Trane RTAF HSE Series Installation Operation & Maintenance

Category
Split-system air conditioners
Type
Installation Operation & Maintenance

This manual is also suitable for

RLC-SVX19A-E4
RTAF SE/HE/XE/HSE
Air-cooled
Helical-rotary chillers
300 - 750kW
Installation
Operation
Maintenance
Table of Contents
RLC-SVX19A-E4
2
© 2014 Trane
Introduction ....................................................................................................... 4
Unit Model Number Description ..................................................................... 6
General Data ...................................................................................................... 8
Operating Map: Condenser Airside ...............................................................15
Installation Requirements ..............................................................................16
Dimensional Data ............................................................................................ 19
Chilled Water Piping Recommendations .......................................................21
Evaporator Piping ............................................................................................22
Integrated Pump Package (Optional) ............................................................ 26
Evaporator Waterside ...................................................................................... 30
General Electrical Recommendations ........................................................... 35
Installer-Supplied Components ..................................................................... 41
Alarm and Status Relay Outputs (Programmable Relays) .......................... 42
EDLS and ECWS Analog Input Signal Wiring Details .................................. 42
Operating Principles ....................................................................................... 43
Controls ........................................................................................................... 45
Tracer TD7 Operator Interface ........................................................................ 45
Pre-Start Checkout ......................................................................................... 46
Unit Start Up Procedures ...............................................................................48
Periodic Maintenance .....................................................................................50
Condenser Coils MCHE Maintenance ............................................................56
Integrated Pump Maintenance (Optional with Pump Package) .................. 57
Log Check Sheet ............................................................................................. 58
RLC-SVX19A-E4
3
RLC-SVX19A-E4
4
Introduction
Foreword
These instructions are given as a guide to good practice
in the installation, start-up, operation, and maintenance
by the user, of Trane RTAF chillers, manufactured in
France. A separate manual is available for the use and
maintenance of the unit’s control, Tracer™ UC800. They
do not contain full service procedures necessary for the
continued successful operation of this equipment. The
services of a qualifi ed technician should be employed
through the medium of a maintenance contract with a
reputable service company. Read this manual thoroughly
before unit start-up.
Units are assembled, pressure tested, dehydrated,
charged and run tested before shipment.
Warnings and Cautions
Warnings and Cautions appear at appropriate sections
throughout this manual. Your personal safety and the
proper operation of this machine require that you follow
them carefully. The constructor assumes no liability
for installations or servicing performed by unqualifi ed
personnel.
WARNING: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
CAUTION: Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe
practices or for equipment or property-damage-only
accidents.
Safety Recommendations
To avoid death, injury, equipment or property damage,
the following recommendations should be observed
during maintenance and service visits:
1. The maximum allowable pressures for system leak
testing on low and high pressure side are given in
the chapter “Installation”. Always provide a pressure
regulator.
2. Disconnect the main power supply before any
servicing on the unit.
3. Service work on the refrigeration system and the
electrical system should be carried out only by qualifi ed
and experienced personnel.
Reception
On arrival, inspect the unit before signing the delivery
note.
Reception in France only:
In case of visible damage: The consignee (or the site
representative) must specify any damage on the delivery
note, legibly sign and date the delivery note, and the
truck driver must countersign it. The consignee (or the
site representative) must notify Trane Epinal Operations.
- Claims team and send a copy of the delivery note.
The customer (or the site representative) should send
a registered letter to the last carrier within 3 days of
delivery.
Note: For deliveries in France, even concealed damage
must be looked for at delivery and immediately treated
as visible damage.
Reception in all countries except France:
In case of concealed damage: The consignee (or the
site representative) must send a registered letter to the
last carrier within 7 days of delivery, claiming for the
described damage. A copy of this letter must be sent to
Trane Epinal Operations - Claims team.
Warranty
Warranty is based on the general terms and conditions
of the manufacturer. The warranty is void if the
equipment is repaired or modifi ed without the written
approval of the manufacturer, if the operating limits are
exceeded or if the control system or the electrical wiring
is modifi ed. Damage due to misuse, lack of maintenance
or failure to comply with the manufacturers instructions
or recommendations is not covered by the warranty
obligation. If the user does not conform to the rules of
this manual, it may entail cancellation of warranty and
liabilities by the manufacturer.
RLC-SVX19A-E4
5
Unit Description
The Sintesis RTAF units are helical-rotary type, air-cooled
chillers designed for outdoor installation. The refrigerant
circuits are factory-piped, leak tested and dehydrated.
Every unit is electrically tested for proper control
operation before shipment.
Chilled water inlet and outlet openings are covered
for shipment. The Sintesis RTAF features Tranes
exclusive Adaptive Control™ logic, which monitors
the control variables that govern the operation of the
chiller unit. Adaptive control logic can adjust capacity
variables to avoid chiller shutdown when necessary,
and keep producing chilled water. The units feature two
independent refrigerant circuits. On the HSE version
each compressor is controlled by a dedicated variable
speed Adaptive Frequency Drive. Each refrigerant circuit
is provided with fi lter, sight glass, electronic expansion
valve, and charging valves. The shell-and-tube CHIL™
(Compact-High performance-Integrated design-Low
charge) evaporator is manufactured in accordance with
the Pressure Equipment Directive (PED) code. Each
evaporator is fully insulated and equipped with water
drain and vent connection.
Units are shipped with full oil and refrigerant charge.
Loose Parts Inventory
Check all the accessories and loose parts that are
shipped with the unit against the shipping list. Included
in these items will be the water vessel drain plugs,
rigging and electrical diagrams, service literature, which
are placed inside the control panel and/or starter panel
for shipment.
If optional elastomeric isolators are ordered with the
unit (model number digit 42 =1) they are shipped
mounted on the horizontal support frame of the chiller.
