Robertshaw Braeburn 7300 7305 Thermostat User manual

Category
Thermostats
Type
User manual
Installer Guide
Universal Programmable Smart Wi-Fi Thermostats
1
Specifications
2
Installation and Wiring
3
Quick Reference
4
Installer Settings
5
System Testing
• Possible electric shock or damage to equipment can occur.
• Disconnect power before beginning installation.
Caution
This thermostat requires 24 Volt AC Power or 2 properly installed “AA Alkaline
batteries for
proper operation. If connecting this thermostat to a Wi-Fi network,
a 24 VAC common (C wire) is required.
For use only as described in this manual. Any other use will void warranty.
7300
Single Stage Heat / Cool
Conventional or Heat Pump
7305
Up to 3 Heat / 2 Cool Heat Pump
Up to 2 Heat / 2 Cool Conventional
Warning
For installation by experienced service technicians only.
®
This thermostat is compatible with:
• Singlestageheat/coolconventionalandheatpumpsystems
• Conventionalsystemsupto2stagesofheatingand2stagesofcooling(7305only)
• Heatpumpsystemsupto3stagesofheatingand2stagesofcooling(7305only)
• 2or3wirehydroniczonesystems
Electrical and control specifications:
• ElectricalRating:24VoltAC
• 1ampmaximumloadperterminal
• ACPower:18–30VoltsAC
• DCPower:3.0VoltDC(2“AA”AlkalineBatteriesIncluded)
• ControlRange:45°–90°F(7°–32°C)
• TemperatureAccuracy:+/-1°F(+/-.5°C)
• OutdoorTemperatureDisplayRange:-40°-120°F(-40°-49°C)
Terminations
• 7300:Rc,Rh,W1,C,Y1,K,O/B/V3,G,S2,S1
• 7305:Rc,Rh,W2,W1/E/W3,A,C,L,Y2,Y1,K,O/B/V3,G,S2,S1
1
Specifications
7300-100-02
Model number is located on back of thermostat.
®
See Wi-Fi Setup Guide for Wi-Fi Setup Instructions
“C” Common
Wire Required
for Wi-Fi
Thermostat Location
Installthethermostatapproximately5feet(1.5m)abovetheoorinanareathathasagoodamountofair
circulationandmaintainsanaverageroomtemperature.
Avoidinstallationinlocationswherethethermostatcanbeaffectedbydrafts,deadairspots,hotorcoldair
ducts,sunlight,appliances,concealedpipes,chimneysandoutsidewalls.
Installer Guide 2
Install your new Braeburn thermostat in 4 basic steps:
1 InstalltheSub-Base
2 ProvidePower
3 ConnectYourWires
4 AttachThermostattoSub-Base
Install the Sub-Base:
•Removethesub-basefromthebodyofthethermostat.
•Mountthesub-baseasshownbelow:
Warning
Disconnect power before beginning installation.
2
Installation and Wiring
1
UP
UP
Drill 3/16” pilot holes in your
desired location. Use supplied
anchors for drywall or plaster.
3 Installer Guide
Provide Power
C
24VAC Power Terminal (C)
2
Wiring Terminations for model 7300
Terminal Function Description
 Rc Input 24VoltACCoolingTransformer
(DualTransformerSystemsOnly)
 Rh Input PowerConnection(24VoltAC
HeatingTransformer)
GOutput FanControl
W1Output ConventionalHeatRelay
O/B/V3 Output (O)CoolActiveReversingValve
(B)HeatActiveReversingValve
(V3)ZoneValvePowerClose
Y1 Output CompressorRelay
 C Input 24VoltACTransformerCommon
K - OptionalShare-a-Wire
TM
  moduleconnection
S1
S2
Connect Your Wires
3
Input OptionalRemoteSensor(indoororoutdoor)
+
+
For24VoltACpower,youmustconnectthecommonsideofthetransformertotheCterminalonthethermostat
sub-base.Indualtransformerinstallations,thetransformercommonmustcomefromthecoolingtransformer.
•Forbatterypower,insertthe2supplied“AA”typealkalinebatteriesintothebatterycompartmentlocatedintherear
housingofthethermostat.MakesuretopositionthePositive(+)andNegative(-)sidesofthebatteriescorrectlywith
the+/-symbolsinthebatterycompartment.
