemperature.
Typically,thelowertheoutdoortemperature,thehigherthe
acceptedreturntemperature.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
BymeansofthepressuresensorS7theECLcontrollerverifiesthat
thecirculationpumpinquestionisoperating.Ifanacceptable
pressuredifferenceisnotdetected,theECLcontrolleractivates
thealarm.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thecirculationpump(P2)isONatheatdemandoratfrost
protection.
Thefrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
AQ437051327765en-010101©Danfoss|2023.04|11
OperatingGuideECLComfort310,applicationP370
AdditionalforP370.11,Heatingcircuit1
ThecirculationpumpsP3andP5areoperatedalternately.One
circulationpumpisusedasaworkingpumpandtheother
circulationpumpisusedasasparepump.Thecirculationpump
inquestionisONatheatdemandoratfrostprotection.The
alternationtimecanbesetasanumberofdaysandasettimeon
theshiftday.Asolutionwithasinglecirculationpumpcanalso
beselected.
Thestaticpressureonthesecondaryside(consumerside)can
1.bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2.beaswitchsignalfromapressureswitch
Incaseofatoolowpressure(S10),therefillwaterfunctionwill
supplementwithwaterfromawatersourceonthesupplyside.The
refillpumpP4/P7isswitchedONandtheON/OFFvalveV1opens.
TherefillpumpsP4andP7areoperatedalternately.Thealternation
timecanbesetasanumberofdays.
Asolutionwithasinglerefillpumpcanalsobeselected.Incase
ofnotreachedpressureatS10withinasettimeanalarmwillbe
generated.
ThesupplytemperatureS2candeterminethedesiredflow
temperature.
Exerciseofcirculationpumpsandcontrolvalveinperiodswithout
heatingdemandcanbearranged.
Overridefunction:
Bymeansofanexternalswitchorarelaycontactthescheduleof
theheatingcircuitcanbeoverriddento
constantComfortmode
constantSavingmode
constantDesiredflowtemperature
constantFrostprotectionmode
12|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
DomesticHotWater(DHW)
P370.11:
IfthemeasuredDHWtemperature(S4)islowerthanthedesired
DHWtemperature,themotorizedcontrolvalve(M1)isopened
graduallyandviceversa.
Bymeansofaweekschedule,theDHWcircuitcanbein‘Comfort
or‘Saving’mode(twovaluesforthedesiredDHWtemperature).
Theweekschedulecanhaveupto3‘Comfortperiods/day.
AvalueforthedesiredDHWtemperaturecanbesetineachof
themodes.
Thereturntemperature(S6)canbelimitedtoafixedvalue.
ThereturntemperatureS6canmeasure,formonitoringpurpose,
thereturntemperatureonthesecondaryside.Analternative
positionforS6canbeinthereturnontheprimarysideinorderto
limitthereturntemperaturetoafixedvalue.
ThecirculationpumpP1canbecontrolledwithschedule.
ThecirculationpumpinquestionisONatDHWheatingdemandor
atfrostprotection.Thealternationtimecanbesetasanumberof
daysandasettimeontheshiftday.
TheFrostprotectionmodemaintainsaselectableflowtemperature,
forexample10°C.
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworpowertoasetmaximumvalue.
Overridefunction:
Bymeansofanexternalswitchorarelaycontactthescheduleof
theDHWcircuitcanbeoverriddento
constantComfortmode
constantSavingmode
constantFrostprotectionmode
DHWcircuits,ingeneral
AconnectedfloworenergymeterbasedonM-bussignalcanlimit
thefloworenergytoasetmaximumvalue.
IfthedesiredDHWtemperaturecannotbereached,theheating
circuitcanbeclosedgraduallytoallowmoreenergytotheDHW
circuit.
Ananti-bacteriafunctionisavailableforactivationonselected
daysoftheweek.
Theoutdoortemperature(S1)isusedtoprotectthecirculation
circuit(s)againstfrost.