The isolators’ location and distribution weight diagram
is placed with the service literature inside the starter/
control panel.
Introduction
RLC-SVX19A-E4
6
Digit 1, 2, 3, 4 – Unit model
RTAF = Air-Cooled Chiller
Digit 5, 6, 7 – Unit size
090 = 090 Tons
105 = 105 Tons
125 = 125 Tons
145 = 145 Tons
155 = 155 Tons
175 = 175 Tons
190 = 190 Tons
205 = 205 Tons
Digit 8 – Unit voltage
D = 400V/50Hz/3ph
Digit 9 – Manufacturing Location
E = Europe
Digit 10,11 – Design sequence
A0 = Factory assigned
Digit 12 – Effi ciency level
N = Standard Effi ciency (SE)
H = High Effi ciency (HE)
A = eXtra Effi ciency (XE)
V = High Seasonal Effi ciency (HSE)
Digit 13 – Agency listing
C = CE Marking
U = UL Certifi ed
Digit 14 – Pressure vessel code
2 = PED (Pressure equipment directive)
Digit 15 – Acoustic level
X = Standard noise (SN)
L = Low noise (LN)
Q = Low Noise with Night Noise SetBack (NNSB)
E = Extra Low Noise (XLN)
Digit 16 – Operating map : airside
X = Standard ambient
L = Low ambient
H = High ambient
Digit 17 – Relief valve option
L = Single relief valve high & low Pressure side
D = Dual relief valve with 3 way valve high pressure &
low pressure side
Digit 18 – Water connection
X = Grooved pipe connection
W = Grooved pipe with coupling and pipe stub
Digit 19 – Operating map water side
N = Comfort cooling (above 4.4°C)
P = Process cooling (below 4.4°C)
C = Ice Making (-7°C to 20°C)
Digit 20 – Evaporator Confi guration
2 = Two pass evaporator
T = Two pass evaporator with turbulators
Digit 21 – Thermal Insulation
N = Standard
H = High performance
X = None
Digit 22 – Condenser coating
N = Aluminum micro channel
C = E-Coated Micro channel
Digit 23 – Open for future use = X
Digit 24 – Hydraulic module
X = Pump signal On/Off
1 = Dual pump standard pressure
3 = Dual pump high pressure
Digit 25 – Open for future use = X
Digit 26 – Disconnect switch
F = With Fuse
B = With circuit breaker
Digit 27 – Under/over Voltage
X = None
1 = Included
2 = Included with ground fault protection
Digit 28 – Human Interface language
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
M = Swedish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
2 = Romanian
6 = Hungarian
8 = Turkish
Digit 29 – Smart com protocol
X = None
B = Bacnet interface
M = Modbus interface
L = LonTalk interface
Digit 30 – Communication customer
X = None
A = External set point & capacity outputs
Digit 31 – Flow switch
X = None
F = Field installed fl ow switch
Unit Model Number Description
RLC-SVX19A-E4
7
Digit 32 – Electrical IP protection
X = Enclosure with Dead Front protection
1 = Enclosure with IP20 internal protection
Digit 33 – Open for future use = X
Digit 34 – Open for future use = X
Digit 35 – Open for future use = X
Digit 36 – Open for future use = X
Digit 37 – Open for future use = X
Digit 38 – Open for future use = X
Digit 39 – Open for future use = X
Digit 40 – Power socket
X = None
P = Included (230V - 100W)
Digit 41 – Factory Test
X = None
B = Visual Inspection with Customer attendance
E = Performance Test without Customer attendance
Digit 42 – Installation accessory
X = None
1 = Neoprene Isolators
4 = Neoprene pads
Digit 43 – Literature language
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
M = Swedish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
2 = Romanian
6 = Hungarian
8 = Turkish
Digit 44 – Shipping package
X = Standard protection
A = Containerization package
Digit 45 – Open for future use = X
Digit 46 – Open for future use = X
Digit 47 – Open for future use = X
Digit 48 – Design special
Unit Model Number Description
RLC-SVX19A-E4
8
General Data
RTAF Standard Ef ciency - Standard and Low Noise RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF
090 105 125 145 155 175 190 205
Eurovent Performances SE SN&LN SE SN&LN SE SN&LN SE SN&LN SE SN&LN SE SN&LN SE SN&LN SE SN&LN
Net Cooling Capacity (3) (4) (kW) 326 375 440 522 564 615 675 732
Power Input (5) (kW) 104 121 146 165 184 206 221 244
EER (3) (4) (6) (kW/kW) 3.14 3.10 3.02 3.16 3.06 2.98 3.05 3.00
ESEER (6) (kW/kW) 3.86 3.86 3.94 3.91 3.84 3.95 3.92 3.92
Eurovent Ef ciency class Cooling AB BA B BB B
Sound power level (Standard Noise) (10) (dBA) 95 95 95 96 96 97 97 97
Sound power level (Low Noise) (10) (dBA) 92 92 92 93 93 94 94 94
Middle East design condition performances (7)
Gross cooling capacity (tons) 77 88 103 124 133 145 160 172
Gross EER (kW/ton) 1.5 1.5 1.6 1.5 1.5 1.6 1.5 1.6
MEW (Kuwait) rating point performances (8)
Gross cooling capacity (tons) 73 84 97 117 125 135 150 162
Gross EER (kW/ton) 1.6 1.7 1.7 1.6 1.7 1.7 1.7 1.7
