SKYDANCE DH8 User manual

  • Hello! I've analyzed the user manual for the DALI DH8 Relay Unit. This document details its features, operating modes (DALI, DMX, and manual), and how to configure its 8 independent output channels. It also highlights its compliance with DALI-2 and DMX512 protocols. I'm ready to help with any questions you have about the device.
  • What are the operating modes of the relay unit?
    What is the maximum load current for relay?
    How many output channels does the device have?
    What standards does the device comply with?
DH8
Page 1
2023.7
Mechanical Structures and Installations
User Manual Ver 1.0.0
Technical Parameters
DALI
LVD
Input and Output
Input voltage 100-240VAC
Input current 0.1A
Gross weight
Size
Package
0.422kg
L165 x W98 x H72mm
Safety and EMC
Warranty
5 years
Warranty
EMC standard (EMC) ETSI EN 301 489-1 V2.2.3
ETSI EN 301 489-17 V3.2.4
Certication CE,EMC,LVD
EN 62368-1:2020+A11:2020
Safety standard(LVD)
DALI/DMX8-Channel Relay Unit
Three operating modes: DALI mode, DMX mode and manual mode.
LED segment display and 3 button operation.
Compliant DALI device type 7, , in accordance DALI-2 certified
with DALI standard protocol IEC 62386-101,102, 208 and in compliance
with DALI products from other international incorporation.
DALI address can be manually assigned and shown in digital display or
automatically assigned by DALI master.
Comply with the DMX512 standard protocols, support RDM function.
Support manual switch.
High-inrush specification relays (single pole, normally open).
Zero cross switching function, 8 independently output channels.
Can operate as:
8 individual channels (8 × 1)
4 sets of 2 channels (4 × 2)
2 sets of 4 channels (2 × 4)
DT7 / 8,4,2 DALI address / DMX-RDM / 8-channel dry contact output / Numeric display / Din Rail
DALI and DMX512
Input signal
16A resistive load (incandescent lamp)
8A Capacitive load (LED dimming driver)
8A inductive load (uorescent lamp)
High inrush (120A at 20ms),
single-pole, single-throw (SPST) relay.
Relay
contacts

Operation temperature
Case temperature (Max.)
Environment
IP20
IP rating
Ta: -20
O
C ~ +55
O
C
Tc:
+70
O
C
AC input
DMX signal input
LED indicator
Digital display Setting button
DIN Rail Mounting Size:
TS-35/7.5 or TS-35/15
Installation rack
L
DA1 DA2
GND
DALI IN
K1A K1B K2A K2B K3A K3B K4A K4B K5A K5B K6A K6B K7A K7B K8A K8B
100-240VACIN
Uin
= 100-240VAC
Iin = 0.1A
Out = 8×16A
Temp Range: -20~+55
DH8
DALI/DMX 8-ChannelRelay Unit
1 2
D- D+
DMX IN
PG N
3 4 5 6 7 8
DT7
IEC62386
1#
Relay
2#
Relay
3#
Relay
4#
Relay
5#
Relay
6#
Relay
7#
Relay
8#
Relay
DALI signal input, no need
distinguish plus-minus polarity
GND
D- D+
DMX OUT
DA1 DA2
DMX signal output
Max relay
load current
Full load
loss power Max. 12W
Wiring Diagram
Page 2
2023.7
User Manual Ver 1.0.0
L
DA1 DA2
GND
DALI IN
K1A K1B K2A K2B K3A K3B K4A K4B K5A K5B K6A K6B K7A K7B K8A K8B
100-240VACIN
1 2
D- D+
DMX IN
PG N
3 4 5 6 7 8
DA 1
DA 2
DALI
N
L
E
D+
D- DMX
GND
DA1 DA2
GND
D- D+
DMX OUT
Operation
Work mode setting
Short press M button to switch DALI mode, manual mode and DMX mode.
DALI mode, display “dAxx” or “dUxx”, xx is DALI address.
Manual mode, display “Hxon” or “HxoF”, x is 1-8 channel.
DMX mode, display “Axxx”, xxx is DMX start address.
Channel setting
Long press M and button for 2s, prepare for setup channel.This setting is valid for all three work modes.
Short press or button to switch 8 independent channels(”CH-8"), 4 groups of 2 channels(”CH-4") or 2 groups of 4 channels(”CH-2").
Short press M button or timeout 10s, quit channel setting.
DALI mode
Set start DALI Address via buttons:
Display “dAxx”, xx is start DALI address.
Long press or button for 2s, prepare for setup DALI address.
Short press or button to setup start DALI address.
Short press M button or timeout 10s, quit DALI address setting.
DALI address can also be assigned by DALI Master controller automatically.
Please refer to user manuals of compatible DALI Masters for specic operations.
The digital display will show “dAAU” When the DALI master is assigning address.
After address is assigned, the digital display will show the start DALI address”dAxx”, xx is from 00 to 63.
Using the DALI master to assign addresses may result in discontinuous addresses, and the starting DALI address "dUxx" is displayed.
DALI address assigned by DALI masters:
Manual mode
Display “Hxon” or “HxoF”, x is 1-8 channel, “on” is ON state, “oF” is OFF state.
Short press button to switch channel.
Short press button to switch ON/OFF state.
DMX mode
Set start DMX Address via buttons:
Display “Axxx”, xxx is start DMX address.
Long press or button for 2s, prepare for setup DMX address.
Short press or button to setup start DMX address.
Short press M button or timeout 10s, quit DMX address setting.
(dA00~dA63)
DALI mode
(H1on~H8on)
Manual mode
(A001~A512)
DMX mode
DALI Bus
Power Supply
/