Notifier NION-16C48M Fire Alarm System Owner's manual

Type
Owner's manual
Document 52004
10/10/02 Rev A
52004:A ECN 02-232
UniNetī€ˆ 2000
NION-16C48M
(NION-48M)
NION-16C48M (NION-48M)
Instruction Manual
Version 2
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
2Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
3
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
An automatic fire alarm systemā€“typically made up of smoke
detectors, heat detectors, manual pull stations, audible warn-
ing devices, and a fire alarm control with remote notification
capabilityā€“can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec-
tors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72), manufacturer's
recommendations, State and local codes, and the recommen-
dations contained in the Guide for Proper Use of System
Smoke Detectors, which is made available at no charge to all
installing dealers. A study by the Federal Emergency Manage-
ment Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm systems are designed to pro-
vide early warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide
timely or adequate warning, or simply may not function, for a
variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a build-
ing. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors be-
cause:
ā€¢ Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
ā€¢ Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
ā€¢ Smoke particles may be blown away from detectors by air
outlets.
ā€¢ Smoke particles may be drawn into air returns before reach-
ing the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing cham-
bers tend to detect smoldering fires better than flaming fires,
which have little visible smoke. Detectors that have ionizing-
type sensing chambers tend to detect fast-flaming fires better
than smoldering fires. Because fires develop in different ways
and are often unpredictable in their growth, neither type of de-
tector is necessarily best and a given type of detector may not
provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of flam-
mable materials, etc.).
Heat detectors do not sense particles of combustion and alarm
only when heat on their sensors increases at a predetermined
rate or reaches a predetermined level. Rate-of-rise heat de-
tectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be
tested at least once per year by a qualified fire protection spe-
cialist.
Heat detectors are designed to protect property, not
life.
IMPORTANT!
Smoke detectors must be installed in the
same room as the control panel and in rooms used by the sys-
tem for the connection of alarm transmission wiring, communi-
cations, signaling, and/or power.
If detectors are not so lo-
cated, a developing fire may damage the alarm system, crip-
pling its ability to report a fire.
Audible warning devices such as bells may not alert people if
these devices are located on the other side of closed or partly
open doors or are located on another floor of a building. Any
warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medica-
tion. Please note that:
ā€¢Strobes can, under certain circumstances, cause seizures in
people with conditions such as epilepsy.
ā€¢Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibil-
ity to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
ā€¢In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries have
been properly maintained and replaced regularly.
Equipment used in the system may not be technically com-
patible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against tele-
phone line failure, backup radio transmission systems are rec-
ommended.
The most common cause of fire alarm malfunction is inade-
quate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA stan-
dards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent mainte-
nance. A maintenance agreement should be arranged through
the local manufacturer's representative. Maintenance should
be scheduled monthly or as required by National and/or local
fire codes and should be performed by authorized professional
fire alarm installers only. Adequate written records of all in-
spections should be kept.
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
Precau-L-4-2002.p65
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
4Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
WARNING -
Several different sources of power can be con-
nected to the fire alarm control panel.
Disconnect all sources
of power before servicing. Control unit and associated equip-
ment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION -
System Reacceptance Test after Software
Changes.
To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification, re-
pair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvert-
ently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 de-
vices, must also be tested and proper system operation veri-
fied.
This system meets NFPA requirements for operation at
0-49Ā° C/32-120Ā° F and at a relative humidity of 85% RH - 93%
per ULC - (non-condensing) at 30Ā° C/86Ā° F. However, the use-
ful life of the system's standby batteries and the electronic
components may be adversely affected by extreme tempera-
ture ranges and humidity. Therefore, it is recommended that
this system and all peripherals be installed in an environment
with a nominal room temperature of 15-27Ā° C/60-80Ā° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to light-
ning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility.
Overhead or outside
aerial wiring is not recommended, due to an increased suscep-
tibility to nearby lightning strikes.
Consult with the Technical
Services Department if any problems are anticipated or en-
countered.
Disconnect AC power and batteries prior to removing or in-
serting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifi-
cations, verify that they will not interfere with battery, trans-
former, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Overtightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal re-
moval.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive com-
ponents. Always ground yourself with a proper wrist strap be-
fore handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed to
avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
WARNING: This equipment generates, uses, and can radi-
ate radio frequency energy and if not installed and used in
accordance with the instruction manual, may cause interfer-
ence to radio communications. It has been tested and
found to comply with the limits for class A computing device
pursuant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such in-
terference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to
cause interference, in which case the user will be required
to correct the interference at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of
the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des
Communications du Canada.