Table 1 – General Data RTAF 090 – 205 Standard Effi ciency - Standard and Low Noise
Compressor
Quantity # 22222222
Nominal Size (1) tons 45/45 50/50 70/50 70/70 85/70 100/70 100/85 100/100
Evaporator
Evaporator Model 115B 115A 165B 165B 165A 200B 200B 250C
Water Storage l 51 58 74 74 78 99 99 109
Two pass Evaporator
Minimum Flow l/s 8.0 9.4 11.6 11.6 12.4 14.2 14.2 16.2
Maximum Flow l/s 29.6 34.7 43.1 43.1 46.0 52.6 52.6 60.3
Two pass Evaporator – with Turbulators
Minimum Flow l/s 6.6 7.8 9.7 9.7 10.3 11.8 11.8 13.5
Maximum Flow l/s 26.6 31.2 38.7 38.7 41.3 47.2 47.2 54.1
Condenser
Quantity of Coils # 4/4 4/4 4/4 5/5 5/5 6/4 6/6 6/6
Coil Length mm 1967 1967 1967 1967 1967 1967 1967 1967
Coil Height mm 1214 1214 1214 1214 1214 1214 1214 1214
Condenser Fans
Quantity (1) # 4/4 4/4 4/4 5/5 5/5 6/4 6/6 6/6
Diameter mm 800 800 800 800 800 800 800 800
Total Air Flow m
3
/s 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Nominal RPM rpm 932 932 932 932 932 932 932 932
Motor kW 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
Minimum Starting/Operating Ambient
Standard Unit °C -10 -10 -10 -10 -10 -10 -10 -10
Low-Ambient Unit (Option) °C -20 -20 -20 -20 -20 -20 -20 -20
Maximum ambient operation
Standard ambient (9)
°C 46 46 46 46 46 46 46 46
Maximum ambient operation
High ambient (9)
°C 55 55 55 55 55 55 55 55
General Unit
Refrigerant HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a
Number of Independent
Refrigerant Circuits # 22222222
Minimum Load (2) % 15 15 15 15 15 15 15 15
Operating Weight kg 3295 3315 3495 3990 4260 4405 4880 4995
Shipping Weight kg 3236 3247 3409 3904 4170 4290 4765 4868
R134a refrigerant charge
Circuit1/Circuit 2
(kg) 38/38 36/36 40/39 44/43 47/42 57/48 58/55 66/63
Oil charge Circuit1/Circuit 2 (l) 6/6 6/6 6/6 6/6 7/6 7/6 7/7 8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.
RLC-SVX19A-E4
9
General Data
RTAF Standard Ef ciency - eXtra Low Noise RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF
090 105 125 145 155 175 190 205
Eurovent Performances SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN SE XLN
Net Cooling Capacity (3) (4) (kW) 326 376 440 522 564 616 676 732
Power Input (5) (kW) 101 119 143 162 181 203 217 240
EER (3) (4) (6) (kW/kW) 3.23 3.17 3.08 3.22 3.12 3.03 3.11 3.05
ESEER (6) (kW/kW) 4.13 4.07 4.06 4.12 4.02 4.08 4.04 4.01
Eurovent Ef ciency class Cooling AA BA A BA B
Sound power level (eXtra Low Noise) (10) (dBA) 88 89 89 89 90 90 91 91
Middle East design condition performances (7)
Gross cooling capacity (tons) 77 88 103 124 133 145 160 172
Gross EER (kW/ton) 1.5 1.5 1.6 1.5 1.5 1.6 1.5 1.6
MEW (Kuwait) rating point performances (8)
Gross cooling capacity (tons) 73 84 97 117 125 135 150 162
Gross EER (kW/ton) 1.6 1.7 1.7 1.6 1.7 1.7 1.7 1.7
Table 2 – General Data RTAF 090 – 205 Standard Effi ciency - Extra Low Noise
Compressor
Quantity # 22222222
Nominal Size (1) tons 45/45 50/50 70/50 70/70 85/70 100/70 100/85 100/100
Evaporator
Evaporator Model 115B 115A 165B 165B 165A 200B 200B 250C
Water Storage l 51 58 74 74 78 99 99 109
Two pass Evaporator
Minimum Flow l/s 8.0 9.4 11.6 11.6 12.4 14.2 14.2 16.2
Maximum Flow l/s 29.6 34.7 43.1 43.1 46.0 52.6 52.6 60.3
Two pass Evaporator – with Turbulators
Minimum Flow l/s 6.6 7.8 9.7 9.7 10.3 11.8 11.8 13.5
Maximum Flow l/s 26.6 31.2 38.7 38.7 41.3 47.2 47.2 54.1
Condenser
Quantity of Coils # 4/4 4/4 4/4 5/5 5/5 6/4 6/6 6/6
Coil Length mm 1967 1967 1967 1967 1967 1967 1967 1967
Coil Height mm 1214 1214 1214 1214 1214 1214 1214 1214
Condenser Fans
Quantity (1) # 4/4 4/4 4/4 5/5 5/5 6/4 6/6 6/6
Diameter mm 800 800 800 800 800 800 800 800
Total Air Flow m
3
/s 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Nominal RPM rpm 860 860 860 860 860 860 860 860
Motor kW 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
Minimum Starting/Operating Ambient
Standard Unit °C -10 -10 -10 -10 -10 -10 -10 -10
Low-Ambient Unit (Option) °C -20 -20 -20 -20 -20 -20 -20 -20
Maximum ambient operation
Standard ambient (9)
°C 46 46 46 46 46 46 46 46
Maximum ambient operation
High ambient (9)
°C 55 55 55 55 55 55 55 55
General Unit
Refrigerant HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a
Number of Independent
Refrigerant Circuits # 22222222
Minimum Load (2) % 15 15 15 15 15 15 15 15
Operating Weight kg 3375 3395 3575 4090 4360 4505 5000 5115
Shipping Weight kg 3316 3327 3489 4004 4270 4390 4885 4988
R134a refrigerant charge
Circuit1/Circuit 2
(kg) 38/38 36/36 40/39 44/43 47/42 57/48 58/55 66/63
Oil charge Circuit1/Circuit 2 (l) 6/6 6/6 6/6 6/6 7/6 7/6 7/7 8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.