• If connecting this thermostat to a Wi-Fi network, a 24 VAC common (C wire) is required.
Batteries Installed as Shown
Installer Guide 4
Wiring Terminations for model 7305
Terminal Function Description
  Rc Input 24VoltACCoolingTransformer
(DualTransformerSystemsOnly)
Rh Input PowerConnection(24VoltAC
HeatingTransformer)
G Output FanControl
W1/E/W3 Output (W1)1stStageConventionalHeat,
  (E)EmergencyHeat,
(W3)3rdStageAuxiliaryHeat
 W2 Output 2ndStageConventionalHeat
O/B/V3 Output (O)CoolActiveReversingValve
(B)HeatActiveReversingValve
(V3)ZoneValvePowerClose
  Y1 Output 1stStageCompressor
  Y2 Output 2ndStageCompressor
  L Input SystemMalfunctionIndicator
  A Output Economizer,FreshAirorOutputControl
C Input 24VoltACTransformerCommon
  K - OptionalShare-a-Wire
TM
  moduleconnection
  S1
  S2
Connecting Your Wires (continued)
3
Input OptionalRemoteSensor(indoororoutdoor)
5 Installer Guide
Heat Only
Set System Type to 11CONV
Rh PowerConnection
W1 HeatRelay
G FanRelay[note 4]
C 24VoltACTransformerCommon[note 1]
1 HEAT / 1 COOL Single or Dual Transformer
Set System Type to 11CONV
Rh
24VoltACPower(heatingtransformer)[note 2]
Rc
24VoltACPower(coolingtransformer)[note 2]
W1 HeatRelay
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
NOTES - Conventional Systems
[1]Optional24VoltACcommonconnection
(requiredforWi-Fi).
[2]Onlyremovefactoryinstalledjumperfordual
transformersystems.
[3]Indualtransformersystems,transformer
commonmustcomefromcoolingtransformer.
[4]Ifneededforsystem.
Provide disconnect and overload protection as required.
2 HEAT / 2 COOL Single or Dual transformer
Set System Type to 22CONV
Rh
24VoltACPower(heatingtransformer)[note 2]
Rc
24VoltACPower(coolingtransformer)[note 2]
W1 HeatRelayStage1
W2 HeatRelayStage2
Y1 CompressorRelayStage1
Y2 CompressorRelayStage2 [note 4]
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
Typical Wiring Congurations
NOTE: The “System Type” option will be configured in the Installer Settings section. The 7300 is a single stage
thermostat and not intended for multi stage equipment.
Conventional Systems
Hydronic Heat Only
Set System Type to 1HD
Rh
24VoltACPower(heatingtransformer)[note 2]
W1 ZoneValvePowerOpen
V3 ZoneValvePowerClose
G FanRelay[note 4]
C 24VoltACTransformerCommon[note 1]
Hydronic Heat / 1 Cool
Set System Type to 11HD
Rh
24VoltACPower(heatingtransformer)[note 2]
Rc
24VoltACPower(coolingtransformer)[note 2]
W1 ZoneValvePowerOpen
V3 ZoneValvePowerClose
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
Installer Guide 6
1 HEAT / 1 COOL - No Auxiliary Heat
Set System Type to 11HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve [note 2]
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon [note 1]
3 HEAT / 2 COOL – Including Auxiliary Heat
Set System Type to 32HP
Rh 24VoltACPower
Rc
ConnectedtoRhwithsuppliedJumperWire
O/B ChangeoverValve [note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
W3
AuxiliaryHeatRelay(3rdstageheating)[note 5]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 1 COOL - Including Auxiliary Heat
Set System Type to 22HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve[note 2]
Y1 CompressorRelay(1ststageheating/cooling)
W2
AuxiliaryHeatRelay(2ndstageheating)[note 3]
E EmergencyHeatRelay[note 3]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 2 COOL - No Auxiliary Heat
Set System Type to 32HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve[note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
NOTES - Heat Pump Systems
[1] Optional24VoltACcommonconnection
(requiredforWi-Fi).
[2]O(coolactive)orB(heatactive)isselectedinthe
InstallerSettingsmenu.
[3] Installaeldsuppliedjumperbetweenthe
W2andW1/E/W3terminalsifthereis
noseparateemergencyheatrelayinstalled.
[4] IftheLterminalisused,the24VoltACcommon
mustbeconnected(Cterminal).