AQ437051327765en-010101©Danfoss|2023.04|13
OperatingGuideECLComfort310,applicationP370
P370.12ingeneral
ThecirculationpumpsP1andP2(circuit1)/P3andP5(circuit
2)workinshiftaccordingtoaschedule.Onepumpisusedasa
sparepumpandtheotherpumpisworking.Incaseofmalfunction
(missingdifferentialpressure)ofonepump,theotherpumpwill
takeover.Analarmwillbegeneratedandthedefectivepumpcan
beinspected/repaired.
WhenS12digitalinputisinmonitoringmode,alarmcanbeset.
S15andS16areusedfor0-10pressureinputsandlogged.Input
scalingisenabled.Alarmloworhighvaluecanbemadeforeach
input.
A01andA02(outputsonECA32)areinparallelcontrollingM1
andM2.Either3-pointandanalogoutputarepossibleascontrol
signals.
SCADAoverridenowpossiblewithanoffsetorabsolutevalue.
Summerandwinterdatesforcut-offareimplementedinstandard
set-up.
AlarmA1(=relay6)canbeactivatedif:
Theactualflowtemperaturediffersfromthedesiredflow
temperature
Theactivatedcirculationpumpdoesnotgenerateapressure
difference
Therefillwaterfunctiondoesnotgenerateapressurewithin
apresettime
ModbuscommunicationtoaSCADAsystemcanbeestablished.
UptotwoRemoteControlUnits,ECA30/31canbeconnectedto
oneECLcontrollerinordertocontroltheECLcontrollerremotely.
AdditionalECLComfortcontrollerscanbeconnectedviatheECL
485businordertoutilizecommonoutdoortemperaturesignal,
timeanddatesignals.
TheECLcontrollersintheECL485systemcanworkina
master-slavesystem.
Unusedinputscan,bymeansofanoverrideswitch,beusedto
overridethescheduletoafixed'Comfort'or'Saving'mode.
M-buscommunicationenablesconnectiontofloworenergymeter.
Thecontrollercanlimitthefloworenergytoasetmaximum,but
alsoinrelationtotheoutdoortemperature.
Furthermore,theM-busdatacanbetransferredtotheModbus
communication.
P370.12
Theshowndiagramisafundamentalandsimplifiedexampleanddoes
notcontainallcomponentsthatarenecessaryinasystem.
AllnamedcomponentsareconnectedtotheECLComfortcontroller.
Listofcomponents:P370.12,sensorsandinputs
S1Outdoortemperaturesensor
S2Supplyflowtemperaturesensor
S3Flowtemperaturesensor,circuit1
S4Flowtemperaturesensor,circuit2
S5Returntemperaturesensor,circuit1
S6Returntemperaturesensor,circuit2
S7Differentialpressureswitch,circuit1
S8Differentialpressureswitch,circuit2
S9Pressuretransmitterorpressureswitch,circuit2
S10Pressuretransmitterorpressureswitch,circuit1
S12Alarm
S15(Optional)Primarysupplypressuresensor.Formonitoring
purpose
S16(Optional)Primaryreturnpressuresensor.Formonitoring
purpose
Listofcomponents:P370.12,pumpsandactuators
P1Circulationpump,circuit1
P2Circulationpump,circuit1
P3Circulationpump,circuit2
P4Refillwaterpump
P5Circulationpump,circuit2
M1Motorizedcontrolvalve,circuit1
M2Motorizedcontrolvalve,circuit2
V1Solenoidvalve,circuit1,refillwatervalve
V2Solenoidvalve,circuit2,refillwatervalve
R6Relayoutput,alarm
14|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
P370.12:Heating(circuit1and2):
Typically,theflowtemperatureisadjustedaccordingtoyour
requirements.TheflowtemperaturesensorS3(circuit1)and
S4(circuit2)arethemostimportantsensors.Thedesiredflow
temperaturesatS3andS4arecalculatedintheECLcontroller,
basedontheoutdoortemperature(S1).Thelowertheoutdoor
temperature,thehigherthedesiredflowtemperature.