RLC-SVX19A-E4
10
General Data
RTAF High Ef ciency - Standard and Low Noise RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF
090 105 125 145 155 175 190 205
Eurovent Performances HE SN&LN HE SN&LN HE SN&LN HE SN&LN HE SN&LN HE SN&LN HE SN&LN HE SN&LN
Net Cooling Capacity (3) (4) (kW) 326 375 440 522 564 615 675 732
Power Input (5) (kW) 105 121 143 164 181 201 217 239
EER (3) (4) (6) (kW/kW) 3.14 3.10 3.02 3.16 3.06 2.98 3.05 3.00
ESEER (6) (kW/kW) 3.86 3.86 3.94 3.91 3.84 3.95 3.92 3.92
Eurovent Ef ciency class Cooling AB BA B BB B
Sound power level (Standard Noise) (10) (dBA) 95 95 95 96 96 97 97 97
Sound power level (Low Noise) (10) (dBA) 92 92 92 93 93 94 94 94
Middle East design condition performances (7)
Gross cooling capacity (tons) 79 91 107 127 137 150 164 178
Gross EER (kW/ton) 1.5 1.5 1.5 1.4 1.5 1.5 1.5 1.5
MEW (Kuwait) rating point performances (8)
Gross cooling capacity (tons) 76 87 102 121 130 142 155 168
Gross EER (kW/ton) 1.5 1.6 1.6 1.5 1.6 1.6 1.6 1.6
Table 3 – General Data RTAF 090 – 205 High Effi ciency - Standard and Low Noise
Compressor
Quantity # 22222222
Nominal Size (1) tons 45/45 50/50 70/50 70/70 85/70 100/70 100/85 100/100
Evaporator
Evaporator Model 11<5B 115A 165B 165B 165A 200B 200B 250B
Water Storage l 51 58 74 74 78 99 99 118
Two pass Evaporator
Minimum Flow l/s 8.0 9.4 11.6 11.6 12.4 14.2 14.2 17.9
Maximum Flow l/s 29.6 34.7 43.1 43.1 46.0 52.6 52.6 66.5
Two pass Evaporator – With Turbulators
Minimum Flow l/s 6.6 7.8 9.7 9.7 10.3 11.8 11.8 14.9
Maximum Flow l/s 26.6 31.2 38.7 38.7 41.3 47.2 47.2 59.7
Condenser
Quantity of Coils # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Coil Length mm 1967 1967 1967 1967 1967 1967 1967 1967
Coil Height mm 1214 1214 1214 1214 1214 1214 1214 1214
Condenser Fans
Quantity (1) # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Diameter mm 800 800 800 800 800 800 800 800
Total Air Flow m
3
/s 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Nominal RPM rpm 932 932 932 932 932 932 932 932
Motor kW 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
Minimum Starting/Operating Ambient
Standard Unit °C -10 -10 -10 -10 -10 -10 -10 -10
Low-Ambient Unit (Option) °C -20 -20 -20 -20 -20 -20 -20 -20
Maximum ambient operation
Standard ambient (9)
°C 46 46 46 46 46 46 46 46
Maximum ambient operation
High ambient (9)
°C 55 55 55 55 55 55 55 55
General Unit
Refrigerant HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a
Number of Independent
Refrigerant Circuits # 22222222
Minimum Load (2) % 15 15 15 15 15 15 15 15
Operating Weight kg 3605 3625 3800 4310 4580 4730 5180 5295
Shipping Weight kg 3546 3557 3714 4224 4490 4615 5065 5168
R134a refrigerant charge
Circuit1/Circuit 2
(kg) 42/41 40/39 44/43 46/45 50/44 61/52 62/59 67/65
Oil charge Circuit1/Circuit 2 (l) 6/6 6/6 6/6 6/6 7/6 7/6 7/7 8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.
RLC-SVX19A-E4
11
General Data
RTAF eXtra Ef ciency - Standard and Low Noise RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF
090 105 125 145 155 175 190 205
Eurovent Performances XE SN&LN XE SN&LN XE SN&LN XE SN&LN XE SN&LN XE SN&LN XE SN&LN XE SN&LN
Net Cooling Capacity (3) (4) (kW) 326 380 447 526 569 633 690 752
Power Input (5) (kW) 97 116 138 158 177 199 215 236
EER (3) (4) (6) (kW/kW) 3.35 3.28 3.23 3.32 3.23 3.18 3.21 3.19
ESEER (6) (kW/kW) 4.26 4.14 4.19 4.27 4.17 4.15 4.11 4.11
Eurovent Ef ciency class Cooling AA AA A AA A
Sound power level (Standard Noise) (10) (dBA) 94 94 95 96 97 97 98 98
Sound power level (Low Noise) (10) (dBA) 91 91 92 93 94 94 95 95
Middle East design condition performances (7)
Gross cooling capacity (tons) 77 90 105 125 135 150 164 178
Gross EER (kW/ton) 1.4 1.4 1.5 1.4 1.5 1.5 1.5 1.5
MEW (Kuwait) rating point performances (8)
Gross cooling capacity (tons) 74 86 100 119 127 142 156 168
Gross EER (kW/ton) 1.5 1.5 1.6 1.5 1.6 1.6 1.6 1.6
Table 4 – General Data RTAF 090 – 205 Extra Effi ciency - Standard and Low Noise
Compressor
Quantity # 22222222
Nominal Size (1) tons 45/45 50/50 70/50 70/70 85/70 100/70 100/85 100/100
Evaporator
Evaporator Model 115B 115A 165B 165B 165A 200B 200B 250B
Water Storage l 51 58 74 74 78 99 99 118
Two pass Evaporator
Minimum Flow l/s 8.0 9.4 11.6 11.6 12.4 14.2 14.2 17.9