[5] Ifaseparateemergencyheatrelayisinstalled,the
W1/E/W3terminalshouldhaveboththeauxiliary
heat1relayandemergencyheatrelayconnected.
Provide disconnect and overload protection as required.
Typical Wiring Congurations
NOTE: The “System Type” option will be configured in the Installer Settings section. The 7300 is a single
stage thermostat and not intended for multi stage equipment.
Heat Pump Systems
NOTE: Additional options are configured in the
Installer Settings section.
S1
S2
A Economizer,FreshAirorOutputControl
K Share-a-Wire
TM
Module[note 2]
NOTES - Additional Wiring Options
[1]Theseterminalscanbeusedtoconnecta
Braeburn
®
indoororoutdoorremotesensor.
[2]
Canbeusedtoshareawireonexistinginstallations
whereacommonconnection(Cwire)isrequired.
Additional Wiring Options - All System Types
IndoororOutdoorRemoteSensor[note 1]
INSTRUCTIONS
DAY/TIME
7 Installer Guide
NOTE: This thermostat ships congured as a 1H/1C conventional
thermostat. Conrm installer settings. See page 10.
UP
UP
S1
S2
G
Y1
Y2
A
H
L
C
W1/E
/AUX1
W2/
AUX2
W3/
O/B
RH
RC
L
S1
L
S2
G
C
W1/E
/AUX
/AUX
/AUX
/AUX
1
1
1
1
4
Attach Thermostat to Sub-Base
3) InsertQuickReferenceCardintoslot
ontopofthermostat.
1) Lineupthethermostatbodywiththesub-base.
2) Carefullypushthethermostatbodyagainstthe
sub-baseuntilitsnapsinplace.
Installer Guide 8
3
Quick Reference
8
* BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor
congurationmodes,BACKandNEXTappearinthedisplayscreenindicatingthatthePROGand
HOLDbuttonsnowfunctionasBACKandNEXT.
**Alsosee#25onpage9.
BACK NEXT
1
2
3 4
7
8
10
11
12
5
13
14
15
9
Room Temperature...................... Displaysthecurrentroomtemperature
Set Temperature..........................Displaysthecurrentsetpointtemperature
Outdoor Temperature Indicator...Displaysalongwiththeoutdoortemperaturereading**
BACK Indicator*........................... BACKbuttonisactive
NEXT Indicator*............................ NEXTbuttonisactive
Service Indicators ...................... Displaysvariousservice/maintenanceinformation
Fan Indicator................................ Indicateswhenthesystemfanisrunning
Wi-Fi Indicator.............................
IndicateswhenconnectedtoWi-Fi(asheswhenconnectionhasbeenlost)
Low Battery Indicator.................. Indicateswhenthebatteriesneedtobereplaced
Hold Mode Indicator ................... IndicatesifthethermostatisinHOLDmode
Lock Mode Indicator ................... Indicatesifthethermostatislocked
System Status Indicator ............. Displaysinformationaboutthestatusofthesystem
Day of the Week........................... Displaysthecurrentdayoftheweek
Program Event Indicator..............Displaystheprogramevent
Time of Day ................................. Displaysthecurrenttimeofday
1
2
3
4
5
6
7
8
9
10
11
Thermostat Display
12
13
14
15
6
9 Installer Guide
INSTRUCTIONS
DAY/ TIME
BACK NEXT
16
17
24
18 19 20 21
22
23
25
Reset Button ............................... Resetscurrenttime,programandusersettings
SYSTEM Button............................Selectsthesystemyouwanttocontrol
DAY/TIME Button.......................... Setsthecurrenttimeanddayoftheweek
PROG Button................................. Selectsprogrammingmodeorpressfor3secondstoselectSpeedSet
®
BACK Button*...............................SecondaryfunctionofthePROGbutton-movesbackasetting
HOLD Button.................................Enters/ExitstheHOLDmode(programbypass)
NEXT Button*............................... SecondaryfunctionoftheHOLDbutton-movestonextsetting
RETURN Button............................ Returnstonormalmodefromprogramorsettingmodes
FAN Button................................... Selectsthesystemfanmode
Quick Reference Instructions......Storedinslotlocatedattopofthermostat
SpeedBar
®
...................................Increasesordecreasessettings(time,temperature,etc.)