Thesupplytemperature(S2)isusedto
1.controltheS3andS4temperaturesinrelationtotheS2
temperatureor
2.maximizethelimitofthedesiredflowtemperature
Thefactorysetting,wherethesupplytemperature(S2)determines
thedesiredflowtemperature,doesnotchangethedesiredflow
temperatureaccordingtoComfortor‘Savingmode.
However,ifthesupplytemperature(S2)determinesamax.
limitationofthedesiredflowtemperature,the‘Comfort’and
‘Savingmodewillhavetwodifferenttemperaturevaluesfor
desiredroomtemperature.
ThemotorizedcontrolvalvesM1(circuit1)andM2(circuit2)are
openedgraduallywhentheflowtemperatureislowerthanthe
desiredflowtemperatureandviceversa.
ThereturntemperaturesS5(circuit1)andS6(circuit2)tothe
districtheatingsupplyshouldnotbetoohigh.Ifso,thedesired
flowtemperaturecanbeadjusted(typicallytoalowervalue),thus
resultinginagradualclosingofthemotorizedcontrolvalves.
Inboiler-basedheatingsupplythereturntemperatureshouldnot
betoolow(sameadjustmentprocedureasabove).
Furthermore,thereturntemperaturelimitationcanbedependent
oftheoutdoortemperature.Typically,thelowertheoutdoor
temperature,thehighertheacceptedreturntemperature.
ThecirculationpumpinquestionisONatheatdemandoratfrost
protection.
TheheatingcanbeswitchedOFFwhentheoutdoortemperatureis
higherthanaselectablevalue.
Thestaticpressureonthesecondaryside(consumerside)can
1.bemeasuredasa0-10Vsignal(fromapressuretransmitter)or
2.canbeaswitchsignalfromapressureswitch
IncaseofatoolowpressureatS9/S10,therefillwaterfunction
willsupplementwithwaterfromthesupplyside.
PumpP4willbestartedandactuatorV1orV2willopen.
Thecontrollerispre-programmedwithfactorysettingsthatareshown
inthe‘ParameterIDoverview’appendix.
AQ437051327765en-010101©Danfoss|2023.04|15
OperatingGuideECLComfort310,applicationP370
2.2Identifyingthesystemtype
Sketchyourapplication
TheECLComfortcontrollerseriesisdesignedforawiderange
ofheating,domestichot-water(DHW)andcoolingsystemswith
differentconfigurationsandcapacities.Ifyoursystemdiffers
fromthediagramsshownhere,youmaywanttomakeasketch
ofthesystemabouttobeinstalled.Thismakesiteasiertouse
theOperatingGuide,whichwillguideyoustep-by-stepfrom
installationtofinaladjustmentsbeforetheend-usertakesover.
TheECLComfortcontrollerisauniversalcontrollerthatcanbe
usedforvarioussystems.Basedontheshownstandardsystems,
itispossibletoconfigureadditionalsystems.Inthischapteryou
findthemostfrequentlyusedsystems.Ifyoursystemisnotquite
asshownbelow,findthediagramwhichhasthebestresemblance
withyoursystemandmakeyourowncombinations.
SeetheInstallationGuide(deliveredwiththeapplicationkey)for
applicationtypes/sub-types.
Thecirculationpump(s)inheatingcircuit(s)canbeplacedintheflow
aswellasthereturn.Placethepumpaccordingtothemanufacturer’s
specification.
Advicesforsettings:
Whencircuit1mustbeabletoreceiveaheatdemandfromcircuit
2,circuit3oraslave:
MENU\Settings\Application:'Demandoffset'(ID11017):3K*
WhenaheatingorDHWcircuitmustbeabletosenditsheat
demandtocircuit1orthemaster:
MENU\Settings\Application:'SenddesiredT'(ID1x500):ON
WhenaheatingorDHWcircuitshouldnotsenditsheatdemand
tocircuit1orthemaster:
MENU\Settings\Application:'SenddesiredT'(ID1x500):OFF
*Thisrecommendedvalueisaddedtotheheatdemandvaluefrom
circuit2,circuit3ortheslave;alwaysthehighestdemand.
