Robertshaw 5320 User manual

Category
Thermostats
Type
User manual

This manual is also suitable for

Detailed
Installer Guide
Programmable Touchscreen Thermostats
1
Specifications
2
Installation and Wiring
3
Quick Reference
4
Installer Settings
5
System Testing
To prevent damage to the thermostat, never use a sharp instrument
to press the touchscreen keys. Always press keys with your fingers.
Attention
• Possible electric shock or damage to equipment can occur.
• Disconnect power before beginning installation.
Caution
This thermostat requires 24 Volt AC Power or 2 properly installed “AAAlkaline
batteries for
proper operation. When connecting 24 Volt AC Power the batteries may
be installed as a backup.
For use only as described in this manual. Any other use will void warranty.
5310
Single Stage Heat / Cool Conventional
or Heat Pump
5320
Up to 4 Heat / 2 Cool Heat Pump
Up to 3 Heat / 2 Cool Conventional
Warning
For installation by experienced service technicians only.
Touchscreen
®
®
This thermostat is compatible with:
• Singlestageheat/coolconventionalandheatpumpsystems
• Conventionalsystemsupto3stagesofheatingand2stagesofcooling(5320only)
• Heatpumpsystemsupto4stagesofheatingand2stagesofcooling(5320only)
• 250–750millivoltheatingonlysystems
Electrical and control specifications:
• ElectricalRating:24VoltAC
• 1ampmaximumloadperterminal
• ACPower:18–30VoltsAC
• DCPower:3.0VoltDC(2“AAAlkalineBatteriesIncluded)
• ControlRange:45°–90°F(7°–32°C)
• TemperatureAccuracy:+/-1°F(+/-.5°C)
• OutdoorTemperatureDisplayRange:-40°-120°F(-40°-49°C)
Terminations
• 5310:G,Rc,Rh,W1,O/B,Y1,C,S1,S2
• 5320:A,G,Rc,Rh,W1/E/AUX1,W2/AUX2,W3/O/B,Y1,Y2,C,L,S1,S2
1
Specifications
5310W-100-04
Model number is located on back of thermostat.
Thermostat Location
Installthethermostatapproximately5feet(1.5m)abovetheoorinanareathathasagoodamountofair
circulationandmaintainsanaverageroomtemperature.
Avoidinstallationinlocationswherethethermostatcanbeaffectedbydrafts,deadairspots,hotorcoldair
ducts,sunlight,appliances,concealedpipes,chimneysandoutsidewalls.
Installer Guide 2
Install your new Braeburn thermostat in 4 basic steps:
1 InstalltheSub-Base
2 ProvidePower
3 ConnectYourWires
4 AttachThermostattoSub-Base
Install the Sub-Base:
•Removethesub-basefromthebodyofthethermostat.
•Mountthesub-baseasshownbelow:
Warning
Disconnect power before beginning installation.
2
Installation and Wiring
1
UP
UP
Drill 3/16” pilot holes in your
desired location. Use supplied
anchors for drywall or plaster.
3 Installer Guide
Provide Power
C
24VAC Power Terminal (C)
2
Wiring Terminations for model 5310
Terminal Function Description
G Output FanControl
 Rc Input 24VoltACCoolingTransformer
(DualTransformerSystemsOnly)
 Rh Input PowerConnection(24VoltACHeating
TransformerorMillivoltPowerSource)
W1 Output ConventionalHeatRelay
O/B Output ReversingValve(CoolActiveorHeatActive)
Y1 Output CompressorRelay
C Input 24VoltACTransformerCommon
S1
S2
Connect Your Wires
3
Input OptionalRemoteSensor(indoororoutdoor)
+
+
For24VoltACpower,youmustconnectthecommonsideofthetransformertotheCterminalonthethermostatsub-base.In
dualtransformerinstallations,thetransformercommonmustcomefromthecoolingtransformer.