Outdoor Temperature................... IfaBraeburn
®
outdoorsensorwasconnectedyoucanviewtheoutdoor
temperaturebypressingthePROGandHOLDbuttonsatthesametime.
Battery Compartment.................. Locatedinthebackofthermostat
Thermostat
16
17
18
19
20
21
22
23
24
25
* BACKand NEXTaresecondaryfunctionsofthePROGandHOLDbuttons.Wheninprogrammingor
congurationmodes,BACKandNEXTappearinthedisplay,indicatingthatthePROGandHOLDbuttons
nowfunctionasBACKandNEXT.
INSTRUCTIONS
DAY/ TIME
TheInstallerSettingsmustbeproperlyconguredinorderforthisthermostattooperatecorrectly.TheInstaller
Settingsaremenudriven.Theportionofthesesettingsthatdonotapplytoyoursetupwillbeskipped.These
settingsareindicatedbelowwithcomments.Moredetailoneachsettingfollowsthistable.
Installer Guide 10
1. PressandholddowntheRETURNand
buttonsfor3seconds.
2. Releasebothbuttonsandtherstinstaller
settingwillbedisplayed.
3. Changesettingsasrequiredusingthe
orportionoftheSpeedBar
®
.
4. PressNEXT (HOLD)orBACK (PROG)to
movetothenextorprevioussetting,
pressRETURNtoexit.
No. Installer Setting Factory Setting Comments
(Notes follow this table) Default Options (More information follows this table)
1 Residentialor RES RES SelectforResidentialprole
 orCommercialProle COMM SelectforCommercialprole
2 ProgrammingMode 7 PROG 7 PROG Selectfor7dayprogrammingmode
[note 1] 52 PROG Selectfor5-2dayprogrammingmode
NO PROG Selectfornon-programmablemode
3 ClockFormat 12 HR 12 HR Selectfor12hourclock
24 HR Selectfor24hourclock
4 TemperatureScale F DEG F DEG SelectforFahrenheitdisplay
C DEG SelectforCelsiusdisplay
5 AutoChangeover oF AUTO oF AUTO DisablesAutoChangeovermode
ON AUTO EnablesAutoChangeovermode
11CONV Selectfor1H/1CConventionalsystem
22CONV Selectfor2H/2CConventionalsystem
6 SystemType 11CONV 11HP Selectfor1H/1CHeatPumpsystem
22HP Selectfor2H/2CHeatPumpsystem
32HP Selectfor3H/2CHeatPumpsystem
1HD SelectforHeatOnlyHydronicsystem
11HD SelectforHydronicHeat/1Csystem
7 1stStageDifferential 0.5 DIF1 0.5, 1.0or Selecta1ststagetemperaturedifferentialof.5°,
2.0 DIF1 1°or2°F(.25°,.5°or2°C)
8 2ndStageDifferential 2.0 DIF2 1.0, 2.0, 3.0, Selecta2ndstagetemperaturedifferentialof1°,
[note 2] 4.0, 5.0or 2°,3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C)
6.0 DIF2
9 3rdStageDifferential 2.0 DIF3 1.0, 2.0, 3.0, Selecta3rdstagetemperaturedifferentialof1°,2°,
[note 2] 4.0, 5.0or 3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C)
6.0 DIF3
4
Installer Settings
NOTE: Shaded areas below do not apply to the 7300.
INSTRUCTIONS
DAY/ TIME
BACK NEXT
11 Installer Guide
No. Installer Setting Factory Setting Comments
(
Notes follow this table) Default Options (More information follows this table)
10 1stStageFanControl HG FAN 1 HG FAN 1 Selectfor1ststageGasheating
[note 3] HE FAN 1 Selectfor1ststageElectricheating
11 EmergencyHeat HE EMER HE EMER SelectforElectricEmergencyHeat
FanControl[note 4] HG EMER SelectforGasEmergencyHeat
12 ReversingValve REVO REVO SelectforcoolactiveReversingValve(Oterminal)
(O/BTerminal)[note 5] REVB SelectforheatactiveReversingValve(Bterminal)
13 FossilFuel AE AUX AE AUX SelectforElectricAuxiliaryheat(withcompressor)
BackupHeat[note 4] AG AUX SelectforGasAuxiliaryheat(withoutcompressor)
14
CompressorPowerOutage
oF CPOP oF CPOP DisablesPowerOutageLockoutDelay
Protection [notes 4, 6] on CPOP EnablesPowerOutageLockoutDelay
15 ACPowerInterrupt
AC oF MONR
AC oF MONR DisablesACPowerInterruptWarning
Warning[note 6] AC on MONR EnablesACPowerInterruptWarning
16 CompressorShort 5 CSCP 5, 4, 3, 2or Selectacompressorshortcycleprotectiondelayof5,
CycleProtection[note 7] 0 CSCP 4,3,2or0minutes
17 ResidualCooling 60 FAN 90, 60, 30 SelectaResidualCoolingFanDelayof90,60,
FanDelay[note 7] or0 FAN 30or0seconds.