Maximum Flow l/s 29.6 34.7 43.1 43.1 46.0 52.6 52.6 66.5
Two pass Evaporator – With Turbulators
Minimum Flow l/s 6.6 7.8 9.7 9.7 10.3 11.8 11.8 14.9
Maximum Flow l/s 26.6 31.2 38.7 38.7 41.3 47.2 47.2 59.7
Condenser
Quantity of Coils # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Coil Length mm 1967 1967 1967 1967 1967 1967 1967 1967
Coil Height mm 1214 1214 1214 1214 1214 1214 1214 1214
Condenser Fans
Quantity (1) # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Diameter mm 800 800 800 800 800 800 800 800
Total Air Flow m
3
/s 4.2 4.8 4.8 4.8 4.8 5.6 5.6 5.6
Nominal RPM rpm 710 810 810 810 810 910 910 910
Motor kW 0.6 0.9 0.9 0.9 0.9 1.3 1.3 1.3
Minimum Starting/Operating Ambient
Standard Unit °C -10 -10 -10 -10 -10 -10 -10 -10
Low-Ambient Unit (Option) °C -20 -20 -20 -20 -20 -20 -20 -20
Maximum ambient operation
Standard ambient (9)
°C 46 46 46 46 46 46 46 46
Maximum ambient operation
High ambient (9)
°C 55 55 55 55 55 55 55 55
General Unit
Refrigerant HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a
Number of Independent
Refrigerant Circuits # 22222222
Minimum Load (2) % 15 15 15 15 15 15 15 15
Operating Weight kg 3605 3625 3800 4310 4580 4730 5180 5295
Shipping Weight kg 3546 3557 3714 4224 4490 4615 5065 5168
R134a refrigerant charge
Circuit1/Circuit 2
(kg) 42/41 40/39 44/43 46/45 50/44 61/52 62/59 67/65
Oil charge Circuit1/Circuit 2 (l) 6/6 6/6 6/6 6/6 7/6 7/6 7/7 8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.
RLC-SVX19A-E4
12
General Data
RTAF eXtra Ef ciency - eXtra Low Noise RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF
090 105 125 145 155 175 190 205
Eurovent Performances XE XLN XE XLN XE XLN XE XLN XE XLN XE XLN XE XLN XE XLN
Net Cooling Capacity (3) (4) (kW) 326 380 447 526 569 633 689 752
Power Input (5) (kW) 97 115 138 158 176 197 213 234
EER (3) (4) (6) (kW/kW) 3.36 3.30 3.24 3.33 3.23 3.20 3.24 3.21
ESEER (6) (kW/kW) 4.29 4.20 4.21 4.30 4.19 4.19 4.14 4.14
Eurovent Ef ciency class Cooling AA AA A AA A
Sound power level (eXtra Low Noise)
(10)
(dBA) 88 88 88 89 90 90 91 91
Middle East design condition performances (7)
Gross cooling capacity (tons) 77 90 105 125 135 150 164 178
Gross EER (kW/ton) 1.4 1.4 1.5 1.4 1.5 1.5 1.4 1.5
MEW (Kuwait) rating point performances (8)
Gross cooling capacity (tons) 73 86 100 119 127 142 155 168
Gross EER (kW/ton) 1.5 1.5 1.6 1.5 1.6 1.6 1.6 1.6
Table 5 – General Data RTAF 090 – 205 Extra Effi ciency - Extra Low Noise
Compressor
Quantity # 22222222
Nominal Size (1) tons 45/45 50/50 70/50 70/70 85/70 100/70 100/85 100/100
Evaporator
Evaporator Model 115B 115A 165B 165B 165A 200B 200B 250B
Water Storage l 51 58 74 74 78 99 99 118
Two pass Evaporator
Minimum Flow l/s 8.0 9.4 11.6 11.6 12.4 14.2 14.2 17.9
Maximum Flow l/s 29.6 34.7 43.1 43.1 46.0 52.6 52.6 66.5
Two pass Evaporator – With Turbulators
Minimum Flow l/s 6.6 7.8 9.7 9.7 10.3 11.8 11.8 14.9
Maximum Flow l/s 26.6 31.2 38.7 38.7 41.3 47.2 47.2 59.7
Condenser
Quantity of Coils # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Coil Length mm 1967 1967 1967 1967 1967 1967 1967 1967
Coil Height mm 1214 1214 1214 1214 1214 1214 1214 1214
Condenser Fans
Quantity (1) # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Diameter mm 800 800 800 800 800 800 800 800
Total Air Flow m
3
/s 4.2 4.8 4.8 4.8 4.8 5.6 5.6 5.6
Nominal RPM rpm 660 760 760 760 760 860 860 860
Motor kW 0.5 0.8 0.8 0.8 0.8 1.1 1.1 1.1
Minimum Starting/Operating Ambient
Standard Unit °C -10 -10 -10 -10 -10 -10 -10 -10
Low-Ambient Unit (Option) °C -20 -20 -20 -20 -20 -20 -20 -20
Maximum ambient operation
Standard ambient (9)
°C 46 46 46 46 46 46 46 46
Maximum ambient operation
High ambient (9)
°C 55 55 55 55 55 55 55 55
General Unit
Refrigerant HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a
Number of Independent
Refrigerant Circuits # 22222222
Minimum Load (2) % 15 15 15 15 15 15 15 15
Operating Weight kg 3705 3725 3900 4430 4700 4850 5320 5435
Shipping Weight kg 3646 3657 3814 4344 4610 4735 5205 5308
R134a refrigerant charge
Circuit1/Circuit 2
(kg) 42/41 40/39 44/43 46/45 50/44 61/52 62/59 67/65
Oil charge Circuit1/Circuit 2 (l) 6/6 6/6 6/6 6/6 7/6 7/6 7/7 8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.