• Forbatterypower,insertthe2supplied“AA”typealkalinebatteriesintothebatterycompartmentlocatedintherear
housingofthethermostat.MakesuretopositionthePositive(+)andNegative(-)sidesofthebatteriescorrectlywith
the+/-symbolsinthebatterycompartment.
Batteries Installed as Shown
Installer Guide 4
Wiring Terminations for model 5320
Terminal Function Description
A Output EconomizerControl
G Output FanControl
  Rc Input 24VoltACCoolingTransformer
(DualTransformerSystemsOnly)
Rh Input PowerConnection(24VoltACHeating
TransformerorMillivoltPowerSource)
W1/E/ Output (W1)1stStageConventionalHeat,
 AUX1 (E)EmergencyHeat,
(AUX1)1stStageAuxiliaryHeat
W2/AUX2 Output (W2)2ndStageConventionalHeat,
(AUX2)2ndStageAuxHeat
W3/O/B Output (W3)3rdStageConventionalHeat,
(O)CoolActiveReversingValve
(B)HeatActiveReversingValve
  Y1 Output 1stStageCompressor
  Y2 Output 2ndStageCompressor
  C Input 24VoltACTransformerCommon
  L Input SystemMalfunctionIndicator
  S1
  S2
Connecting Your Wires (continued)
3
Input OptionalRemoteSensor(indoororoutdoor)
5 Installer Guide
1 HEAT / 1 COOL Single or Dual Transformer
Set System Type to 11CONV
Rh
24VoltACPower(heatingtransformer)[note 2]
Rc
24VoltACPower(coolingtransformer)[note 2]
W1 HeatRelay
Y1 CompressorRelay
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
NOTES - Conventional Systems
[1]Optional24VoltACcommonconnection.
[2]Removefactoryinstalledjumperfordual
transformersystems.Providedisconnectand
overloadprotectionasrequired.
[3]Indualtransformersystems,transformer
commonmustcomefromcoolingtransformer.
[4]Ifneededforsystem.
Provide disconnect and overload protection as required.
3 HEAT / 2 COOL Single or Dual Transformer
Set System Type to 32CONV
Rh
24VoltACPower(heatingtransformer)[note 2]
Rc
24VoltACPower(coolingtransformer)[note 2]
W1 HeatRelayStage1
W2 HeatRelayStage2
W3 HeatRelayStage3
Y1 CompressorRelayStage1
Y2 CompressorRelayStage2 [note 4]
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
2 HEAT / 2 COOL Single or Dual transformer
Set System Type to 22CONV
Rh
24VoltACPower(heatingtransformer)[note 2]
Rc
24VoltACPower(coolingtransformer)[note 2]
W1 HeatRelayStage1
W2 HeatRelayStage2
Y1 CompressorRelayStage1
Y2 CompressorRelayStage2 [note 4]
G FanRelay
C 24VoltACTransformerCommon[note 1, 3]
Typical Wiring Configurations
NOTE: The “System Type” option will be configured in the Installer Settings section. The 5310 is a single stage
thermostat and not intended for multi stage equipment.
Conventional Systems
NOTE: Additional options are configured in the
Installer Settings section.
S1
S2
A EconomizerControl(5320only)[note 2]
NOTES - Additional Wiring Options
[1]Theseterminalscanbeusedtoconnecta
Braeburn
®
indoororoutdoorremotesensor.
[2]
Thisterminalcanbeusedforeconomizer
control(5320).