18 CirculatingFanLock oF CIRC oF CIRC DisablesCirculatingFanLockmode
on CIRC EnablesCirculatingFanLockmode
19 AdaptiveRecovery oF REC oF REC DisablesAdaptive(early)Recoverymode
Mode(ARM™) [note 8] on REC EnablesAdaptive(early)Recoverymode
20 IndoorRemoteSensor I SENS I SENS Temperatureissensedfromthermostatonly.
Control*[note 9] E SENS Temperatureissensedfromremotesensoronly.
A SENS Temperatureiscombinedwiththethermostatand
theremotesensor.
21 LockoutSecurityLevel 2 LOCK 2 LOCK Iflocked–Completelockoutisenabled
1 LOCK Iflocked–Partiallockoutisenabled(SpeedBar
®
is
stillfunctional)
22 AutoChangeover 3 BAND 2, 3, 4or5 SelectaDeadBandof2°,3°,4°or5˚F
DeadBand[note 10] BAND (1°,2°or3°C)forAutoChangeovermode.
23 CompressorBalance NO BALC NO BALC DisablesBalancePoints
Point[notes 4, 11] 0-50 BALC SelectaCompressorBalancePointof0°-50°F
(-9°-10°C)
24 AuxiliaryHeatBalance NO BALA NO BALA DisablesBalancePoints
Point[notes 4, 11]
70-40 BALA
SelectaAuxiliaryHeatBalancePointof70°-40°F
(21°-4°C)
25 EconomizerFreshAiror OA NONE OA NONE DisablesFreshAirIntakeoption
OutputControl[note 12] OA ECON EnablesFreshAirIntake(EconomizerMode)
OA TOD EnablesFreshAirIntake(TimeofDayMode)
26
HeatSetPointUpperLimit
90LIM 90-60 LIM
SelectaHeatSetPointUpperLimitof90°-60°F(32°-10°C)
27
CoolSetPointLowerLimit
45LIM 45-80 LIM
SelectaCoolSetPointLowerLimitof45°-80°F(7°-27°C)
[note 7]
28 InstallerClear CLR0 CLR0 ClearOff-Nochangesmadetosettings
CLR2 Clearsallthermostatsettings(factorydefaults)
*WhenaBraeburn
®
outdoorsensorisconnected,thethermostatautomaticallyrecognizesit.PressPROGandHOLDatthesame
timetodisplayoutdoortemperature.
NOTE: Additional options such as Service Monitors, setting the lock code, etc. are located in the User Settings –
See User manual for information on setting these options.
Installer Guide 12
NOTES - Installer Settings
1 OnlyavailableifResidentialprolewasselectedinoption1.
2 Onlyavailableifa2or3stagesystemtypewasselectedinoption6.
3 OnlyavailableifaConventionalsystemwasselectedinoption6.
4 Onlyavailableifa2or3stageHeatPumpsystemwasselectedinoption6.
5 OnlyavailableifaHeatPumpsystemwasselectedinoption6.
6 Onlyavailableifthe24VoltACcommonwireisconnectedtotheCterminal.
7 Notavailableifaheatonlyhydronicsystemisselectedinoption6.
8 Onlyavailableifaprogrammableprolewasselectedinoption2.
9 OnlyavailableifaBraeburn®indoorremotesensorwasconnected.
10 Onlyavailableifautochangeoverwasenabledinoption5.
11 OnlyavailableifaBraeburnoutdoorsensorwasconnected.
12 OnlyavailableifaCommercialprolewasselectedinoption1.
Detailed Explanation of Installer Settings (also see NOTES above):
1 Profile–Selectsaresidential(RES)orcommercial(COMM)prole.Ifresidentialisselected,4programming
eventsperdayareavailable.Ifcommercialisselected,2event,7dayprogrammingisavailable.
2 Programming Mode [note 1]–Selectstheprogrammingmode,eitherfull7dayor5-2day(weekday/
weekend)programmingornon-programmable.
3 Clock Type–Selectseithera12houror24hourclock.
4 Temperature Scale–Selectsatemperaturescaleofeither°For°C.
5 Auto Changeover–Selectsautochangeoveronoroff.Whenautochangeovermodeisenabledand
selected,thesystemautomaticallyswitchesbetweenheatingandcoolingmodes.Thereisa5minutedelay
whenswitchingfromheatingtocoolingorcoolingtoheatinginautochangeovermode.
NOTE: Also see “Auto Changeover Dead Band” in option 21.
6 System Type–Selectsthesystemtypeforyourinstallation.NOTE: Changes made to this option will reset
options 7 through 15 back to their default values dependant on the system type.
7 1st Stage Differential–Selectsa1ststagetemperaturedifferential.
8 2nd Stage Differential [note 2]–Selectsa2ndstagetemperaturedifferential.
9 3rd Stage Differential [note 2]–Selectsa3rdstagetemperaturedifferential.
10 1st Stage Fan Control [note 3]–Selectsa1ststagefancontrolofeithergasorelectricheat.
11 Emergency Heat Fan Control [note 4]–Selectsemergencyheatfancontrolofeithergasorelectricheat.
12 Reversing Valve [note 5]–SelectstheoutputstateoftheO/Bterminal.SelectOforthisterminaltobe
activeinthecoolmodeorselectBforthisterminaltobeactiveintheheatmode.
13 Auxiliary Fossil Fuel Heat Pump Control [note 4]–Whensettoelectric(AEAUX),boththecompressor
(1ststage)andauxiliarystage(s)willrunwhenacallforauxiliaryheatismade.Whensettogas(AGAUX),
thecompressorstage(s)willbelockedoutoneminuteafteracallforauxiliaryheat.NOTE: This option can
be overridden if setting an auxiliary heat balance point in Option 23.
14 Compressor Power Outage Protection [notes 4, 6]–Selectspoweroutageprotectiononoroff.When
enabled,thisthermostatwillprovidecoldweathercompressorprotectionbylockingoutthecompressor
stage(s)ofheatingforaperiodoftimeafterapoweroutagegreaterthan60minutes.
15 AC Power Interrupt Warning [note 6]–Whenenabled,thethermostatwilldisplayanoutagewarning
whenACpowertothethermostatislost.
13 Installer Guide
16 Short Cycle Protection [note 7]–Selectsthenumberofminutesthecoolingcompressorwillbelocked
outafterturningoff.Thisshortcycleprotectionisalsoactiveintheheatmodeifaheatpumpsystemwas
selectedinOption6.
17 Residual Cooling Fan Delay [note 7]–
Selectsadelayforthesystemfanafterthecoolingcompressorhas
turnedoff.Thisdelaywillhelpremovetheremainingcoolairoutoftheductworkprovidingadditionalefciency.
18 Circulating Fan Lock–Whenenabled,theonlyuserfanoptionsavailableareONandCIRC(Circulation).
TheAUTOoptionisnotavailablewiththisoptionenabled.
19 Adaptive Recovery Mode (early recovery) [note 8]–EnablesordisablestheARM
TM
(adaptiverecovery
mode)feature.DuringARM,roomtemperatureisrecoveredbyturningontheheatingorcoolingbeforethe
endofthesetbackperiod.Thesetpointtemperatureischangedtothatoftheupcomingprogramtemperature.
20 Indoor Remote Sensor Control [note 9]–IfaBraeburn
®
indoorremotesensorisconnectedduring
installation,thethermostatwillautomaticallydetectthesensor.Whenanindoorsensorisdetected,youmay
selectbetweenthermostatonly(ISENS),remotesensoronly(ESENS)orcombiningthethermostatandthe
remotesensor(ASENS).NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor
sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.
21 Lockout Security Level–Selectsthelevelofkeypadlockoutwhenthethermostatislocked.Level2locks
theentirethermostat(includingthefrontresetbutton).Level1lockseverythingexcepttheSpeedBar
®
allowingforupanddowntemperatureadjustment.NOTE: The lock code is set in the User Settings mode
(see User Manual).
22 Auto Changeover Dead Band [note 10]–Whenautochangeovermodeisenabledinoption5and
selected,thesystemautomaticallyswitchesbetweenheatingandcoolingwhentheroomtemperature
meetsthenormalcriteriaforeitheraheatingorcoolingcall.Thereisaforcedseparation(deadband)
betweentheheatingandcoolingsetpointssothatthesystemsdonotworkagainsteachother.This
optionselectstheamountofthisdeadbandindegreeswiththedefaultbeing3°F.
23 Compressor Balance Point [notes 4, 11]–Locksouttheuseofthecompressorheatstagewhenthe
outsideairtemperatureislessthantheselectedsettingof15°Fto50°F(-9°Cto10°C)
24 Auxiliary Heat Balance Point [notes 4, 11]–Locksouttheuseoftheauxiliaryheatstagewhenthe
outsideairtemperatureexceedstheselectedsettingof70°Fto40°F(21°Cto4°C).NOTE: This balance
point overrides the fossil fuel compressor lockout in option 13. If this option is set to gas and the outdoor
temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
Continued
Installer Guide 14
26 Heat Set Point Upper Limit–Selectstheheatingsetpointupperadjustmentlimit.
27 Cool Set Point Lower Limit [note 7] –Selectsthecoolingsetpointloweradjustmentlimit.
28 Installer Clear–Clearssettingsbasedonyourselection.CLROmakesnochangesandCLR2clearsALL
thermostatsettingstofactorydefault.
WARNING:IfyoupressNEXTorRETURNafterselectingCLR2theclearwilltakeplaceandtheappropriate
settingswillbereturnedtofactorydefaults.Ifyoudonotwishtomakeanychanges,usetheSpeedBar
®
to
selectCLRO.
Time Step / Override Cooling Call
Occupied YES or NO ON ON OFF
YES ON OFF OFF
NO OFF OFF OFF
Override YES or NO ON ON OFF
External Air or Output Control (A)
Economizer Time of Disabled
Mode Day Mode
Time Step / Override Heating Call
Occupied YES or NO ON ON OFF
YES OFF OFF OFF
NO OFF OFF OFF
Override YES or NO ON ON OFF
External Air Output (A)
Economizer Time of Disabled
Mode Day Mode
Unoccupied
Unoccupied
25 Economizer, Fresh Air or Output Control [note 12]–Selectscontroloptions.Selectbetweendisabled
(NONE),economizermode(ECON)andtimeofday(TOD)mode.
ThisequipmenthasbeentestedandfoundtocomplywiththelimitsforaClassBdigitaldevice,pursuanttoPart15oftheFCCRules.Theselimits
aredesignedtoprovidereasonableprotectionagainstharmfulinterferenceinaresidentialinstallation.Thisequipmentgeneratesusesandcanradiate
radiofrequencyenergyand,ifnotinstalledandusedinaccordancewiththeinstructions,maycauseharmfulinterferencetoradiocommunications.
However,thereisnoguaranteethatinterferencewillnotoccurinaparticularinstallation.Ifthisequipmentdoescauseharmfulinterferencetoradio
ortelevisionreception,whichcanbedeterminedbyturningtheequipmentoffandon,theuserisencouragedtotrytocorrecttheinterferencebyone
ormoreofthefollowingmeasures:
•Reorientorrelocatethereceivingantenna.
•Increasetheseparationbetweentheequipmentandreceiver.
•Connecttheequipmentintoanoutletonacircuitdifferentfromthattowhichthereceiverisconnected.
•Consultthedealeroranexperiencedradio/TVtechnicianforhelp.
Changesormodicationsnotexpresslyapprovedbythepartyresponsibleforcompliancecouldvoidtheuser’sauthoritytooperatetheequipment.
Thisdevicecomplieswithpart15oftheFCCRules.Operationissubjecttothefollowingtwoconditions:(1)Thisdevicemaynotcauseharmful
inter
ference,and(2)thisdevicemustacceptanyinterferencereceived,includinginterferencethatmaycauseundesiredoperation.
ThisdevicecomplieswithIndustryCanada’slicence-exemptRSSs.Operationissubjecttothefollowingtwoconditions:
(1)Thisdevicemaynotcauseinterference;and
(2)Thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesiredoperationofthedevice.