RLC-SVX19A-E4
13
General Data
RTAF High Seasonal Ef ciency
- Standard and Low Noise
RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF
090 105 125 145 155 175 190 205
Eurovent Performances
HSE
SN&LN
HSE
SN&LN
HSE
SN&LN
HSE
SN&LN
HSE
SN&LN
HSE
SN&LN
HSE
SN&LN
HSE
SN&LN
Net Cooling Capacity (3) (4) (kW) 330 383 452 534 576 638 695 755
Power Input (5) (kW) 101 121 145 167 186 208 224 246
EER (3) (4) (6) (kW/kW) 3.26 3.17 3.11 3.19 3.10 3.07 3.10 3.07
ESEER (6) (kW/kW) 4.42 4.37 4.55 4.71 4.61 4.53 4.53 4.53
Eurovent Ef ciency class Cooling AA AAABA B
Sound power level (Standard Noise) (10) (dBA) 94 94 95 96 97 97 98 98
Sound power level (Low Noise) (10) (dBA) 91 91 92 93 94 94 95 95
Middle East design condition performances (7)
Gross cooling capacity (tons) 78 91 107 127 137 152 167 180
Gross EER (kW/ton) 1.47 1.50 1.54 1.47 1.52 1.54 1.50 1.53
MEW (Kuwait) rating point performances (8)
Gross cooling capacity (tons) 75 88 103 123 133 147 161 174
Gross EER (kW/ton) 1.56 1.59 1.64 1.56 1.62 1.63 1.60 1.63
Table 6 – General Data RTAF 090 – 205 High Seasonal Effi ciency - Standard and Low Noise
Compressor
Quantity # 22222222
Nominal Size (1) tons 45/45 50/50 70/50 70/70 85/70 100/70 100/85 100/100
Evaporator
Evaporator Model 115B 115A 165B 165B 165A 200B 200B 250B
Water Storage l 51 58 74 74 78 99 99 118
Two pass Evaporator
Minimum Flow l/s 8.0 9.4 11.6 11.6 12.4 14.2 14.2 17.9
Maximum Flow l/s 29.6 34.7 43.1 43.1 46.0 52.6 52.6 66.5
Two pass Evaporator – With Turbulators
Minimum Flow l/s 6.6 7.8 9.7 9.7 10.3 11.8 11.8 14.9
Maximum Flow l/s 26.6 31.2 38.7 38.7 41.3 47.2 47.2 59.7
Condenser
Quantity of Coils # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Coil Length mm 1967 1967 1967 1967 1967 1967 1967 1967
Coil Height mm 1214 1214 1214 1214 1214 1214 1214 1214
Condenser Fans
Quantity (1) # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Diameter mm 800 800 800 800 800 800 800 800
Total Air Flow m
3
/s 4.2 4.8 4.8 4.8 4.8 5.6 5.6 5.6
Nominal RPM rpm 710 810 810 810 810 910 910 910
Motor kW 0.6 0.9 0.9 0.9 0.9 1.3 1.3 1.3
Minimum Starting/Operating Ambient
Standard Unit °C -10 -10 -10 -10 -10 -10 -10 -10
Low-Ambient Unit (Option) °C -20 -20 -20 -20 -20 -20 -20 -20
Maximum ambient operation
Standard ambient (9)
°C 46 46 46 46 46 46 46 46
Maximum ambient operation
High ambient (9)
°C 55 55 55 55 55 55 55 55
General Unit
Refrigerant HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a
Number of Independent
Refrigerant Circuits # 22222222
Minimum Load (2) % 15 15 15 15 15 15 15 15
Operating Weight kg 3705 3765 3945 4450 4760 4915 5405 5520
Shipping Weight kg 3646 3697 3859 4364 4670 4800 5290 5393
R134a refrigerant charge
Circuit1/Circuit 2
(kg) 42/41 40/39 44/43 46/45 50/44 61/52 62/59 67/65
Oil charge Circuit1/Circuit 2 (l) 6/6 6/6 6/6 6/6 7/6 7/6 7/7 8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.