16|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
2.3Mounting
2.3.1MountingtheECLComfortcontroller
SeetheInstallationGuidewhichisdeliveredtogetherwiththe
ECLComfortcontroller.
Foreasyaccess,youshouldmounttheECLComfortcontrollernear
thesystem.
ECLComfort210/296/310canbemounted
onawall
onaDINrail(35mm)
ECLComfort296canbemounted
inapanelcut-out
ECLComfort210canbemountedinanECLComfort310basepart
(forfutureupgrade).
Screws,PGcableglandsandrawlplugsarenotsupplied.
LockingtheECLComfort210/310controller
InordertofastentheECLComfortcontrollertoitsbasepart,secure
thecontrollerwiththelockingpin.
Topreventinjuriestopersonsorthecontroller,thecontrollerhasto
besecurelylockedintothebase.Forthispurpose,pressthelocking
pinintothebaseuntilaclickisheardandthecontrollernolonger
canberemovedfromthebase.
Ifthecontrollerisnotsecurelylockedintothebasepart,thereisarisk
thatthecontrollerduringoperationcanunlockfromthebaseandthe
basewithterminals(andalsothe230Va.c.connections)areexposed.
Topreventinjuriestopersons,alwaysmakesurethatthecontroller
issecurelylockedintoitsbase.Ifthisisnotthecase,thecontroller
shouldnotbeoperated!
AQ437051327765en-010101©Danfoss|2023.04|17
OperatingGuideECLComfort310,applicationP370
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
Mountingonawall
Mountthebasepartonawallwithasmoothsurface.Establishthe
electricalconnectionsandpositionthecontrollerinthebasepart.
Securethecontrollerwiththelockingpin.
MountingonaDINrail(35mm)
MountthebasepartonaDINrail.Establishtheelectrical
connectionsandpositionthecontrollerinthebasepart.Secure
thecontrollerwiththelockingpin.
DismountingtheECLComfortcontroller
Inordertoremovethecontrollerfromthebasepart,pulloutthe
lockingpinbymeansofascrewdriver.Thecontrollercannowbe
removedfromthebasepart.
Theeasywaytolockthecontrollertoitsbaseorunlockitistousea
screwdriveraslever.
18|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
BeforeremovingtheECLComfortcontrollerfromthebasepart,ensure
thatthesupplyvoltageisdisconnected.
2.3.2MountingtheRemoteControlUnitsECA30/31
Selectoneofthefollowingmethods:
Mountingonawall,ECA30/31
Mountinginapanel,ECA30
Screwsandrawlplugsarenotsupplied.
Mountingonawall
MountthebasepartoftheECA30/31onawallwithasmooth
surface.Establishtheelectricalconnections.PlacetheECA30/
31inthebasepart.
Mountinginapanel
MounttheECA30inapanelusingtheECA30framekit(ordercode
no.087H3236).Establishtheelectricalconnections.Securethe
framewiththeclamp.PlacetheECA30inthebasepart.TheECA
30canbeconnectedtoanexternalroomtemperaturesensor.
TheECA31mustnotbemountedinapanelifthehumidity
functionistobeused.
AQ437051327765en-010101©Danfoss|2023.04|19
OperatingGuideECLComfort310,applicationP370
2.3.3MountingtheinternalI/OmoduleECA32
MountingoftheinternalI/OmoduleECA32
TheECA32module(ordercodeno.087H3202)mustbeinserted
intotheECLComfort310/310Bbasepartforadditionalinputand
outputsignalsinrelevantapplications.
TheconnectionbetweentheECLComfort310/310BandECA32
isa10-pole(2x5)connector.Theconnectionisautomatically
establishedwhentheECLComfort310/310Bisplacedonthe
basepart.
20|©Danfoss|2023.04AQ437051327765en-010101
OperatingGuideECLComfort310,applicationP370
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190