Additional Wiring Options
IndoororOutdoorRemoteSensor[note 1]
Heat Only or Millivolt
Set System Type to 11CONV
Rh PowerConnection
W1 HeatRelay
G FanRelay[note 4]
C 24VoltACTransformerCommon[note 1]
Installer Guide 6
1 HEAT / 1 COOL - No Auxiliary Heat
Set System Type to 11HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve [note 2]
Y1 CompressorRelay(appearsasYonthe5310)
G FanRelay
C 24VoltACTransformerCommon [note 1]
3 HEAT / 2 COOL – Including Auxiliary Heat
Set System Type to 32HP
Rh 24VoltACPower
Rc
ConnectedtoRhwithsuppliedJumperWire
O/B ChangeoverValve [note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
AUX1
AuxiliaryHeatRelay(3rdstageheating)[note 5]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 1 COOL - Including Auxiliary Heat
Set System Type to 22HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve[note 2]
Y1 CompressorRelay(1ststageheating/cooling)
W2
AuxiliaryHeatRelay(2ndstageheating)[note 3]
E EmergencyHeatRelay[note 3]
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
2 HEAT / 2 COOL - No Auxiliary Heat
Set System Type to 32HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B
ChangeoverValve[note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
4 HEAT / 2 COOL - Including Auxiliary Heat
Set System Type to 42HP
Rh 24VoltACPower
Rc ConnectedtoRhwithsuppliedJumperWire
O/B ChangeoverValve[note 2]
Y1
Compressor1Relay(1ststageheating/cooling)
Y2
Compressor2Relay(2ndstageheating/cooling)
AUX1
AuxiliaryHeatRelay1(3rdstageheating)[note 5]
AUX2
AuxiliaryHeatRelay2Relay(4thstageheating)
G FanRelay
C 24VoltACTransformerCommon[note 1]
L OptionalSystemFaultMonitor[note 4]
NOTES - Heat Pump Systems
[1] Optional24VoltACcommonconnection.
[2] O(coolactive)orB(heatactive)isselectedin
theInstallerSettingsmenu.
[3] Installaeldsuppliedjumperbetweenthe
W2/AUX2andW1/E/AUX1terminalsifthereis
noseparateemergencyheatrelayinstalled.
[4] IftheLterminalisused,the24VoltACcommon
mustbeconnected(Cterminal).
[5] Ifaseparateemergencyheatrelayisinstalled,the
W1/E/AUX1terminalshouldhaveboththeauxiliary
heat1relayandemergencyheatrelayconnected.
Provide disconnect and overload protection as required.
Typical Wiring Configurations
NOTE: The “System Type” option will be configured in the Installer Settings section. The 5310 is a single
stage thermostat and not intended for multi stage equipment.
Heat Pump Systems
7 Installer Guide
NOTE: This thermostat ships configured as a 1H/1C conventional
thermostat. Confirm installer settings. See page 10.
UP
UP
S1
S2
G
Y1
Y2
A
H
L
C
W1/E
/AUX1
W2/
AUX2
W3/
O/B
RH
RC
C
W1/E
/
AUX
1
S2
G
4
Attach Thermostat to Sub-Base
3) InsertQuickReferenceCardintoslot
ontopofthermostat.
1) Lineupthethermostatbodywiththesub-base.
2) Carefullypushthethermostatbodyagainstthe
sub-baseuntilitsnapsinplace.
NOTE: Additional options are configured in the
Installer Settings section.
S1
S2
A EconomizerControl(5320only)[note 2]
NOTES - Additional Wiring Options
[1]Theseterminalscanbeusedtoconnecta
Braeburn
®
indoororoutdoorremotesensor.
[2]
Thisterminalcanbeusedforeconomizer
control(5320).
Additional Wiring Options
IndoororOutdoorRemoteSensor[note 1]
Installer Guide 8
Room Temperature...................... Displaysthecurrentroomtemperature
Lock Mode Indicator ................... Indicatesifthethermostatislocked
Set Temperature.......................... Displaysthecurrentsetpointtemperature
Service Indicators ...................... Displaysvariousservice/maintenanceinformation
Time of Day .................................Displaysthecurrenttimeofday
Program Event Indicator.............. Displaystheprogramevent
Day of the Week........................... Displaysthecurrentdayoftheweek
System Status Indicator ............. Displaysinformationaboutthestatusofthesystem
Hold Mode Indicator ................... IndicatesifthethermostatisinHOLDmode
Fan Indicator................................ Indicateswhenthesystemfanisrunning
Low Battery Indicator.................. Indicateswhenthebatteriesneedtobereplaced
Quick Reference Instructions...... Storedinslotlocatedattopofthermostat
SpeedBar
®
...................................Increasesordecreasessettings(time,temperature,etc.)