RLC-SVX19A-E4
14
General Data
RTAF High Seasonal Ef ciency - eXtra Low Noise RTAF RTAF RTAF RTAF RTAF RTAF RTAF RTAF
090 105 125 145 155 175 190 205
Eurovent Performances HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN HSE XLN
Net Cooling Capacity (3) (4) (kW) 330 383 451 533 575 638 694 755
Power Input (5) (kW) 100 119 144 165 184 206 221 243
EER (3) (4) (6) (kW/kW) 3.29 3.21 3.13 3.22 3.12 3.10 3.14 3.11
ESEER (6) (kW/kW) 4.46 4.43 4.62 4.77 4.68 4.62 4.62 4.61
Eurovent Ef ciency class Cooling AA AA A AA A
Sound power level (eXtra Low Noise) (10) (dBA) 88 88 88 89 90 90 91 91
Middle East design condition performances (7)
Gross cooling capacity (tons) 78 91 107 127 135 151 166 180
Gross EER (kW/ton) 1.46 1.48 1.53 1.47 1.54 1.54 1.49 1.52
MEW (Kuwait) rating point performances (8)
Gross cooling capacity (tons) 75 88 103 122 130 145 161 174
Gross EER (kW/ton) 1.56 1.58 1.63 1.58 1.64 1.64 1.58 1.61
Table 7 – General Data RTAF 090 – 205 High Seasonal Effi ciency - Extra Low Noise
Compressor
Quantity # 22222222
Nominal Size (1) tons 45/45 50/50 70/50 70/70 85/70 100/70 100/85 100/100
Evaporator
Evaporator Model 115B 115A 165B 165B 165A 200B 200B 250B
Water Storage l 51 58 74 74 78 99 99 118
Two pass Evaporator
Minimum Flow l/s 8.0 9.4 11.6 11.6 12.4 14.2 14.2 17.9
Maximum Flow l/s 29.6 34.7 43.1 43.1 46.0 52.6 52.6 66.5
Two pass Evaporator – With Turbulators
Minimum Flow l/s 6.6 7.8 9.7 9.7 10.3 11.8 11.8 14.9
Maximum Flow l/s 26.6 31.2 38.7 38.7 41.3 47.2 47.2 59.7
Condenser
Quantity of Coils # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Coil Length mm 1967 1967 1967 1967 1967 1967 1967 1967
Coil Height mm 1214 1214 1214 1214 1214 1214 1214 1214
Condenser Fans
Quantity (1) # 5/5 5/5 5/5 6/6 6/6 7/5 7/7 7/7
Diameter mm 800 800 800 800 800 800 800 800
Total Air Flow m
3
/s 4.2 4.8 4.8 4.8 4.8 5.6 5.6 5.6
Nominal RPM rpm 660 760 760 760 760 860 860 860
Motor kW 0.5 0.8 0.8 0.8 0.8 1.1 1.1 1.1
Minimum Starting/Operating Ambient
Standard Unit °C -10 -10 -10 -10 -10 -10 -10 -10
Low-Ambient Unit (Option) °C -20 -20 -20 -20 -20 -20 -20 -20
Maximum ambient operation
Standard ambient (9)
°C 46 46 46 46 46 46 46 46
Maximum ambient operation
High ambient (9)
°C 55 55 55 55 55 55 55 55
General Unit
Refrigerant HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a HFC134a
Number of Independent
Refrigerant Circuits # 22222222
Minimum Load (2) % 15 15 15 15 15 15 15 15
Operating Weight kg 3805 3865 4045 4570 4880 5035 5545 5660
Shipping Weight kg 3746 3797 3959 4484 4790 4920 5430 5533
R134a refrigerant charge
Circuit1/Circuit 2
(kg) 42/41 40/39 44/43 46/45 50/44 61/52 62/59 67/65
Oil charge Circuit1/Circuit 2 (l) 6/6 6/6 6/6 6/6 7/6 7/6 7/7 8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.
RLC-SVX19A-E4
15
RTAF Operating Map
To choose the unit confi guration, refer to operating map
gure below: Standard ambient, High ambient or Low
ambient.
* Standard ambient units:
-10°C Air temperature 46°C
* Low ambient units:
-18°C Air temperature 46°C
* High ambient units:
-10°C Air temperature 55°C
Note: It is not possible to have a unit operate low and
high ambient.
Figure 16 – RTAF Operating Map
Operating Map
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
-16 -12 -8 -4 0 4 8 12 16 20 24
Entering Air Temp [C]
Leaving Water Temp [C]
Standard ambient
Low ambient
High ambient
Part load
RLC-SVX19A-E4
16
Installation Requirements
Installation Responsibilities
Generally contractor must do following items when
installing an RTAF unit;
1. Install the unit in a fl at foundation, level and strong
enough to support unit loading.
2. Install the units as per instructions contained in this
manual.
3. Make electrical connections of the Tracer UC800.
4. Where specifi ed, provide and install valves in
the water piping upstream and downstream of
the evaporator water connections, to isolate the
evaporator for maintenance, and to balance and trim
the system.
5. Furnish and install a water fl ow prove device and/or
auxiliary contacts to prove chiller water fl ow.
6. Furnish and install water pressure gauges in the inlet
and outlet of the evaporator water box.
7. Supply and install an air vent cock to the top of the
evaporator water box.
8. Furnish and install strainers ahead of all pumps and
automatic modulating valves.
9. Provide and install fi eld wiring.
10. Install heat tape and insulate the chilled water lines
and any other portion of the system, as required, to
prevent sweating under normal operating conditions
or freezing during low ambient temperature
conditions.
11. Ensure that the compressor and oil separator
heaters have been operating for a minimum of
24 hours before starting. Failure to do so may
result in equipment damage.
12. Start the unit under supervision of a qualifi ed service
technician.
Storage
Extended storage of the unit prior to the installation
requires the following precautions:
1. Store the unit in a secured area, to avoid intentional
damages.
2. Close the suction, discharge and liquid-line isolation
valves.
3. At least every three months, connect a gauge and
manually check the pressure in the refrigerant circuit.
If the refrigerant pressure is below 13 Bar at 20°C (or
10 Bar at 10°C), call a qualifi ed service organization
and the appropriate Trane sales offi ce.
Note: If the unit is stored before servicing near a
construction site it is highly recommended to protect
micro-channel coils from any concrete dust. Failure to
do so may considerably reduce reliability of the unit.
Lifting and Moving Instructions
A specifi c lifting method is recommended, which can be
described as follow:
1. Lifting points are built into the unit, see lifting
instruction label on the unit.
2. Slings and spreader bar must be provided by crane
operator and attached on the lifting points.
3. Use the four rigging points which are built into the
unit.
4. The minimum lifting capacity of each sling as well as
the spreader bar must be higher than the tabulated
unit shipping weight.
5. CAUTION! Lift and handle with care. Avoid shocks
while handling.
Figure 1 Lifting
Dimension and Weights
See lifting weight on the submittal on the unit for
complete information.
Center of Gravity
See instructions on lifting drawings available on request.
WARNING! Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to lift
the unit must be capable of supporting the entire weight
of unit. Lifting cables (chains or slings) may not be the
same length. Adjust as necessary for even unit lift. Other
lifting arrangements could cause equipment or property
damage. Failure to follow instructions above or properly
lift unit could result in unit dropping and possibly
crushing operator/technician which could result in death
or serious injury.