CetappareilestconformeauxCNRexemptsdelicenced’IndustrieCanada.Sonfonctionnementestsoumisauxdeuxconditionssuivantes:
(1)Cedispositifnepeutcauserdesinterférences;et
(2)Cedispositifdoitacceptertouteinterférence,ycomprislesinterférencesquipeuventcauserunmauvaisfonctionnementdel’appareil.
MPEG LA License Agreement
THISPRODUCTISLICENSEDUNDERTHEWIRELESSNETWORKPATENTPORTFOLIOLICENSEFORUSEBYACONSUMEROROTHERUSESFORWHICH
THEREISNOREMUNERATION.ANYOTHERUSEOFTHISPRODUCTINANYMANNERISNOTLICENSEDANDISEXPRESSLYPROHIBITEDWITHOUTA
LICENSEUNDERAPPLICABLEPATENTSINTHEWIRELESSNETWORKPATENTPORTFOLIO,WHICHLICENSEISAVAILABLEFROMMPEGLA,LLC,4600S.
ULSTERST.,SUITE400,DENVER,COLORADO80237U.S.A.SEEHTTP://WWW.MPEGLA.COM.
PleaseNote:Thisthermostatmayhavebeenupdatedovertheinternetsincethismanualwasprinted.
Alwaysrefertothesupportwebsiteforthelatestinformation.
15 Installer Guide
Warning
Read Before Testing
• Donotshort(orjumper)acrossterminalsonthegasvalveorattheheatingorcoolingsystemcontrolboard
totestthethermostatinstallation.Thiscoulddamagethethermostatandvoidthewarranty.
• DonotselecttheCOOLmodeofoperationiftheoutsidetemperatureisbelow50ºF(10ºC).Thiscould
possiblydamagethecontrolledcoolingsystemandmaycausepersonalinjury.
• Thisthermostatincludesanautomaticcompressorprotectionfeaturetoavoidpotentialdamagetothe
compressorfromshortcycling.Whentestingthesystem,makesuretotakethisdelayintoaccount.
NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat.
All user settings will be returned to factory default, however all Installer settings will remain as originally
programmed in section 4.
1 PresstheSYSTEMbuttonuntilthethermostatisinHEATmode.
2 UsingtheSpeedBar®raisethesettemperatureaminimumof3degreesabovethecurrentroom
temperature.Thesystemshouldstartwithinafewseconds.Withagasheatingsystem,thefanmay
notstartrightaway.
3 PressSYSTEMuntilthethermostatisintheOFFmode.Allowtheheatingsystemtofullyshutdown.
4 PressSYSTEMuntilthethermostatisintheCOOLmode.
5 UsingtheSpeedBarlowerthesettemperatureaminimumof3degreesbelowthecurrentroom
temperature.Thesystemshouldstartwithinafewseconds(unlesscompressorshortcycleprotection
isactive–Seenoteabove).
6 PressSYSTEMuntilthethermostatisintheOFFmode.Allowthecoolingsystemtofullyshutdown.
7 PressFANuntilthethermostatisinFANONmode.Thesystemfanshouldstartwithinafewseconds.
8 PressFANuntilthethermostatisinFANAUTOmode.Allowthesystemfantoturnoff.
5
System Testing
Limited Warranty
Wheninstalledbyaprofessionalcontractor,thisproductisbackedbya5yearlimited
warranty.Limitationsapply.Forlimitations,termsandconditions,youmayobtainafull
copyofthiswarranty:
·Visitusonline:www.braeburnonline.com/warranty
·Phoneus:866.268.5599
·Writeus: BraeburnSystemsLLC
2215CornellAvenue
Montgomery,IL60538
5
YEAR
WARRANT Y
LIMITED
BraeburnSystemsLLC
2215CornellAvenue•Montgomery,IL60538
TechnicalAssistance:www.braeburnonline.com
Callustoll-free:866-268-5599(U.S.)
630-844-1968(OutsidetheU.S.)
©2016BraeburnSystemsLLC•AllRightsReserved•MadeinChina.
®
7300-100-02
Store this manual for futur
e reference.
Foradditionalinformationvisit:www.braeburnonline.com
Foronlineaccessvisit:www.bluelinksmartconnect.com
®
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16