Reset Button ...............................Resetscurrenttime,programandusersettings
Battery Compartment ................. Locatedinthebackofthermostat
3
Quick Reference
1
2
3
10
4
14
6
5
7
13
8
9
11
12
1
2
3
4
5
6
7
8
9
10
11
Thermostat Display
12
13
14
Thermostat
9 Installer Guide
Thermostat TouchPads
NOTE: Thermostat TouchPads are located on the left, right and bottom portions of the display screen. They are
the “touch sensitive” segments used to adjust your thermostat. Depending on the equipment installed, all touch
pads may not show.
SYSTEM......SelectsAUTO(Heat/Cool),COOL,OFFHEATorEMER(EmergencyHeat)
FAN.............SelectsAUTO,ON,CIRC(Circulation)andPROG(Program)fanmodes
PROG..........Selectsprogrammingmodeorpressfor3secondstoselectSpeedSet
®
mode
HOLD..........Enters/ExitstheHOLDmode(programbypass)
DAY/TIME...Setsthecurrenttimeanddayoftheweek
BACK..........Movesbackinsettingandprogrammingmodes
NEXT...........Movesforwardinsettingandprogrammingmodes
RETURN......Returnstonormalmodefromprogramorsettingsmodes
CONFIG.......EnterstheUserandInstallersettingsmodes
CLEAN........Entersabriefscreencleaningmode
Outdoor Temperature
IfaBraeburn
®
outdoortemperaturesensorwasconnected,youmaytouchtheroomtemperatureareaofthe
screentoviewtheoutdoortemperature.
TheInstallerSettingsmustbeproperlyconguredinorderforthisthermostattooperatecorrectly.TheInstaller
Settingsaremenudriven.Theportionofthesesettingsthatdonotapplytoyoursetupwillbeskipped.These
settingsareindicatedbelowwithcomments.Moredetailoneachsettingfollowsthistable.
Installer Guide 10
1. TouchandholddowntheSYSTEMandCONFIGTouchPadsfor3seconds.
2. Releasebothbuttonsandtherstinstallersettingwillbedisplayed.
3. ChangesettingsasrequiredusingtheUPorDOWNportionoftheSpeedBar
®
.
4. TouchNEXTorBACKtomovetothenextorprevioussetting,touchRETURNtoexit.
NOTE: Shaded areas below do not apply to the 5310.
No. Installer Setting Factory Setting Comments
(Notes follow this table) Default Options (More information follows this table)
1 Residentialor RES RES SelectforResidentialprole
 orCommercialProle COMM SelectforCommercialprole
2 ProgrammingMode 7 PROG 7 PROG Selectfor7dayprogrammingmode
[note 1] 52 PROG Selectfor5-2dayprogrammingmode
NO PROG Selectfornon-programmablemode
3 ClockFormat 12 HR 12 HR Selectfor12hourclock
24 HR Selectfor24hourclock
4 TemperatureScale F DEG F DEG SelectforFahrenheitdisplay
C DEG SelectforCelsiusdisplay
5 AutoChangeover oF AUTO oF AUTO DisablesAutoChangeovermode
ON AUTO EnablesAutoChangeovermode
11CONV Selectfor1H/1CConventionalsystem
22CONV Selectfor2H/2CConventionalsystem
32CONV Selectfor3H/2CConventionalsystem
6 SystemType 11CONV 11HP Selectfor1H/1CHeatPumpsystem