WARNING! Improper Unit Lift!
Test lift unit approximately 10 cm to verify proper center
of gravity lift point. To avoid dropping of unit, reposition
lifting point if unit is not level. Failure to properly lift
unit could result in unit dropping and possibly crushing
operator/technician which could result in death or
serious injury and possible equipment or property- only
damage.
4000
2400
2200
A
2525
OPTION XLN
OPZIONZE XLN
OPTIE XLN
OPCIONE XLN
150 MAXI
SORTIE CONTENEUR
BEFESTIGUNGSPUNKT
CONTAINER PULL OUT
ESTRZIONE DAL CONTAINER
SLEEP-OOG
GANCHO DE ARRASTRE
X
Y
G
RLC-SVX19A-E4
17
Installation Requirements
Clearances
When installing the unit, provide enough space around
the unit to allow the installation and maintenance
personnel unrestricted access to all service points.
Unobstructed fl ow of condenser air is essential to
maintain chiller capacity and operating effi ciency. When
determining unit placement, give careful consideration to
ensuring a suffi cient air fl ow across the condenser coils
heat-transfer surface.
In case of enclosure around the unit, the height of the
enclosure must not be higher than the unit itself. If the
enclosure is higher than the unit, restrictive airfl ow
louvers should be fi tted to ensure fresh air supply.
Unit Isolation and Leveling
Provide a foundation with suffi cient strength and mass
to support the unit operating weight (that is, including
completed piping, full operating charges of refrigerant
and oil, and water). Refer to unit operating weights.
The unit must be leveled within 6mm over its length
and width. Use shims as necessary to level the unit. For
additional reduction of sound and vibration, install the
optional elastomeric isolators.
Isolator and Sound Emissions
The most effective form of isolation is to locate the
unit away from any sound sensitive area. Structurally
transmitted sound can be reduced by elastomeric
vibration eliminators. Spring isolators are not
recommended. Consult an acoustical engineer in critical
sound applications.
For maximum isolation effect, isolate water lines and
electrical conduit. Rubber isolated piping hangers can
be used to reduce the sound transmitted through water
piping. To reduce sound transmitted through electrical
conduit, use fl exible electrical conduit.
EU and Local Regulations codes on sound emissions
should always be considered. Since the environment
in which a sound source is located affects the sound
pressure, unit placement must be carefully evaluated.
Sound power levels for Sintesis RTAF are available on
request.
Neoprene Isolators Installation (Optional)
Isolators are ready to install. Mountings have to
be placed on a rigid and level foundation. External
equipment should not transmit additional vibration
to the chiller. The position of elastomeric isolator and
weight per point are given in the submittal which is
supplied with the chiller.
1. Secure the isolators to the mounting surface using
the mounting slots in the isolators base plate. Do
NOT fully tighten the isolators mounting bolts at
this time. See the isolators submittals for isolators
location, maximum weights, and isolators diagrams.
2. Align the mounting holes in the base of the unit
with the threaded positioning pins on the top of the
isolators.
3. Install the unit on the isolators and secure the
isolators to the unit with a nut. The maximum
isolators defl ection should be 6mm.
4. Level the unit carefully. Fully tighten the isolator
mounting bolts.
Figure 2 – Neoprene Isolator for SE – HE – XE – HSE units
117.6
14.2
127 159
16
63.5
70
12.7
9.6
40.6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
RLC-SVX19A-E4
18
Installation Requirements
Neoprene Pads Installation (Optional)
Isolators are ready to install. Mountings have to be placed
on a rigid and level foundation. External equipment should
not transmit additional vibration to the chiller.
Figure 3 – Neoprene pads for SE – HE – XE – HSE units
450
90
8
1
2
3
4
5
6
7
8
RTAF 190 HE_190 XE_190 HSE_205 HE_205 XE_205 HSE
1
2
3
4
5
6
RTAF 090_105_125_145_155_175
RLC-SVX19A-E4
19
Dimensional Data
Dimensional drawings below are approximate. For accurate dimensions, please use the submittals shipped within
the unit.
Figure 4 Units RTAF SE – HE – XE
2200
A
1000
1000
H1
H2
1000
1000
AH1H2
090-105-125
SE 4520
2526 2672
HE_XE 5645
145-155-175
SE 5645
HE_XE 6770
190-205
SE 6770
HE_XE 7895
090_105_125
SE 8
HE_XE 10
145_155_175
SE 10
HE_XE 12
190_205
SE 12
HE_XE 14
4
H1 = STD_LN
H2 = XLN
13
3
7
8
5
6
13
3 1
RLC-SVX19A-E4
20
Dimensional Data
Figure 5 Units RTAF HSE
Numbers in circles
1 = Evaporator water inlet connection
2 = Evaporator water outlet connection
3 = Electrical panel
4 = Minimum clearance (air entering and maintenance)
5 = Power cable gland plate for customer wiring
6 = External control wiring cable gland plate
7 = Power disconnect switch
8 = Display module
9 = Main processor module
10 = Hydraulic module
11 = Isolators
12 = Operating weight (kg)
13 = Number of fans
Numbers in arrows
1 = SN_LN unit
2 = Unit with hydraulic module
3 = Option XLN
4 = Grooved pipe (option)
For dimensions of hydraulic connections, electrical connections and isolator positioning, please refer to the
submittals delivered with the chiller. Submittals are available prior to shipment on request.
2200
A
1000
1000
H1
H2
1000
1000
090-105-125 10
145-155-175 12
190-205 14
AH1H2
090-105-125 5645
2526 2672145-155-175 6770
190-205 7895
4
13
3
7
8
5
6
H1 = STD_LN
H2 = XLN
13
3 1
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58