11 Installer Guide
No. Installer Setting Factory Setting Comments
(
Notes follow this table) Default Options (More information follows this table)
11 1stStageFanControl HG FAN 1 HG FAN 1 Selectfor1ststageGasheating
[note 3] HE FAN 1 Selectfor1ststageElectricheating
12 EmergencyHeat] HE EMER HE EMER SelectforElectricEmergencyHeat
FanControl[note 4] HG EMER SelectforGasEmergencyHeat
13 ReversingValve REVO REVO SelectforcoolactiveReversingValve(Oterminal)
(O/BTerminal)[note 5] REVB SelectforheatactiveReversingValve(Bterminal)
14 FossilFuel AE AUX AE AUX SelectforElectricAuxiliaryheat(withcompressor)
BackupHeat[note 4] AG AUX SelectforGasAuxiliaryheat(withoutcompressor)
15
CompressorPowerOutage
oF CPOP oF CPOP DisablesPowerOutageLockoutDelay
Protection [notes 4, 6] on CPOP EnablesPowerOutageLockoutDelay
16 ACPowerInterrupt
AC oF MONR
AC oF MONR DisablesACPowerInterruptWarning
Warning[note 6] AC on MONR EnablesACPowerInterruptWarning
17 CompressorShort 5 CSCP 5, 4, 3, 2or Selectacompressorshortcycleprotectiondelayof5,
CycleProtection 0 CSCP 4,3,2or0minutes
18 ResidualCooling 60 FAN 90, 60, 30 SelectaResidualCoolingFanDelayof90,60,
FanDelay or0 FAN 30or0seconds.
19 CirculatingFanLock oF CIRC oF CIRC DisablesCirculatingFanLockmode
on CIRC EnablesCirculatingFanLockmode
20 AdaptiveRecovery oF REC oF REC DisablesAdaptive(early)Recoverymode
Mode(ARM™) [note 7] on REC EnablesAdaptive(early)Recoverymode
21 IndoorRemoteSensor I SENS I SENS Temperatureissensedfromthermostatonly.
Control*[note 8] E SENS Temperatureissensedfromremotesensoronly.
A SENS Temperatureiscombinedwiththethermostatand
theremotesensor.
22 LockoutSecurityLevel 2 LOCK 2 LOCK Iflocked–Completelockoutisenabled
1 LOCK Iflocked–Partiallockoutisenabled(SpeedBar
®
is
stillfunctional)
23 AutoChangeover 3 BAND 2, 3, 4or5 SelectaDeadBandof2°,3°,4°or5˚F
DeadBand[note 9] BAND (1°,2°or3°C)forAutoChangeovermode.
24 CompressorBalance NO BALC NO BALC DisablesBalancePoints
Point[notes 4, 10] 15-50 BALC SelectaCompressorBalancePointof15°-50°F
(-9°-10°C)
25 AuxiliaryHeatBalance NO BALA NO BALA DisablesBalancePoints
Point[notes 4, 10]
70-40 BALA
SelectaAuxiliaryHeatBalancePointof70°-40°F
(21°-4°C)
26 OutsideAirIntake OA NONE OA NONE DisablesOutsideAirIntakeoption
(ATerminal)[note 11] OA ECON EnablesOutsideAirIntake(EconomizerMode)
OA TOD EnablesOutsideAirIntake(TimeofDayMode)
27
HeatSetPointUpperLimit
90LIM 90-60 LIM
SelectaHeatSetPointUpperLimitof90°-60°F(32°-10°C)
28
CoolSetPointLowerLimit
45LIM 45-80 LIM
SelectaCoolSetPointLowerLimitof45°-80°F(7°-27°C)
*WhenaBraeburn
®
outdoorsensorisconnected,thethermostatautomaticallyrecognizesit.Pressroomtemperaturedigitsto
displayoutdoortemperature.
NOTE: Additional options such as Service Monitors, Setting the lock code, audible tone, etc. are located in the
User Settings – See User manual for information on setting these options.