22HP Selectfor2H/2CHeatPumpsystem
32HP Selectfor3H/2CHeatPumpsystem
42HP Selectfor4H/2CHeatPumpsystem
7 1stStageDifferential 0.5 DIF1 0.5, 1.0or Selecta1ststagetemperaturedifferentialof.5°,
2.0 DIF1 1°or2°F(.25°,.5°or2°C)
8 2ndStageDifferential 2.0 DIF2 1.0, 2.0, 3.0, Selecta2ndstagetemperaturedifferentialof1°,
[note 2] 4.0, 5.0or 2°,3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C)
6.0 DIF2
9 3rdStageDifferential 2.0 DIF3 1.0, 2.0, 3.0, Selecta3rdstagetemperaturedifferentialof1°,2°,
[note 2] 4.0, 5.0or 3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C)
6.0 DIF3
10 4thStageDifferential 2.0 DIF4 1.0, 2.0, 3.0,
Selecta4thstagetemperaturedifferentialof1˚,
[note 2] 4.0, 5.0or 2°,3°,4°,5°or6°F(.5°,1°,1.5°,2°,2.5°or3°C)
6.0 DIF4
4
Installer Settings
11 Installer Guide
No. Installer Setting Factory Setting Comments
(
Notes follow this table) Default Options (More information follows this table)
11 1stStageFanControl HG FAN 1 HG FAN 1 Selectfor1ststageGasheating
[note 3] HE FAN 1 Selectfor1ststageElectricheating
12 EmergencyHeat] HE EMER HE EMER SelectforElectricEmergencyHeat
FanControl[note 4] HG EMER SelectforGasEmergencyHeat
13 ReversingValve REVO REVO SelectforcoolactiveReversingValve(Oterminal)
(O/BTerminal)[note 5] REVB SelectforheatactiveReversingValve(Bterminal)
14 FossilFuel AE AUX AE AUX SelectforElectricAuxiliaryheat(withcompressor)
BackupHeat[note 4] AG AUX SelectforGasAuxiliaryheat(withoutcompressor)
15
CompressorPowerOutage
oF CPOP oF CPOP DisablesPowerOutageLockoutDelay
Protection [notes 4, 6] on CPOP EnablesPowerOutageLockoutDelay
16 ACPowerInterrupt
AC oF MONR
AC oF MONR DisablesACPowerInterruptWarning
Warning[note 6] AC on MONR EnablesACPowerInterruptWarning
17 CompressorShort 5 CSCP 5, 4, 3, 2or Selectacompressorshortcycleprotectiondelayof5,
CycleProtection 0 CSCP 4,3,2or0minutes
18 ResidualCooling 60 FAN 90, 60, 30 SelectaResidualCoolingFanDelayof90,60,
FanDelay or0 FAN 30or0seconds.
19 CirculatingFanLock oF CIRC oF CIRC DisablesCirculatingFanLockmode
on CIRC EnablesCirculatingFanLockmode
20 AdaptiveRecovery oF REC oF REC DisablesAdaptive(early)Recoverymode
Mode(ARM™) [note 7] on REC EnablesAdaptive(early)Recoverymode
21 IndoorRemoteSensor I SENS I SENS Temperatureissensedfromthermostatonly.
Control*[note 8] E SENS Temperatureissensedfromremotesensoronly.
A SENS Temperatureiscombinedwiththethermostatand
theremotesensor.
22 LockoutSecurityLevel 2 LOCK 2 LOCK Iflocked–Completelockoutisenabled
1 LOCK Iflocked–Partiallockoutisenabled(SpeedBar
®
is
stillfunctional)
23 AutoChangeover 3 BAND 2, 3, 4or5 SelectaDeadBandof2°,3°,4°or5˚F
DeadBand[note 9] BAND (1°,2°or3°C)forAutoChangeovermode.
24 CompressorBalance NO BALC NO BALC DisablesBalancePoints
Point[notes 4, 10] 15-50 BALC SelectaCompressorBalancePointof15°-50°F
(-9°-10°C)
25 AuxiliaryHeatBalance NO BALA NO BALA DisablesBalancePoints
Point[notes 4, 10]
70-40 BALA
SelectaAuxiliaryHeatBalancePointof70°-40°F
(21°-4°C)
26 OutsideAirIntake OA NONE OA NONE DisablesOutsideAirIntakeoption
(ATerminal)[note 11] OA ECON EnablesOutsideAirIntake(EconomizerMode)
OA TOD EnablesOutsideAirIntake(TimeofDayMode)
27
HeatSetPointUpperLimit
90LIM 90-60 LIM
SelectaHeatSetPointUpperLimitof90°-60°F(32°-10°C)
28
CoolSetPointLowerLimit
45LIM 45-80 LIM
SelectaCoolSetPointLowerLimitof45°-80°F(7°-27°C)
*WhenaBraeburn
®
outdoorsensorisconnected,thethermostatautomaticallyrecognizesit.Pressroomtemperaturedigitsto
displayoutdoortemperature.
NOTE: Additional options such as Service Monitors, Setting the lock code, audible tone, etc. are located in the
User Settings – See User manual for information on setting these options.
Installer Guide 12
NOTES - Installer Settings
1 OnlyavailableifResidentialprolewasselectedinoption1.
2 Onlyavailableifa2,3or4stagesystemtypewasselectedinoption6.
3 OnlyavailableifaConventionalsystemwasselectedinoption6.
4 Onlyavailableifa2,3or4stageHeatPumpsystemwasselectedinoption6.
5 OnlyavailableifaHeatPumpsystemwasselectedinoption6.
6 Onlyavailableifthe24VoltACcommonwireisconnectedtotheCterminal.
7 Onlyavailableifaprogrammableprolewasselectedinoption2.
8 OnlyavailableifaBraeburn®indoorremotesensorwasconnected.
9 Onlyavailableifautochangeoverwasenabledinoption5.
10 OnlyavailableifaBraeburnoutdoorsensorwasconnected.
11 OnlyavailableifCommercialprolewasselectedinoption1.
Detailed Explanation of Installer Settings (also see NOTES above):
1 Profile–Selectsaresidential(RES)orcommercial(COMM)prole.Ifresidentialisselected,4programming
eventsperdayareavailable.Ifcommercialisselected,2event,7dayprogrammingisavailable.
2 Programming Mode [note 1]–Selectstheprogrammingmode,eitherfull7dayor5-2day(weekday/
weekend)programmingornon-programmable.
3 Clock Type–Selectseithera12houror24hourclock.
4 Temperature Scale–Selectsatemperaturescaleofeither°For°C.
5 Auto Changeover–Selectsautochangeoveronoroff.Whenautochangeovermodeisenabledand
selected,thesystemautomaticallyswitchesbetweenheatingandcoolingmodes.Thereisa5minutedelay
whenswitchingfromheatingtocoolingorcoolingtoheatinginautochangeovermode.
NOTE: Also see “Auto Changeover Dead Band” in option 23.
6 System Type–Selectsthesystemtypeforyourinstallation.NOTE: Changes made to this option will reset
options 7 through 15 back to their default values dependant on the system type.
7 1st Stage Differential–Selectsa1ststagetemperaturedifferential.
8 2nd Stage Differential [note 2]–Selectsa2ndstagetemperaturedifferential.
9 3rd Stage Differential [note 2]–Selectsa3rdstagetemperaturedifferential.
10 4th Stage Differential [note 2]–Selectsa4thstagetemperaturedifferential.
11 1st Stage Fan Control [note 3]–Selectsa1ststagefancontrolofeithergasorelectricheat.
12 Emergency Heat Fan Control [note 4]–Selectsemergencyheatfancontrolofeithergasorelectricheat.
13 Reversing Valve [note 5]–SelectstheoutputstateoftheO/Bterminal.SelectOforthisterminaltobe
activeinthecoolmodeorselectBforthisterminaltobeactiveintheheatmode.
14 Auxiliary Fossil Fuel Heat Pump Control [note 4]–Whensettoelectric(AEAUX),boththecompressor
(1ststage)andauxiliarystage(s)willrunwhenacallforauxiliaryheatismade.Whensettogas(AGAUX),
thecompressorstage(s)willbelockedoutoneminuteafteracallforauxiliaryheat.NOTE: This option can
be overridden if setting an auxiliary heat balance point in Option 25.
15 Compressor Power Outage Protection [notes 4, 6]–Selectspoweroutageprotectiononoroff.When
enabled,thisthermostatwillprovidecoldweathercompressorprotectionbylockingoutthecompressor
stage(s)ofheatingforaperiodoftimeafterapoweroutagegreaterthan60minutes.
13 Installer Guide
16 AC Power Interrupt Warning [note 6]–Whenenabled,thethermostatwilldisplayanoutagewarning
whenACpowertothethermostatislost.
17 Short Cycle Protection–Selectsthenumberofminutesthecoolingcompressorwillbelockedoutafter
turningoff.Thisshortcycleprotectionisalsoactiveintheheatmodeifaheatpumpsystemwasselectedin
Option6.
18 Residual Cooling Fan Delay–Selectsadelayforthesystemfanafterthecoolingcompressorhasturned
off.Thisdelaywillhelpremovetheremainingcoolairoutoftheductworkprovidingadditionalefciency.
19 Circulating Fan Lock–Whenenabled,theonlyuserfanoptionsavailableareONandCIRC(Circulation).
TheAUTOoptionisnotavailablewiththisoptionenabled.
20 Adaptive Recovery Mode (early recovery) [note 7]–EnablesordisablestheARM
TM
(adaptiverecovery
mode)feature.DuringARM,roomtemperatureisrecoveredbyturningontheheatingorcoolingbeforethe
endofthesetbackperiod.Thesetpointtemperatureischangedtothatoftheupcomingprogramtemperature.
21 Indoor Remote Sensor Control [note 8]–IfaBraeburn
®
indoorremotesensorisconnectedduring
installation,thethermostatwillautomaticallydetectthesensor.Whenanindoorsensorisdetected,youmay
selectbetweenthermostatonly(ISENS),remotesensoronly(ESENS)orcombiningthethermostatandthe
remotesensor(ASENS).NOTE: This option does not apply to a Braeburn outdoor sensor. When an outdoor
sensor is connected the thermostat automatically recognizes it and no further configuration is necessary.
22 Lockout Security Level–Selectsthelevelofkeypadlockoutwhenthethermostatislocked.Level2locks
theentirethermostat(includingthefrontresetbutton).Level1lockseverythingexcepttheSpeedBar
®
allowingforupanddowntemperatureadjustment.NOTE: The lock code is set in the User Settings mode
(see User Manual).
23 Auto Changeover Dead Band [note 9]–Whenautochangeovermodeisenabledinoption5and
selected,thesystemautomaticallyswitchesbetweenheatingandcoolingwhentheroomtemperature
meetsthenormalcriteriaforeitheraheatingorcoolingcall.Thereisaforcedseparation(deadband)
betweentheheatingandcoolingsetpointssothatthesystemsdonotworkagainsteachother.This
optionselectstheamountofthisdeadbandindegreeswiththedefaultbeing3°F.
24 Compressor Balance Point [notes 4, 10]–Locksouttheuseofthecompressorheatstagewhenthe
outsideairtemperatureislessthantheselectedsettingof15°Fto50°F(-9°Cto10°C)
25 Auxiliary Heat Balance Point [notes 4, 10]–Locksouttheuseoftheauxiliaryheatstagewhenthe
outsideairtemperatureexceedstheselectedsettingof70°Fto40°F(21°Cto4°C).NOTE: This balance
point overrides the fossil fuel compressor lockout in option 14. If this option is set to gas and the outdoor
temperature is over the auxiliary balance point, the compressor will remain on during a call for auxiliary heat.
Installer Guide 14
26 Outside Air Intake [note 11]–Selectseconomizercontroloptions.Selectbetweendisabled(NONE),
economizermode(ECON)andtimeofday(TOD)mode.
Time Step / Override Cooling Call
Occupied YES or NO ON ON OFF
YES ON OFF OFF
NO OFF OFF OFF
Override YES or NO ON ON OFF
External Air Output (A)
Economizer Time of Disabled
Mode Day Mode
Time Step / Override Heating Call
Occupied YES or NO ON ON OFF
YES OFF OFF OFF
NO OFF OFF OFF
Override YES or NO ON ON OFF
External Air Output (A)
Economizer Time of Disabled
Mode Day Mode
Unoccupied
Unoccupied
27 Heat Set Point Upper Limit–Selectstheheatingsetpointupperadjustmentlimit.
28 Cool Set Point Lower Limit–Selectsthecoolingsetpointloweradjustmentlimit.
15 Installer Guide
Warning
Read Before Testing
• Donotshort(orjumper)acrossterminalsonthegasvalveorattheheatingorcoolingsystemcontrolboard
totestthethermostatinstallation.Thiscoulddamagethethermostatandvoidthewarranty.
• DonotselecttheCOOLmodeofoperationiftheoutsidetemperatureisbelow50ºF(10ºC).Thiscould
possiblydamagethecontrolledcoolingsystemandmaycausepersonalinjury.
• Thisthermostatincludesanautomaticcompressorprotectionfeaturetoavoidpotentialdamagetothe
compressorfromshortcycling.Whentestingthesystem,makesuretotakethisdelayintoaccount.
NOTE: The compressor delay can be bypassed by pressing the reset button on the front of the thermostat.
All user settings will be returned to factory default, however all Installer settings will remain as originally
programmed in section 4.
1 TouchtheSYSTEMTouchPaduntilthethermostatisinHEATmode.
2 UsingtheSpeedBar®raisethesettemperatureaminimumof3degreesabovethecurrentroom
temperature.Thesystemshouldstartwithinafewseconds.Withagasheatingsystem,thefanmay
notstartrightaway.
3 TouchSYSTEMuntilthethermostatisintheOFFmode.Allowtheheatingsystemtofullyshutdown.
4 TouchSYSTEMuntilthethermostatisintheCOOLmode.
5 UsingtheSpeedBarlowerthesettemperatureaminimumof3degreesbelowthecurrentroom
temperature.Thesystemshouldstartwithinafewseconds(unlesscompressorshortcycleprotection
isactive–Seenoteabove).
6 TouchSYSTEMuntilthethermostatisintheOFFmode.Allowthecoolingsystemtofullyshutdown.
7 TouchFANuntilthethermostatisinFANONmode.Thesystemfanshouldstartwithinafewseconds.
8 TouchFANuntilthethermostatisinFANAUTOmode.Allowthesystemfantoturnoff.
9 Ifthethermostatiscontrollingauxiliaryequipmentsuchasaneconomizer(5320only),etc.,adjustthe
thermostatsettingstotestthesedevices.
5
System Testing
®
Store this manual for future reference.
Limited Warranty
Wheninstalledbyaprofessionalcontractor,thisproductisbackedbya5yearlimited
warranty.Limitationsapply.Forlimitations,termsandconditions,youmayobtainafull
copyofthiswarranty:
·Visitusonline:www.braeburnonline.com/warranty
·Phoneus:866.268.5599
·Writeus:BraeburnSystemsLLC
2215CornellAvenue
Montgomery,IL60538
5
YEAR
WARRANT
Y
LIMITED
BraeburnSystemsLLC
2215CornellAvenue•Montgomery,IL60538
TechnicalAssistance:www.braeburnonline.com
Callustoll-free:866-268-5599(U.S.)
630-844-1968(OutsidetheU.S.)
©2014BraeburnSystemsLLC•AllRightsReserved•MadeinChina.
®
5310W-100-04
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16

Robertshaw 5320 User manual

Category
Thermostats
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI