X-22s™ Users Manual Installation and Connections
See section 4 (Configuration and Setup) to enter slope and offset values into the X-400 controller.
2.4.2 Differential Mode
Differential sensors have two outputs that reference each other instead of ground. The differential mode
uses two analog inputs instead of one.
For example, if Channel 1 is selected for differential operation, the differential signals are connected
to Channel 1 and 2. If Channel 3 is selected for differential operation, the differential signals are
connected to Channel 3 and 4, and so on.
Differential mode supports input ranges of up to ±20.48V. However, the absolute input voltages must be
less than ±10V.
For example, if Input 1 is configured for differential operation and Input1 = +10V and Input2 = -10V,
the measurement will read +20V. On the other hand, if Input1 = -10V and Input2 = +10V, the
measurement will read -20V.
With differential connections, a ground connection is still required between the X-22s and your sensor to
maintain the two input voltages within the common mode voltage range (-10V < Vin < +10V) of the X-
22s.
The illustration below shows the connections for a Wheatstone bridge sensor with two output signals.
The outputs are connected to Ain1 and Ain2. The X-22s must be programmed for differential mode on
“Ain1”. The analog measurement will be made by the voltage difference between the two inputs (Ain1-
Ain2).
For example, if Ain1 is 2.0V and Ain2 is 3.0V, the differential measurement will be -1.0V.
In the illustration below the bridge is excited (driven) by the 5.0V reference output. Notice also that the
bridge provides the necessary input bias.
The low input bias and high resolution inputs of the X-22s together with the reference output make the
X-22s workable with many bridge sensors without using a preamplifier or other circuitry.
2.4.3 Current Sensors (4-20mA Mode)
Some industrial sensors output a current instead of voltage levels. Normally, a shunt resistor is needed
to measure the current. The X-22s contains internal shunt resistors which are automatically switched on
when 4-20mA mode is selected. NO EXTERNAL SHUNT RESISTORS ARE REQUIRED.
Xytronix Research & Design, Inc. Page 11