FCC Warning
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
Precau-L-4-2002.p65
Acclimate Plusā„¢, HARSHā„¢, NOTIā€¢FIREā€¢NETā„¢, ONYXā„¢, and VeriFireā„¢ are trademarks, and FlashScanĀ® and VIEWĀ® are registered trademarks of NOTIFIERĀ®.
NIONā„¢ and UniNetā„¢ are trademarks of NIS. NISā„¢ and NOTIFIERĀ® Integrated Systemsā„¢ are trademarks and NOTIFIERĀ® is a registered trademark of Fireā€¢Lite Alarms,
Inc. EchelonĀ® is a registered trademark and LonWorksā„¢ is a trademark of Echelon Corporation. ARCNETĀ® is a registered trademark of Datapoint Corporation.
MicrosoftĀ® and WindowsĀ® are registered trademarks of the Microsoft Corporation. LEXANĀ® is a registered trademark of GE Plastics, a subsidiary of General Electric
Company.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
5
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Contents
Section 1: NION-16C48M (NION-48M) Installation.................................... 7
1.1 Description of the NION-16C48M ...................................................................................... 7
Figure 1-1: NION-16C48M Board Layout ..................................................................................... 7
1.2 NION Components.............................................................................................................. 8
Figure 1-2: NION-16C48M Components ...................................................................................... 8
1.3 Installation Conditions ....................................................................................................... 9
1.4 SMX Transceiver Connection .............................................................................................. 9
Figure 1-3: SMX Transceiver Installation ........................................................................................ 9
1.5 Cabinet Installation - NISCAB-3....................................................................................... 10
Figure 1-4: NION-16C48M Cabinet Installation ......................................................................... 10
1.6 NION Power Requirements .............................................................................................. 11
Figure 1-5: MPS24BRB Power Supply ........................................................................................... 11
1.7 NION-16C48M Operation ................................................................................................ 12
Figure 1-6: NION-16C48M Operation LEDs ............................................................................... 12
1.8 Input Configuration .......................................................................................................... 13
1.9 Discrete or Switched Voltage Inputs (21 - 24 and 45 - 48) ............................................. 13
Figure 1-7: Switched Voltage Input Jumpers ................................................................................ 14
1.10 Output Configuration......................................................................................................15
Figure 1-8: Output Relays and NC/NO Jumper Settings .............................................................. 15
1.11 Software Configuration .................................................................................................. 15
1.12 NION-16C48MTB Terminal Boards ................................................................................ 16
Figure 1-9: 16C48MTB Terminal Board Mounting........................................................................ 16
Figure 1-10: Ribbon Cable Mapping ........................................................................................... 16
1.13 Terminal Board Input/Output Connections .................................................................... 17
Figure 1-11: Terminal I/O Mapping ............................................................................................ 17
Figure 1-12: I/O Point Connections.............................................................................................17
Section 2: NION-16C48M Plug-In Application .......................................... 19
2.1 Plug-In Selection and Configuration ................................................................................ 19
Figure 2-1: NION Plug-In Selection and Configuration Form ...................................................... 19
2.2 Mapping Plug-ins With NIONs......................................................................................... 20
Figure 2-2: Network Configuration Window................................................................................ 20
2.3 NION I/O Configuration ................................................................................................... 21
Figure 2-3: 16C48M I/O Configuration ...................................................................................... 21
2.4 Time Codes........................................................................................................................ 24
Figure 2-4: Time Code Configuration.......................................................................................... 24
2.5 Universal Time Codes and Time Code Groups ................................................................ 25
2.6 Holiday Codes ................................................................................................................... 25
Figure 2-5: Holiday Code Configuration ..................................................................................... 25
2.7 Functional Properties of the 16C48M ............................................................................... 26
Index ........................................................................................................ 31
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
6Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Foreword
The contents of this manual are important and must be kept in close proximity of the hardware. If building owner-
ship is changed, this manual and all other testing and maintenance information must also be passed to the current
owner of the facility. A copy of this manual was shipped with the equipment and is also available from the manu-
facturer.
This equipment has been designed to comply with standards set forth by the following regulatory agencies:
NFPA Standards
ī€± National Fire Protection Association Standards 72.
ī€± National Electric Code (NFPA 70).
ī€± Life Safety Code (NFPA 101).
Underwriters Laboratories U.S. Documents
ī€± UL-864 Control Units for Fire Protective Signaling Systems.
ī€± UL-1076 Proprietary Burglar Alarm Units and Systems.
Underwriters Laboratories Canada Documents
ī€± CAN/ULC-S524-M91 Standard for Installation of Fire Alarm Systems.
ī€± CAN/ULC-S527-M99 Standard for Control Units for Fire Alarm Systems.
Other
ī€± Requirements of the Local Authority Having Jurisdiction (LAHJ).
WARNING: Improper installation, maintenance, and lack of routine testing could result in system malfunction.
Introduction
The NION-16C48M is a plug-in component of the UniNetī€¾ Workstation. The NION-16C48M provides a gateway
to the network for discrete monitored devices, equipment and control panels that have dry contacts.
This system is suitable for proprietary systems listed under:
ī€± NFPA 72-1993 Proprietary Service.
UniNetī€¾ consists of graphical workstations monitoring and controlling local or remote twisted pair or fiber optic
networks. Remote network monitoring is achieved through the use of a Building Communications Interface (BCI),
which has a maximum capacity of 32 nodes. Each Local Area Server (LAS) has a maximum capacity of 200 nodes,
using twisted pair or fiber-optic cabling. A twisted pair network topology (FT-10) may be a maximum length of
6000 feet per network segment with no T-taps, allowing communications between 64 nodes in each segment. In
addition, FT-10 allows dedicated runs of 8000 feet point-to-point or multiple T-taps within 1500 feet of any other
node on the segment. Fiber-optic cable runs can be configured in either a bus or ring topology with up to 8db of
attenuation between nodes. The network is supervised for shorts, opens and node failures as dictated in Style 4
wiring.
The network power is 24 VDC nominal and receives operating power from a power limited, filtered source listed
for use with fire protective signaling units.
Related Documentation
Network Installation Manual 51539 UniLogic 51547
Workstation 51540 AM2020/AFP1010 Instruction Manual 52020
System Utilities 51592 UniTour 51550
BCI ver. 3-3 51543 IRM/IM 51591
Local Area Server 51544 UniNet Online 51994
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
7
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
1.1 Description of the NION-16C48M
The NION-16C48M (16 Control, 48 Monitor) is a discrete input/output interface used on the UniNetī€¾ 2000
network. All of the system components are based on LonWorksī€¾ (Local Operating Network) technologies. The
NION-16C48M provides a gateway to the network for discrete monitored devices, equipment and control panels
that have dry contacts.
The NION-16C48M connects a LonWorksī€¾ FT-10 or fiber optic network with discrete monitored devices and
conventional control panels. It provides a single, two-way communication channel for discrete inputs and outputs.
NIONs are specific to the type of network to which they connect (FT-10 or fiber). The transceiver type must be
specified and ordered separately when ordering the NION.
The NION is also available in a depopulated version - the 48M NION. It is identical in all aspects to the
16C48M, except the 48M board has no output relays.
The NION can be powered by any power limited, filtered source with battery backup which is UL or ULC listed, as
appropriate for your area, for use with fire protective signaling units. Power must be supervised or placed within 20
ft of the NION with connections run in conduit.
The NION mounts in an enclosure (NISCAB-3) with conduit knockouts. It cannot be rack mounted.
Section 1: NION-16C48M (NION-48M) Installation
1
Figure 1-1: NION-16C48M Board Layout
Terminal Board 2
Ribbon Cable
Connectors
Input LEDs
Terminal Board 1 Ribbon
Cable Connectors
Output Relays 1 - 16
Not included on the
NION-48M
Binding Pin
Reset Pin
Status LEDs
Comm. LEDs
SMX Module Connector
Network EPROM
NION
Program
EPROM
SMX Module Stand-
offs Not Used
Configuration
Jumpers for
Inputs 21 - 24
and 45 - 48
Configuration
Legend for Inputs
21 - 24 and 45 -
48
CPU
Configuration
Battery Backup
TB1 Power
Connector
- +
NOTE: Use only wire for power limited systems.
Power limited wire runs use type FPLR, FPLP, FPL or
equivalent cabling per NEC 760.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
8Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
SMX Network Transceiver
One SMX transceiver daughter board
is required for local network connec-
tion. Three styles are available for
different topologies and media. This
daughter board mounts on the mother
board with a header strip and two
standoffs.
NISCAB-3
The NION-16C48M mounts
in a locking cabinet with a
Lexan dress plate.
(12.25"H X 9.25"W X 2.75"D)
Transformer Assembly
One 4000TA, 110VA trans-
former and connector.
Batteries
The cabinet provides space for 12AH
batteries. To use 17AH capacity
batteries use the BB-17 battery box.
16C48M Mother Board
The NION motherboard contains all
relays, LEDs, CPU, configuration
jumpers, network interface, firmware
and terminal board connections.
16C48MTB Terminal Boards
Each NION uses two terminal boards
which mount directly on the mother board
with stand-offs. These boards provide
terminal connections to monitored inputs
and outputs.
MPS24BRB Power Supply
The MPS24B supplies 2.0A of 24VDC
regulated power to operate the NION. Up
to 200mA of resettable auxiliary power is
also available. This supply contains an
integral battery charger which can support
6.5 to 17AH batteries.
NOTE: Line cord not included.
Figure 1-2: NION-16C48M Components
The NION-16C48M is designed to be wired to control panels and the network through plug-in terminal strips.
The NION-16C48M has the following features:
ī€± Accepts normally open or normally closed dry contact inputs in any combination.
ī€± Control outputs are SPDT relays rated at 2.5A @ 30 VDC.
ī€± Powered from a power limited, supervised, filtered source with battery backup which is UL or ULC listed, as
appropriate for your area, for use with fire protective signaling units.
ī€± Point status LEDs for each input and output
ī€± NION status, Binding status (service), and Network status LEDs.
ī€± Inputs can be configured as either two-state unsupervised or four-state supervised with EOL resistors. Eight
of the inputs are configurable for switched voltage monitoring.
ī€± Transformer coupled network connection using SMX style transceivers.
ī€± Software configurable from the workstation plug-in utility.
ī€± Transient protection to 2400V on all terminals.
ī€± Included wall mount enclosure (NISCAB-3).
1.2 NION Components
The following illustration displays components included and required to install a NION-16C48M on the network.
All of these items must be ordered separately.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
9
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
1.3 Installation Conditions
The NION-16C48M can be installed in the following environmental conditions:
ī€± Temperature range of 0ĀŗC to 49ĀŗC (32Ā°F - 120Ā°F).
ī€± 93% humidity non-condensing at 30ĀŗC (86Ā°F).
1.4 SMX Transceiver Connection
Install the standoffs onto the 16C48M board, then connect JP1 of the transceiver to J4 of the 16C48M
motherboard. Lastly, secure the transceiver to the standoffs with screws.
J4 SMX Header on
16C48M board
JP1 Transceiver
Connector
J4 JP1
Transceiver mounting
standoffs Transceiver mounting
standoffs
16C48M board
SMX Transceiver
Figure 1-3: SMX Transceiver Installation
NOTE: Always observe ESD precautions when
working with electircal hardware.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
10 Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Figure 1-4: NION-16C48M Cabinet Installation
1.5 Cabinet Installation - NISCAB-3
The NION-16C48M is installed into a standard wall mount enclosure, the NISCAB-3. This enclosure has a locking
door and mounting hardware for the 16C48M assembly (motherboard, terminal boards and network transceiver),
MPS24BRB power supply, transformer and batteries.
Mounting the enclosure to its wall position
1) Use the provided key to unlock the enclosure cover.
2) Remove the enclosure cover.
3) Mount the enclosure to the wall. Refer to the enclosure mounting hole layout below.
4) Mount the MPS24BRB power supply and transformer to the stand-offs in the back of the cabinet using the
provided hardware.
5) Mount the 16C48M motherboard to the mounting rails in the same manner.
Distances can vary between the NION and monitored equipment, but the maximum wire resistance must not exceed
500 ohms. The type of hardware used is at the discretion of the installer, but must be in accordance with local
code requirements.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
11
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
1.6 NION Power Requirements
The NION-16C48M is powered by the MPS24BRB power supply, which uses 110VAC, 1.8A(max.) of power and
provides 2.0A of 24VDC power and battery backup in accordance with local code requirements. The MPS24BRB
contains a built in battery charging circuit capable of supporting 6.5 to 17AH 24VDC batteries.
Alternately, the NION can be powered by any power limited, regulated 24 VDC source which is UL or ULC listed,
as appropriate for your area, for use with fire protective signaling units. For replacement part orders, specify
MPS24BRB for Replacement Board.
Power Supply Connections to the NION
Power connections from the MPS24BRB to the NION must be as follows:
TB1 on the 16C48M motherboard to pins 3 and 4 of TB2 on the MPS24BRB.
Terminals on both boards are labelled for proper connections.
NOTE: Always remove power from the NION before making any changes to switch settings
and removing or installing option modules, SMX network modules and software upgrade chips
or damage may result.
Figure 1-5: MPS24BRB Power Supply
Transformer
Connection
AC Power Reset
Not Used
Auxiliary 24VDC Power
200mA max. Power limited,
filtered, regulated and resettable.
Removal disables battery
charging.
Normally Closed
Trouble Contacts
Contacts open when the
main power supply enters a
trouble condition.
Secondary Power
27.6VDC, 6.5 to 17AH. Supervised and
power-limited. Fast charge = 0.75 amps
(typical), trickle charge = 20mA (typical).
Hot Neutral Earth/Service Ground
Primary Power
110VAC, 1.8 amps max.
Earth Ground
Connect to chassis with a
grounding cable assembly
(Cable #71073).
Cut JP1 to make auxiliary
power non-resettable.
Do not cut.
+24VDC NION Power
Circuit is power-limited, RMS-regulated,
non-resettable, 2.0 amps max.
Battery -
Battery +
-+
Common
NOTE: Use only wire for power limited systems.
Power limited wire runs use type FPLR, FPLP, FPL or
equivalent cabling per NEC 760.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
12 Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
1.7 NION-16C48M Operation
The NION-16C48M is configured and operated over the network from a workstation using the NION-16C48M
Plug-In configuration utility. The only operation information involving the hardware is the LEDs which display the
status of various parts of the NION. The LEDs (as shown below), operate in the following fashion:
ī€±NION Status LED - The NION status LED shows the status of the NION itself. If the LED is flashing
slowly, the NION is operating normally. If the LED is on solid, then the NION is not functioning properly.
ī€±Network Status LED - The Network status LED shows the status of the neuron chip that interfaces the
NION to the Echelon network. If this LED is flashing, then the neuron chip is operating properly. If it is
unlit, then the neuron chip is not operating, or not bound to the network.
ī€±Network Packet LED - The Network Packet LED indicates when information is sent or received over the
network. This LED will flash for activity in this manner.
ī€±Service LED - The Service LED indicates the binding status of the NION. If this LED is flashing, the NION
is unbound. If this LED is lit, that indicates that the neuron chip is not running or has reached an unrecov-
erable error. When bound, the LED is unlit.
ī€±Input LEDs - Input LEDs indicate the current status of each input. Each LED will display the following
patterns for each device status:
Point Disable - The LED will flash once every seven seconds.
Point Disarm/Override with Input Active or Input Normal - The LED will flash three times in rapid succession
once every three seconds.
Point Arm/Disarm/Override with Wire Open - The LED will flash rapidly (about 20 times a second) continu-
ously.
Point Arm/Disarm/Override with Wire Short - The LED will flash slowly (about once a second) continuously.
Point Armed with Input Active - The LED remains in the ON state continuously.
Point Armed with Input Normal - The LED remains in the OFF state continuously.
Each time the node is reset, all the LEDs will cycle once to test operation.
ī€±Output LEDs - Output LEDs indicate the status of each relay output. If an Output LED is off, then the
associated output is not activated. If the LED is On, then the output is activated. Refer to section 1.7.7 for
the location of output LEDs. Not used on the NION-48M.
ī€±Serial Communications Activity LED - This LED flashes when information is transmitted via the EIA-232
serial interface (not used for this application).
Figure 1-6: NION-16C48M Operation LEDs
Input LEDs 18
48
NION Status
Network Status
Serial
Network
Packet
Service
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
13
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
NOTE: Two-state, unsupervised inputs cannot be used for fire applications.
1.9 Discrete or Switched Voltage Inputs (21 - 24 and 45 - 48)
Inputs 21 through 24 and 45 through 48 can be configured to operate as discrete, two-state unsupervised or four-
state supervised inputs or, switched voltage (SV) inputs. Each input can be individually configured for maximum
flexibility. To define the function of each of these inputs, four jumpers must be set. These jumpers are grouped
together for easy identification. Figure 1-7 shows the location of these jumper groups and a breakdown of each
jumper setting for the defined functions.
1.8 Input Configuration
Inputs can be configured as tracking (default) or latching for two-state unsupervised or four-state supervised
operation. In addition, 8 inputs (21 - 24, 45 - 48) can be configured to monitor switched voltage inputs. Con-
figuration of two-state/four-state and tracking/latching operation is performed in the workstation plug-in. Configu-
ration of switched voltage operation is done by setting jumpers on the 16C48M motherboard. These jumpers are
grouped in an area beneath the terminal boards.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
14 Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Configuration Jumpers for Inputs 21 - 24 Configuration Jumpers for Inputs 45 - 48
Single Input Jumper Group
Pin 1
Pin 2
Pin 3
Vertical Jumpers
For SV inputs, close pins 1 and 2.
For Discrete, close pins 2 and 3.
Factory jumper setting.
Do not change.
For SV inputs close pins 1 and 2.
For Discrete close pins 2 and 3.
For SV inputs, close the following
pins to select the monitored
voltage:
5VDC - 1 and 2
12VDC - 3 and 4
30VDC - 5 and 6
60VDC - 7 and 8
Jumper Pin Key
Figure 1-7: Switched Voltage Input Jumpers
Pin 1 Pin 2 Pin 3
Horizontal Jumpers
Pins 7 5 3 1
Pins 8 6 4 2
Jumper Blocks
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
15
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
1.10 Output Configuration
The NION-16C48M provides 16 SPDT relay outputs. The relays are rated at 2.5A @ 30VDC. They can be wired
for normally open or normally closed operation. All rated loads are resistive. Inductive and tungsten loads will be
lower. For special applications, consult with a NOTIFIERĀ® applications engineer.
Output relays are located at the bottom of the 16C48M motherboard and correspond (from left to right) to outputs
one through sixteen. Above each relay is its related LED and below is a corresponding jumper to set the output for
normally open or normally closed operation. Refer to the diagram below for jumper settings.
Figure 1-8: Output Relays and NC/NO Jumper Settings
Output LED
Output Operation Jumper
Set the jumper across pins 1
and 2 for normally closed
operation. Set the jumper
across pins 2 and 3 for
normally open operation.
Output Relay
(Typical)
Output Relays
1 - 16
16C48M
Motherboard
Pin 1 Pin 3
For information on output terminal connections, refer to section 1.12 NION-16C48MTB Terminal Boards.
1.11 Software Configuration
In order to utilize all features available with the NION-16C48M, the 16C48M Plug-In utility must be configured at
the system workstations. Features include a scheduler for all inputs and outputs and configuring each input as
normally open or normally closed.
16C48M Device Addressing
Device addressing at the workstation uses the following convention:
Inputs - IN1 through IN48
Outputs - OUT1 through OUT16
The NION-48M requires input addresses only.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
16 Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
1.12 NION-16C48MTB Terminal Boards
The Terminal Boards
The NION-16C48M incorporates two terminal daughter boards which are mounted directly to the motherboard
using included stand-offs. Both terminal boards are identical and interchangeable. Each terminal board is
connected to the motherboard via included ribbon cables (four per terminal board). Point designation for each
terminal is determined by the position of the terminal board on the motherboard. Refer to the diagrams below for
terminal board mounting and ribbon cable connections.
Figure 1-9: 16C48MTB Terminal Board Mounting
Ribbon cables have universal ends and are keyed for proper connection. The motherboard has eight cable
sockets, P1 through P8. Each terminal board has four sockets labelled P1 through P4. Terminal board one (T1) is
mounted on the left and terminal board two (T2) is mounted on the right. The chart below maps the motherboard
sockets to the terminal board sockets.
Figure 1-10: Ribbon Cable Mapping
Cable Sockets P1 - P8
Terminal Board 1 Terminal Board 2
Mounting Stand-off Mounting Stand-off
Mounting Stand-off
This stand-off is also
used to attach the
motherboard to the
cabinet.
Mounting Stand-off
Cable Sockets P1 - P4
Motherboa-
rd Socket Terminal
Board Terminal
Socket
P1 T1 P1
P2 T1 P2
P3 T1 P3
P4 T1 P4
P5 T2 P1
P6 T2 P2
P7 T2 P3
P8 T2 P4
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
17
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
1.13 Terminal Board Input/Output Connections
Each terminal board has four rows of plug-in screw terminal connectors to land input and output points. All inputs
are rated at 5VDC nominal, 2.5mA maximum current and 500 ohms maximum resistance. The inputs and outputs
map to the connectors as described by the following diagrams (Outputs are not included on the 48MTB):
P1
Terminal Board 1 Terminal Board 2
P1
P2 P2P3 P3
P4 P4
Inputs 1 - 8
Inputs 9 - 16
Inputs 17 - 24
Outputs 1 - 8
Inputs 25 - 32
Inputs 33 - 40
Inputs 41 - 48
Outputs 9 - 16
Figure 1-11: Terminal I/O Mapping
ABCDE FGH
Output Terminals (A - H represent any 8 outputs)
Input Terminals (A - H represent any 8 inputs)
Ground
ABCDE FGH
Figure 1-12: I/O Point Connections
NOTE: Input ground is common except for inputs 21 - 24 and 45 - 48 when they are used
for switched voltage monitoring.
Four-state Input Wiring
R-1K resistor
R-3.3K
resistor
Ground
Input
NOTE: For each terminal connector the inputs and outputs are numbered from left to right.
NOTES: Wiring Distance - Each input can
accept up to 400 ohms of added line resistance.
No specification is given for maximum wire
length.
Use only wire for power limited systems. Power
limited wire runs use type FPLR, FPLP, FPL or
equivalent cabling per NEC 760.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
18 Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
NOTES
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
19
Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
Section 2: NION-16C48M Plug-In Application
2
2.1 Plug-In Selection and Configuration
Plug-In applications are independently operating software applications that are linked to specific NION types. They
interface with the workstation at the network level. Configuration files act to create new menu options by defining
'macro' commands or sequences of information for communicating with specific devices. Configuration files relate
to specific devices, and their options are accessed through device menu options or macro definitions.
Plug-Ins are designed to be configured automatically when the network monitoring system software is installed.
There may be occasions, however, when a plug-in will need to be configured manually. This is done using the
NION Plug-In Application Selection and Configuration form. To configure the 16C48M/48M NION Plug-In,
follow these steps:
1. Select the appropriate 16C48M/48M NION in the NION Type combo box.
NOTE: The related hardware must be installed to utilize the related features provided by the plug-in.
Menu Items/Commands
Available for Current Plug-In
Click Here to Change
Current Linked Plug-In
Figure 2-1: NION Plug-In Selection and Configuration Form
In this example, the device
types listed are pertinent to
the Disable Input command.
Local Area Server and Wide
Area Server are the two
possibilities. If there is a
restriction for the selected
NION, it will be displayed
here.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
20 Document 52004 NION-16C48M Instruction Manual Rev. A 10/10/02
2. Click Change... to modify the current plug-in for the selected device. This will access a file selection
dialog showing the Plugin directory. Select the .CFG or .EXE file associated with the desired plug-in and
click on OK.
3. The commands associated with the selected plug-in will now appear in the Available Icon Menus display.
These are the commands that can now be assigned to a macro function using the Macro Editor, or
assigned to a Functional Button on the Floor Plan Display. These options will automatically appear on
the pulldown menu for the selected device (provided the current workstation has control of the device).
Clicking on an available command will cause the Device Type for Chosen Menu display to show what devices
are affected by the chosen command. Some commands will affect all device types, others will have specific types
only. When creating devices to use plug-in commands be sure they are defined as one of the appropriate types.
When the plug-in has been configured, click OK to close the Plug-In Selection and Configuration Form.
2.2 Mapping Plug-ins With NIONs
In order for plug-in applications to function, they must be linked with the nodes or devices to which they corre-
spond. In most cases this is done automatically, and each recognized node is linked to the appropriate plug-in
application.
There may be times when nodes and devices are not automatically read and updated by the workstation, and links
are not established. Therefore, it is advised that this one-time linking process be checked when assigning new
plug-ins, and if the device type has not been automatically assigned, then assign it manually. This can be done in
the Network Configuration Window. This window is opened by selecting Tools, Network Administration.
Node Site
Panel
Device
Site (w/ No Nodes
or Devices)
Unassigned
Device Type Identified
Device Type
Figure 2-2: Network Configuration Window
NOTE: Plug-ins often have configuration forms for the related NIONs. These configuration tools can only
be accessed from the device pop-up menus. Therefore, before any configuration of the NION can be
done, a device must be assigned to the node.
To obtain information about a specific node, single click on the desired node,
then select Edit, Inquire NION Type From Node, and the NION type will
automatically be displayed. Add Node/Delete Node will add or delete a node
from the list displayed in the window. Select Exit when finished.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Notifier NION-16C48M Fire Alarm System Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI