Trane Tracer TD7 User manual

Type
User manual
R
LC-
S
VU006A-E
4
Tracer™ TD7 with UC 80
0
for RTHD chillers
User
G
uid
e
Ori
g
inal instruction
s
RLC-
S
VU006A-E4
2
Copyrigh
t
A
ll rights reserved
This document and the information in it are the property of Trane and may not be
used or re
roduced in whole or in
art, without the written
ermission of Trane.
Trane reserves the ri
g
ht to revise this publication at any time and to make chan
g
es
to its content without obligation to noti
f
y any person o
f
such revision or change.
Trademark
s
TD7, RTHD Trane, the Trane logo, and Tracer are trademarks o
f
Trane. All trademarks
re
f
erenced in this document are the trademarks o
f
their respective owners.
© 2014 Tran
e
Tabl
e
o
f
Cont
e
nts
RLC-
S
VU006A-E
4
3
General Recommendations ................................................................................................... 4
Units with Nitrogen Charge Option .....................................................................................
.
5
Installer-
S
upplied Component
s
.............................................................................................
5
Power Supply Wirin
g
..............................................................................................................
5
Control Power Su
pp
l
y
............................................................................................................
5
Motor
C
abl
e
.................................................................................................................................................
.
6
Motor Rotation
C
heck .................................................................................................................................
.
6
A
C
Mains
C
onnectio
n
.................................................................................................................................
.
6
Interconnectin
g
Wirin
g
...........................................................................................................
7
Chilled Water Pum
p
Contro
l
........................................................................................................................
7
Programmable Relay
s
............................................................................................................
7
Relay Assi
g
nments Usin
g
Tracer™ T
U
..................................................................................
9
Low Volta
g
e Wirin
g
................................................................................................................
.
9
Emer
g
ency Sto
p
..........................................................................................................................................
.
9
External Auto/Sto
p
......................................................................................................................................
.
9
Ice Buildin
g
Option ...............................................................................................................
10
External Chilled Water Set
p
oint (ECWS) O
p
tio
n
................................................................
10
External Demand Limit Set
p
oint (EDLS) O
p
tion ..............................................................
.
10
EDL
S
and ECW
S
Analo
g
Input
S
i
g
nal Wirin
g
Details:
........................................................
1
1
Chilled Water Reset
(
CWR
)
....................................................................................................
11
Communications Int
e
rfac
e
..................................................................................................
1
2
LonTalk™ Interface
(
LCI-C
)
........................................................................................................................ 12
BACnet Pr
o
t
o
c
o
l .......................................................................................................................................
.
12
BACnet Testing Laboratory (BTL) Certifi catio
n
......................................................................................... 12
Mo
d
b
us
RTU
P
r
o
t
o
c
ol
................................................................................................................................12
O
v
e
rvi
ew
...............................................................................................................................
1
3
UC800 S
p
ecifi cation
s
...........................................................................................................
1
3
Wirin
g
and Port Description
s
...................................................................................................................
.
1
3
C
o
mmunicati
o
n Inter
f
ace
s
........................................................................................................................
1
3
R
otar
y
Switches .........................................................................................................................................
.
1
3
LED Descri
p
tion and O
p
eratio
n
...............................................................................................................
.
1
3
Tracer TD7 O
p
erator Interface ..............................................................................................
14
Tr a c
e
r™ TU
............................................................................................................................
14
S
tarter Diagnostic
s
...............................................................................................................
17
Main Processor Diagnostics ...............................................................................................
.
20
Communication Diagnostics
...............................................................................................
26
Operator Display Diagnostics and Messages ...................................................................
.
2
9
RLC-
S
VU006A-E4
4
I
nstallation El
e
ctrical
General Recommendation
s
As you review this manual, kee
p
in mind that:
All eld-installed wirin
g
must conform to European
g
uidelines and any applicable local codes. Be sure to
satis
f
y proper equipment grounding requirements per
European guidelines.
Compressor motor and unit electrical data (including
motor kW, voltage utilization range, rated load amps)
is listed on the chiller nameplate.
All eld-installed wiring must be checked for proper
terminations, and for possible shorts or grounds.
N
ote
:
Always refer to wiring diagrams shipped with
:
c
hiller or unit submittal
f
or s
p
eci
c electrica
l
s
chematic and c
o
nnecti
o
n inf
o
rmati
o
n
.
W
ARNIN
G
Proper Field Wirin
g
and
G
roundin
g
Required
!
All fi eld wiring MUST be performed by qualifi ed
personnel. Improperly installed and grounded fi eld
wirin
g
poses FIRE and ELECTR
O
CUTI
O
N hazards. To
avoid these hazards,
y
ou MUST follow re
q
uirements for
eld wiring installation and grounding as described in
local
e
l
e
ctrical cod
e
s. Failur
e
to follow cod
e
could r
e
sult
i
n
d
eat
h
or ser
i
ous
i
n
j
ury.
W
ARNIN
G
Hazardous Volta
g
e w/
C
apacitors!
Disconnect a
ll
e
l
ectric power, inc
l
uding remote
disconnects and dischar
g
e all motor start/run and AFD
(
Adaptive Frequency™ Drive
)
capacitors before servicing.
Follow proper lockout/ta
g
out procedures to ensure the
power cannot be inadvertent
l
y ener
g
ized.
For variable
f
requency drives or other ener
g
y storin
g
com
p
onents
p
rovided by Trane or others, re
f
er to the
a
pp
ro
p
riate manu
f
acturer’s literature
f
or allowable
waiting periods for discharge of capacitors. Verify
with an appropriate vo
l
tmeter that a
ll
capacitors have
di
sc
h
ar
g
e
d.
DC bus capacitors retain hazardous voltages after
i
nput power has been disconnected. Fo
ll
ow proper
lockout/ta
g
out procedures to ensure the power cannot
b
e inadvertently energized. After disconnecting input
p
ower, wait fi ve
(
5
)
minutes for the DC capacitors to
discharge, then chec
k
the vo
l
tage with a vo
l
tmeter.
M
ake sure DC bus capacitors are dischar
g
ed
(
0 VDC
)
b
e
f
ore touchin
g
any internal components
.
Failur
e
to follow th
e
s
e
instructions could r
e
sult in d
e
ath
or serious injury.
For additional information regarding the safe discharg
e
o
f ca
p
acitors, see Ada
p
tive Fre
q
uency™ Drive (AF
D
3
)
3
3
C
apacitor Dischar
g
e,” p. 28 and PR
O
D-SVB06A-EN.
W
ARNIN
G
Hazardous Volta
g
e - Pressurized Burnin
g
Fluid
!
B
efore removin
g
compressor terminal box cover for
servicin
g
, or servicin
g
power side of control panel,
C
LOSE COMPRESSOR DISCHARGE SERVICE VALVE
and disconnect all electric power includin
g
remote
d
isconnects. Dischar
g
e all motor start/run capacitors.
Follow lockout/tagout procedures to ensure the
p
ower cannot be inadvertently energized. Verify with
an appropriate voltmeter that all capacitors have
di
sc
h
arge
d
.
T
he compressor contains hot, pressurized refri
g
erant.
M
otor terminals act as a seal against this refrigerant.
C
are should be taken when servicin
g
NOT to dama
g
e or
l
oosen motor termina
l
s.
Do not operate compressor without termina
l
box cover
i
n
p
lace.
Failure to follow all electrical safety precautions could
result in death or serious in
j
ury
.
For additional in
f
ormation regarding the sa
f
e discharg
e
o
f ca
p
acitors, see Ada
p
tive Fre
q
uency™ Drive (AF
D
3
)
3
3
C
apacitor Dischar
g
e,” p. 28 and PR
O
D-SVB06A-EN.
N
O
TICE
:
Use Co
pp
er Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
resu
l
t in equipment damage
.
Important:
To prevent control malfunctions, do not run
:
l
ow volta
g
e wirin
g
(<30 V) in conduit wit
h
c
on
d
uctors carrying more t
h
an 30 vo
l
ts.
RLC-
S
VU006A-E
4
5
In case of drive servicin
g
only
W
ARNIN
G
DISCHARGE TIME!
Frequency converters contain DC-link ca
p
acitors that
can remain char
g
ed even when the
f
requency converter
is not powered. To avoid electrical hazards, disconnect
AC mains, any permanent magnet type motors, and
any remote D
C
link power supplies, including battery
backu
p
s, UPS and DC-link connections to other
frequency converters. Wait for the ca
p
acitors to fully
dischar
g
e be
f
ore per
f
ormin
g
any service or repair work.
The amount of wait time is listed in the Dischar
g
e Time
table. Failure to wait the specifi ed time after power has
been removed before doin
g
service or repair could result
i
n
d
eat
h
or ser
i
ous
i
n
j
ury.
Table 1. Capacitor Discharge Times
V
olta
ge
Po
we
r
M
inimum waitin
g
t
ime
[
min
]
3
80-500 V 9
0
-2
50
kW
20
3
15-800 kW
40
Units with Nitro
g
en Char
g
e
O
ptio
n
For units with nitro
g
en char
g
e option (model number
di
g
it 15 = 2
)
, the unit must NOT have shore power, or
unit power applied until the unit has been char
g
ed.
A
pplying power will drive
EXV
valves closed, and will
inhibit suffi cient vac for unit char
g
in
g
.
Installer-Su
pp
lied Com
p
onent
s
Customer wiring interface connections are shown in
t
h
e e
l
ectrica
l
sc
h
ematics an
d
connection
d
iagrams t
h
at
are shipped with the unit. The installer must provide the
followin
g
components if not ordered with the unit:
Power supply wirin
g
(
in conduit
)
for all fi eld-wired
c
o
nnecti
o
ns.
All control
(
interconnectin
g)
wirin
g
(
in conduit
)
for
eld supplied devices
.
Fused-disconnect switches or circuit brea
k
ers.
Power Supply Wirin
g
W
ARNIN
G
Proper Field Wirin
g
and Groundin
g
Required
!
All
eld wirin
g
MU
S
T be per
f
ormed by quali
ed
p
ersonnel. Improperly installed and grounded
eld
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
eld wirin
g
installation and
g
roundin
g
as described in
y
our local electrical codes. Failure to follow code could
r
esult in death or serious injury
.
A
ll power supply wirin
g
must
b
e sized and selected
a
ccordingly
b
y the project engineer in accordance
w
ith
EN
60204.
A
ll wiring must comply with local codes.
T
he installing
(
or electrical
)
contractor must provide and install the
s
ystem interconnectin
g
wirin
g
, as well as the power
s
upply wirin
g
.
I
t must
b
e properly sized and equipped
w
ith the a
pp
ro
p
riate fused disconnect switches
.
The type and installation location(s) of the fused
d
isconnects must com
p
ly with all a
pp
licable codes.
N
OTICE:
U
se Co
pp
er Conductors
O
nly!
U
nit terminals are not desi
g
ned to accept other types
o
f
conductors. Failure to use copper conductors could
r
esult in equipment damage
.
Cut holes into the sides of the control
p
anel for the
a
ppropriately-sized power wiring conduits.
T
he wiring
i
s passed throu
g
h these conduits and connected to the
terminal bloc
k
s, optional unit-mounted disconnects, or
H
ACR ty
p
e breakers.
The hi
g
h volta
g
e fi eld-provided connections are made
through patch plate on the right side o
f
the panel. The
low voltage connections are made through
k
noc
k
outs
p
rovided on the le
f
t side o
f
the panel. Additional grounds
may be required for each 115 volt power supply to the
u
nit. Green lu
g
s are provided for 115V customer wirin
g.
Control Power Supply
The unit is e
q
ui
pp
ed with a control
p
ower transformer.
I
t is not necessary to provide additional control power
v
oltage to the unit.
N
o other loads should
b
e connected
to the control power transformer
.
A
ll units are factory-connected for appropriate labeled
v
oltages.
I
nstallation El
e
ctrical
RLC-
S
VU006A-E4
6
I
nstallation El
e
ctrical
Motor Cable
The motor must be connected to terminals U/T1/96, V/
T2/97, W/T3/98. Earth (ground) to terminal 99. All types o
f
three-
p
hase asynchronous standard motors can be used
with a frequency converter unit. The factory setting is for
clockwise rotation with the
f
requency converter output
c
o
nnected as f
o
ll
o
ws:
Table 2.
Terminal n
o
.
F
uncti
on
96, 97, 98, 99
M
ains U/T1, V/T2, W/T3
E
arth (
g
round)
Motor Rotation Ch
e
c
k
The direction of rotation can be chan
g
ed by switchin
g
two phases in the motor cable or by chan
g
in
g
the settin
g
of 4-10 Motor
Sp
eed Direction.
Table 3.
A motor rotation check can be performed using1-28
Motor Rotation Check and
f
ollowing the steps shown in
t
h
e
d
isp
l
ay
.
A
C
Mains
C
onn
e
ctio
n
Size wirin
g
is based upon the input current of the
f
re
q
uency converter
Comply with local and national electrical codes for
c
ab
le size
s
C
onnect 3-phase A
C
input power wirin
g
to terminals
L1, L2, and L3
(
see Figure 1
)
Figure 1. Connecting to AC Mains
Table 4.
1
Mains c
o
nnecti
o
n
2
M
otor connection
Earth
(
ground
)
the cable in accordance with the
instructions provided
All
f
requency converters may be used with an isolated
input source as well as with earth
(g
round
)
reference
p
ower lines. When su
pp
lied from an isolated mains
source
(
IT mains or fl oating delta
)
or TT/TN-S mains
w
ith a grounded leg
(
grounded delta
)
, set 14-50 RFI
Filter t
o
O
FF
.
When off, the internal RFI fi lter capacitors between
the chassis and the intermediate circuit are isolated to
avoi
d
d
amage to t
h
e interme
d
iate circuit an
d
to re
d
uce
earth (ground) capacity currents in accordance with
IE
C
61800-3.
T
erminal
U
/
T
1/96
connected to
U
-
p
hase
Termin
a
l V
/
T2
/9
7
connected to
V
-
p
hase
Terminal W/T
3
/98
connected to
W
-
p
hase
RLC-
S
VU006A-E
4
7
Interconnecting Wirin
g
C
hilled Water Pump
C
ontrol
NOTICE:
E
quipment Dama
g
e
!
If the microprocessor calls for a pump to start and
water does not fl ow, the evaporator may be damaged
catastrophically. It is the responsibility of the installin
g
contractor and/or the customer to ensure that a pump
will always be running when called upon by the chiller
c
o
ntr
o
ls.
An evaporator water pump output relay closes when
the chiller is given a signal to go into the
A
uto mode
o
f
operation
f
rom any source. The contact is opened to
turn off the pump in the event of most machine level
dia
g
nostics to prevent the build up of pump heat.
The relay output is required to operate the Evaporator
Water Pum
p
(EWP) contactor. Contacts should be
compatible with 115/240 VAC control circuit. Normally,
the EWP rela
y
follows the AUTO mode of the chiller.
W
henever the chiller has no diagnostics and is in the
AUTO mode, re
g
ardless of where the auto command
is coming
f
rom, the normally open relay is energized.
When the chiller exits the AUT
O
mode, the rela
y
is timed
to open in an adjustable (usin
g
TU) 0 to 30 minutes.
The non-AUT
O
modes in which the pump is stopped,
include Reset,
S
to
p
, External
S
to
p
, Remote Dis
p
lay
S
to
p
,
S
topped by Tracer,
S
tart Inhibited by Low Ambient Temp,
and Ice Buildin
g
complete.
Table 5. Pump Relay Operation
Chiller Mod
e
R
ela
y
O
p
eratio
n
Au
t
o
I
nst
a
nt cl
o
se
I
ce Buildin
g
I
nst
a
nt cl
o
se
Tr
a
cer
O
verri
d
e Cl
o
se
S
to
p
Timed O
p
en
I
ce Com
p
lete
I
nstant
Op
en
D
ia
g
nostics
I
nstant
Op
en
When going from Stop to Auto, the EWP relay is
energized immediately. If evaporator water fl ow is not
established in 20 minutes
(
for normal transition
)
or 4
minutes, 15 seconds (for
p
um
p
commanded ON due to
an override safety), the UC800 de-ener
g
izes the EWP
relay and generates a non-latching diagnostic. I
f
ow
returns (e.g. someone else is controlling the pump),
the diagnostic is cleared, the EWP is re-energized, and
norma
l
contro
l
resume
d
.
I
f evaporator water fl ow is lost once it had been
established, the EWP relay remains energized and a
non-latching diagnostic is generated. If fl ow returns, the
d
iagnostic is cleared and the chiller returns to normal
o
p
eration.
I
n
g
eneral, when there is either a non-latchin
g
or latchin
g
d
ia
g
nostic, the EWP relay is turned o
ff
as thou
g
h there
w
as a zero time delay. Exce
p
tions whereby the relay
continues to
b
e ener
g
ized occur with:
L
ow
C
hilled Water Temp. diagnosti
c
(non-latching)
(
unless also accompanied by an Evap Leaving Water
Temperature Sensor Diagnostic
)
o
r
L
oss o
f
Evaporator Water Flow diagnosti
c
(
non-
latching) and the unit is in the AUTO mode, after
i
nitially havin
g
proven evaporator water
ow.
P
ro
g
rammable
R
elay
s
A
pro
g
rammable relay concept provides for enunciation
o
f
certain events or states o
f
the chiller
,
selected
f
rom a
list of likely needs, while only using four physical output
r
elays, as shown in the fi eld wirin
g
dia
g
ram. The four
r
elays are provided (
g
enerally with a Quad Relay Output
L
LID) as part of the Pro
g
rammable Relay Option. The
r
elay’s contacts are isolated Form C
(
SPDT
)
, suitable
for use with 120 VAC circuits drawing up to 2.8 amps
i
nductive, 7.2 amps resistive, or 1/3 HP and for 240 VAC
circuits
d
rawin
g
up to 0.5 amp resistive.
The list of events/states that can be assi
g
ned to the
p
rogrammable relays can be
f
ound in Table 6. The relay
w
ill be ener
g
ized when the event/state occurs.
I
nstallation El
e
ctrical
RLC-
S
VU006A-E4
8
I
nstallation El
e
ctrical
Table 6. Chiller events/status descriptions
E
vent
/
Stat
e
D
escri
p
tio
n
A
larm - Latchin
g
This output is true whenever there is any active dia
g
nostic that requires a manual
reset to clear, that effects the Chiller, the Circuit, or an
y
of the Com
p
ressors on a
c
ircuit. This classi cation does not include informational dia
g
nostics.
A
l
a
rm - A
u
t
o
Rese
t
This output is true whenever there is any active dia
g
nostic that could automatically
c
lear, that effects the Chiller, the Circuit, or an
y
of the Com
p
ressors on a circuit.
This classi cation does not include informational dia
g
nostics. If all of the auto
resettin
g
dia
g
nostics were to clear, this output would return to a false condition.
A
l
a
r
m
This output is true whenever there is any dia
g
nostic effectin
g
any component,
whether latchin
g
or automatically clearin
g
. This classi cation does not include
informational dia
g
nostics.
W
arnin
g
This output is true whenever there is any informational dia
g
nostic effectin
g
any
c
omponent, whether latchin
g
or automatically clearin
g
.
Chiller Limit M
od
e This output is true whenever the chiller has been runnin
g
in one of the Unloadin
g
t
yp
es of limit modes
(
Condenser, Eva
p
orator, Current Limit or Phase Imbalance
L
imit) continuously for the last 20 minutes. A
g
iven limit or overlappin
g
of different
limits must be in effect continuously for 20 minutes prior to the output becomin
g
true. It will become false, if no Unload limits are
p
resent for 1 minute. The lter
prevents short duration or transient repetitive limits from indicatin
g
. The chiller
is considered to be in a limit mode for the
p
ur
p
oses of front
p
anel dis
p
la
y
and
a
nnunciation, only if it is fully inhibitin
g
loadin
g
by virtue of bein
g
in either the
hold” or “forced unload” re
g
ions of the limit control, excludin
g
the “limited
loadin
g
re
g
ion”. (In previous desi
g
ns, the “limit load” re
g
ion of the limit control
was included in the criteria for the limit mode call out on the front
p
anel and
a
nnunciation out
p
uts
)
C
ompressor Runnin
g
The output is true whenever any compressors are started or runnin
g
on the
c
hiller and false when no compressors are either startin
g
or runnin
g
on the chiller.
This status ma
y
or ma
y
not re ect the true status of the com
p
ressor in Service
P
um
p
down if such a mode exists for a
p
articular chiller.
Chiller He
ad
Press
u
re Relie
f
R
e
q
uest Rela
y
This relay output is ener
g
ized anytime the chiller is runnin
g
in one of the followin
g
modes; Ice Makin
g
Mode or Condenser Pressure Limit Control Mode continuously
for the duration s
p
eci ed b
y
the Chiller Head Relief Rela
y
Filter Time. The Chiller
H
ead Relief Relay Filter Time is a service setpoint. The relay output is de-ener
g
ized
a
n
y
time the chiller exits all above modes continuousl
y
for the duration s
p
eci ed b
y
the same Chiller Head Relief Rela
y
Filter Time.
RLC-
S
VU006A-E
4
9
R
elay Assignments Using
Tracer™ TU
Tracer™ TU Service Tool is used to install the
Programmable Relay Option package and assign any
o
f
the above list o
f
events or status to each o
f
the
f
our
relays provided with the option. (See “Tracer™ TU,
for more information on the Tracer TU service tool.
)
The relays to be programmed are referred to by the
relay’s terminal numbers on the LLID board 1A10
.
The de
f
ault assignments
f
or the
f
our available relays o
f
the
P
rogramma
b
le
R
elay option are:
Table 7. Default assignments
R
ela
y
R
ela
y
0Terminals J2-1,2,3:
H
ead
p
ress.
R
ela
y
1Terminals J2-4,5,6:
L
imit m
od
e
R
ela
y
2Terminals J2 - 7,8,9:
A
l
a
r
m
R
ela
y
3Terminals J2 -10,11,12: CMP Runnin
g
Rela
y
If any of the Alarm/Status relays are used,
p
rovide
electrical power, 115 VAC with
f
used-disconnect to the
panel and wire through the appropriate relays
(
terminals
on 1A10
)
. Provide wirin
g
(
switched hot, neutral, and
g
round connections) to the remote annunciation devices.
Do not use
p
ower from the chillers control
p
anel
trans
f
ormer to power these remote devices. Re
f
er to the
eld diagrams which are shipped with the unit
.
L
ow Voltage Wirin
g
The remote devices described below require low voltage
w
iring. All wiring to and from these remote input devices
to the Control Panel must be made with shielded, twisted
p
air conductors.
B
e sure to ground the shielding only at
the panel.
Important:
To prevent control malfunctions, do not run
:
low voltage wiring (<30 V) in conduit wit
h
c
onductors carryin
g
more than 30 volts.
E
mergency
S
to
p
U
C800 provides auxiliary control
f
or a customer
s
peci
ed/installed latching trip out. When this customer-
f
urnished remote contact 5K22 is
p
rovided, the chiller
w
ill run normally when the contact is closed.
W
hen the
contact o
p
ens, the unit will tri
p
on a manually resetta
b
le
d
ia
g
nostic.
T
his condition requires manual reset at the
chiller switch on the
f
ront o
f
the control
p
anel
.
Connect low volta
g
e leads to terminal strip locations
1A12. Refer to the fi eld dia
g
rams that are shipped with
t
h
e unit.
S
ilver or gold-plated contacts are recommended. These
customer-furnished contacts must be compatible with 24
V
DC
,
12 mA resistive load.
E
xternal Auto/
S
to
p
I
f the unit requires the external Auto/
S
top function, the
i
nstaller must provide leads
f
rom the remote contacts
5K21 to the
p
ro
p
er terminals of the LLID 1A12 on the
contro
l
pane
l
.
T
he chiller will run normally when the contacts are
closed. When either contact opens, the compressor(s), if
operatin
g
, will
g
o to the RUN:UNLOAD operatin
g
mode
a
nd cycle o
ff
. Unit operation will be inhibited. Closure
o
f
the contacts will permit the unit to return to normal
operation.
F
ield-supplied contacts
f
or all low volta
g
e connections
must be compatible with dry circuit 24 VDC for a 12
mA resistive load. Refer to the fi eld diagrams that are
sh
ippe
d
wit
h
t
h
e unit.
I
nstallation El
e
ctrical
RLC-
S
VU006A-E4
1
0
I
nstallation El
e
ctrical
These customer-supplied contact closures must
be compatible with 24 VDC, 12 mA resistive load.
Silver or gold plated contacts are recommended.
Ice Buildin
g
Optio
n
UC800 provides auxiliary control for a customer
specifi ed/installed correct with contact closure 5K20 for
ice building i
f
so con
gured and enabled. This output
is known as the Ice Building
S
tatus Relay. The normally
open contact will be closed when ice building is in
progress and open when ice
b
uilding has
b
een normally
terminated either through
I
ce
T
ermination setpoint
b
eing
reached or removal of the Ice Buildin
g
command. This
output is
f
or use with the ice storage system equipment
or controls (provided by others) to signal the system
chan
g
es required as the chiller mode chan
g
es
f
rom
ice
b
uilding
to
ice complete
.
W
hen contact 5
K
12 is
p
rovided, the chiller will run normally when the contact
i
s open.
U
C
800 will accept either an isolated contact closure
(External Ice Building command) or a Remote
Communicated in
p
ut (Tracer) to initiate and command
the
I
ce
B
uildin
g
mode.
UC800 also provides a “Front Panel Ice Termination
S
etpoint”, settable through Tracer™ TU, and adjustable
from 20 to 31°F
(
-6.7 to -0.5°C
)
in at least 1°F
(
1°C
)
i
ncrements.
Note:
When in the Ice Building mode, and the
:
e
vaporator entering water temperature
d
rop
s
b
elow the ice termination setpoint, the chille
r
t
erminates the
I
ce
B
uildin
g
mode and chan
g
e
s
t
o the Ice Building
C
omplete Mode.
N
O
TICE
:
Equipment Dama
g
e!
Freeze inhibitor must be adequate for the leaving water
temperature. Failure to do so will result in dama
g
e to
system com
p
onents.
T
racer
TU
must als
o
b
e used t
o
ena
b
le
o
r disa
b
le
I
ce
Machine Control. This settin
g
does not prevent the Tracer
f
rom commandin
g
Ice Buildin
g
mode.
Upon contact closure, the U
C
800 will initiate an ice
building mode, in which the unit runs
f
ully loaded at all
times. Ice buildin
g
shall be terminated either by openin
g
the contact or
b
ased on the entering evaporator water
temperature. U
C
800 will not permit the ice building
mode to
b
e reentered until the unit has
b
een switched
out of ice building mode (open 5K12 contacts) and
then switched back into ice buildin
g
mode (close 5K12
contacts.)
In ice buildin
g
, all limits (freeze avoidance, evaporator,
condenser, current) will be ignored. All safeties will be
enforced.
If, while in ice building mode, the unit gets down to the
freeze stat setting (water or refrigerant), the unit will
shut down on a manually resettable diagnostic, just as in
normal o
p
eration.
Connect leads from 5K12 to the proper terminals of
1A15. Refer to the fi eld diagrams which are shipped with
t
he unit.
Silver or gold-plated contacts are recommended. These
customer furnished contacts must be com
p
atible with
2
4 VD
C
, 12 mA resistive load.
External Chilled Water
S
etpoint
(
ECWS) Optio
n
The U
C
800 provides inputs that accept either 4-20 mA or
2
-10 VDC signals to set the external chilled water setpoint
(ECWS). This is not a reset function. The in
p
ut defi nes the
setpoint. This input is primarily used with generic BAS
(
building automation systems
)
. The chilled water setpoint
set via the
T
racer
TD
7 or throu
g
h di
g
ital communication
with Tracer
(
Comm4
)
. The arbitration of the various
chilled water set
p
oint sources is described in the fl ow
charts at the end
of
the secti
o
n
.
The chilled water setpoint may be chan
g
ed
f
rom a
r
emote location by sending either a 2-10 VD
C
or 4-20 mA
si
g
nal to the 1A14, terminals 5 and 6 LLID. 2-10 VD
C
and
4
-20 mA each correspond to a 10 to 65°F (-12 to 18°C)
external chilled water set
p
oint.
The following equations apply:
Voltage
S
ignal
As
g
enerated from external source VDC=0.1455*(ECWS) + 0.545
4
As
p
rocessed by UC800 ECWS=6.875*(VDC) - 3.7
5
Current Signal
As
g
enerated from external source mA=0.2909(ECWS) + 1.090
9
As
p
rocessed by UC800 ECWS=3.4375(mA) - 3.75
I
f the ECWS input develops an open or short, the LLID
will report either a very high or very low value bac
k
to
t
he main processor. This will
g
enerate an informational
d
iagnostic and the unit will de
f
ault to using the Front
P
anel
(
TD7
)
Chilled Water Setpoint
.
Tracer TU Service Tool is used to set the input signal type
from the factory default of 2-10 VDC to that of 4-20 mA.
T
racer
TU
is als
o
used t
o
install
o
r rem
o
ve the
E
xternal
Chilled Water Set
p
oint o
p
tion as well as a means to
enable and disable ECW
S
.
External Demand Limit Set
p
oint
(
EDLS
)
O
p
tio
n
Similar to the above, the UC800 also provides for an
optional External Demand Limit Setpoint that will accept
either a 2-10 VDC (default) or a 4-20 mA signal. The
D
emand Limit
S
etting can also be set via the Tracer TD7
or throu
g
h di
g
ital communication with Tracer (Comm4).
The arbitration o
f
the various sources o
f
demand limit is
d
escribed in the fl ow charts at the end of this section. The
External Demand Limit
S
etpoint may be changed from a
r
emote location by hooking up the analog input signal to
t
he 1A14 LLID terminals 2 and 3. Re
f
er to the
f
ollowin
g
para
g
raph on Analo
g
Input Si
g
nal Wirin
g
Details.
RLC-
S
VU006A-E
4
1
1
The following equations apply for EDLS:
Volta
g
e Si
g
na
l
Current Si
g
nal
As
g
enerated from
external sourc
e
VDC+0.133*
(
%
)
-6.
0
mA=0.266*
(
%
)
-12.
0
As processed by
U
C
M
%=7.5*(VDC)+45.
0
%=3.75*(mA)+45.
0
If the EDLS input develops an open or short, the LLID
will report either a very high or very low value bac
k
to
the man processor. This will generate an in
f
ormational
diagnostic and the unit will de
f
ault to using the Front
Panel
(
Tracer TD7
)
Current Limit Setpoint
.
The Tracer™ TU
S
ervice T
oo
l must be used t
o
set the
input si
g
nal type
f
rom the
f
actory de
f
ault o
f
2-10 VDC to
that
of
4-20 mA current. Tracer TU must be als
o
be used
to install or remove the External Demand Limit
S
etpoint
O
p
tion for fi eld installation, or can be used to enable or
disable the feature
(
if installed
)
.
EDL
S
and ECW
S
Analo
g
Input
S
i
g
nal Wirin
g
Details
:
Both the ECW
S
and EDL
S
can be connected and setup
as either a 2-10 VDC (factor
y
default), 4-20 mA, or
resistance input
(
also a form of 4-2OmA
)
as indicated
b
elow.
D
ependin
g
on the type to
b
e used, the
T
racer
TU
S
ervice Tool must be used to confi
g
ure the LLID and the
MP for the proper input type that is bein
g
used. This is
accomplished by a setting change on the Custom Tab o
f
the Confi
g
uration View within Tracer TU.
Important:
For proper unit operation, BOTH the EDLS
:
a
nd ECW
S
settin
g
s MU
S
T be the sam
e
(
2-10 VDC or 4-20mA), even if only on
e
i
nput is to
b
e used.
T
he
J
2-3 and
J
2-6 terminal is chassis grounded and
terminal J2- 1 and J2-4 can be used to source 12 VD
C
.
The ECL
S
uses terminals J2-2 and J2-
3
. ECW
S
uses
terminals
J
2-5 and
J
2-6.
B
oth inputs are only compati
b
le
with high-side current sources.
Figure 2. Wiring examples for EDLS and ECWS
J2-1 & 4 Dual
J2-2 & 5 Analog
J2-3 & 6 I/O LLID
J2-1 & 4 Dual
J2-2 & 5 Analog
J2-3 & 6 I/O LLID
J2-1 & 4 Dual
J2-2 & 5 Analog
J2-3 & 6 I/O LLID
Resister
2-10 VDC, 4-20mA
I = 20/(R + 200)
I
Chilled Water Reset (CWR
)
U
C800 resets the chilled water tem
p
erature set
p
oint
based on either return water tem
p
erature, or outdoor air
tem
p
erature. Return Reset is standard, Outdoor Reset is
optional.
The following shall be selectable:
O
ne of three Reset Types: None, Return Water
Temperature Reset,
O
utdoor Air Temperature Reset, or
C
onstant Return Water Temperature Reset.
Reset Ratio Set Points
.
For outdoor air tem
p
erature reset there shall be both
p
ositive and ne
g
ative reset ratio’s
.
Start Reset Set Points
.
Maximum Reset
S
et Points.
The equations
f
or each type o
f
reset are as
f
ollows:
R
eturn
CWS’ = CWS + RATIO
(
START RESET -
(
TWE - TWL
))
a
nd CW
S
’ > or = CW
S
a
nd CW
S
’ - CW
S
< or = Maximum Reset
O
utd
oo
r
CWS’ = CWS + RATIO *
(
START RESET - TOD
)
a
nd CW
S
’ >
o
r = CW
S
a
nd CW
S
’ - CW
S
< or = Maximum Reset
wh
e
r
e
CWS’ is the new chilled water set point or the “reset
CW
S
CW
S
is the active chilled water set
p
oint before any reset
h
as occurred, e.g. normally Front Panel, Tracer, or ECW
S
RESET RATI
O
is a user adjustable gain
S
TART RE
S
ET is a user adjustable reference
T
O
D is the outdoor temperature
TWE is enterin
g
evap. water temperature
TWL
is leaving evap. water temperature
MAXIMUM RESET is a user adjustable limit providing
the maximum amount of reset. For all types of reset,
CW
S
’ - CW
S
<
o
r = Maximum Reset.
R
an
ge
I
ncrement
R
e
s
et
Typ
e
R
e
s
et
R
ati
o
S
tart
R
e
s
et
M
ax
R
e
s
et
IP
U
nit
s
SI
U
nit
s
F
actor
y
D
efa
u
lt
R
et
u
rn
10
t
o
120
%
4
t
o
30
F
0
t
o
20
F
1
%
1
%
50
%
(
2.2 to
1
6.7 C
)
(
0.0 to
1
1.1 C
)
Ou
t
doo
r
8
0 to
-
80%
50
t
o
130
F
0
t
o
20
F
1
%
1
%
10
%
(
10 to
54.4 C
)
(
0.0 to
1
1.1 C
)
I
nstallation El
e
ctrical
RLC-
S
VU006A-E4
1
2
I
nstallation El
e
ctrical
In addition to Return and Outdoor Reset, the MP
provides a menu item for the operator to select a
Constant Return Reset. Constant Return Reset will reset
the leaving water temperature set point so as to provide
a constant entering water temperature. The Constant
R
eturn
R
eset equation is the same as the
R
eturn
R
eset
equation except on selection of Constant Return Reset,
the MP will automaticall
y
set Ratio, Start Reset, and
Maximum Reset to the
f
ollowing.
RATIO = 100
%
START RESET = Design Delta Temp
.
MAXIMUM RESET = Desi
g
n Delta Temp.
The equation for Constant Return is then as follows:
CWS’ = CWS + 100% (Design Delta Temp. - (TWE - TWL))
and CW
S
’ >
o
r = CW
S
and CW
S
’ - CW
S
<
o
r = Maximum Reset
When any ty
p
e of CWR is enabled, the MP will ste
p
the Active CWS toward the desired CWS’
(
based on
the above e
q
uations and setu
p
p
arameters
)
at a rate
of 1 de
g
ree F every 5 minutes until the Active CW
S
equals the desired CW
S
. This applies when the chiller
is runnin
g
.
When the chiller is not running, CW
S
is reset
immediately
(
within one minute
)
for Return Reset and at
a rate of 1 de
g
ree F every 5 minutes for
O
utdoor Reset.
The chiller will start at the Differential t
o
S
tart value
above a fully reset CW
S
or CW
S
’ for both Return and
Outdoor Reset.
Communications Int
e
rfac
e
LonTalk™ Interface
(
LCI-C
)
UC800 provides an optional LonTalk™ Communication
Interface (LCI-C) between the chiller and a Buildin
g
Automation System
(
BAS
)
. An LCI-C LLID shall be used
to provide
g
ateway” functionality between a LonTalk
compatible device and the Chiller. The inputs/outputs
include both mandatory and o
p
tional network variables
as established by the LonMark Functional Chiller Pro
le
8
040.
Note:
For more information see ACC-SVN100*-EN.
:
BACnet Protocol
The Building Automation and Control Network (BACnet
a
nd ANSI/ASHRAE Standard 135-2004) protocol is a
standard that allows building automation systems or
com
p
onents from different manufacturers to share
i
n
f
ormation and control
f
unctions. BACnet provides
buildin
g
owners the capability to connect various
t
ypes of building control systems or subsystems
t
ogether
f
or a variety o
f
reasons. In addition, multiple
vendors can use this protocol to share information for
m
onitoring and supervisory control between systems
a
nd devices in a multi-vendor interconnected s
y
stem.
The BACnet protocol identifi es standard objects
(
data
points) called BACnet ob
j
ects. Each ob
j
ect has a defi ned
list of
p
ro
p
erties that
p
rovide information about that
ob
j
ect. BACnet also defi nes a number of standard
app
lication services that are used to access data and
m
anipulate these o
b
jects and provides a client/server
c
o
mmunicati
o
n between devices.
BACnet Testin
g
Laboratory
(
BTL
)
Certifi cation
All Tracer™ UC800 controllers are desi
g
ned to
su
pp
ort BACnet communication
p
rotocol. In
a
ddition,someparticular revisions o
f
the UC800
rmware
h
ave been tested and have achieved BTL certifi cation by
a
n o
ffi
cial BACnet testing laboratory. For more details,
r
efer to the BTL website at www.bacnetassociation.or
g
.
Modbus RTU Protocol
Modicon Communication Bus (Modbus) is an application
layer-messa
g
in
g
protocol that, like BACnet, provides
client/server communication
b
etween devices over
a
variety of networks. Durin
g
communications on a
Modbus RTU network, the
p
rotocol determines how
each controller will
k
now its device address, recognize
a
message addressed to its device, determine what
a
ction to take, and extract any data or other information
contained in the message.
C
ontrollers communicate
using a master/slave technique, where
b
y, only one
d
evice
(
master
)
can initiate transactions
(
queries
)
. Other
d
evices (slaves) respond by supplying the requested
d
ata to the master or by ta
k
ing the action requested in
t
he query.
T
he master can address individual slaves or it can
i
nitiate a
b
roadcast message to all slaves.
I
n turn, the
s
l
aves respon
d
to queries t
h
at are a
dd
resse
d
to t
h
em
i
ndividually or broadcasted. The Modbus RTU protocol
establishes the format for the masters query by placin
g
i
nto it the device address, a
f
unction code de
nin
g
the
r
e
q
uested action, any data to
b
e sent, and an error-
checkin
g
eld
.
RLC-
S
VU006A-E
4
1
3
Overvie
w
R
THD units utilize the following control/interface
com
p
onents:
T
racer™ UC800 Controlle
r
T
racer TD7
O
perator Interfac
e
UC800
S
peci
cations
This section covers in
f
ormation pertaining to the UC800
c
o
ntr
o
ller hardware.
W
i
r
i
n
g
an
d
Port Descr
i
pt
i
on
s
Figure 3 illustrates the U
C
800 controller ports, LEDs,
rotary switches, and wiring terminals. The numbered list
f
ollowing Figure 3 corresponds to the numbered callouts
in the illustrati
o
n.
Figure 3. Wiring locations and connection ports
F
ront
V
ie
w
Figure 3. Wiring locations and connection ports
B
ottom
V
iew
1
. Rotary Switches for settin
g
BACnet® MAC address or MODBUS ID
.
2
. LINK for BACnet MS/TP, or MODBUS Slave
(
two terminals, ±
)
. Field
wir
e
d if us
e
d
.
3. LINK for BACnet MS/TP, or MODBUS Slave (two terminals, ±). Field
wired if used
.
4. Machine bus for existin
g
machine LLIDs (IPC3 Tracer bus 19.200 baud).
IPC3 Bus: used for Comm4 using TCI or LonTalk® using LCI-C
.
5. Power (210 mA at 24 Vdc) and
g
round terminations (same bus as
i
tem 4). Factor
y
wired
.
6
.
N
ot used
.
7
. Marquee LED power and UC800 Status indicator.
8
.
S
tatus LEDs for the BA
S
link, MBus link, and IMC link
.
9. USB device ty
p
e B connection for the service tool (Tracer TU)
.
1
0. The Ethernet connection can only be used with the Tracer Ada
p
tiView
d
is
pl
ay
.
1
1. USB Host (not used)
.
Communication Interfaces
There are
f
our connections on the UC800 that support
the communication interfaces listed. Refer to Fi
g
ure 3,
p
. 13
f
or the locations o
f
each o
f
these ports.
BACnet M
S
/T
P
M
O
DBU
S
S
lave
L
onTalk using LCI-C
(
from the IPC3 bus
)
Comm 4 using TCI
(
from the IPC3 bus
)
Rotary Switche
s
There are three rotary switches on the
f
ront o
f
the UC800
controller. Use these switches to de
ne a three-digit
a
ddress when the UC800 is installed in a BACnet
o
r
MODBUS system (e.g., 107, 127, etc.)
.
Note:
Valid addresses are 001 to 127 for BACnet and 001
:
t
o 247 for M
O
DBUS.
L
ED Description and
O
peration
There are 10 LEDs on the
f
ront o
f
the UC800. Figure 4
s
hows the locations of each LED and Table 8, p. 14
d
escribes their behavior in specifi c instances
.
Co
ntr
o
ls
RLC-
S
VU006A-E4
1
4
Co
ntr
o
l
s
Figure 4. LED locations
Table 8. LED behavior
LED
U
C800 Statu
s
M
ar
q
uee
LED
Po
wered. If the Marquee LED is
g
reen solid,
the UC800 is
p
owered and no
p
roblems exist.
L
ow
p
ower or malfunction
.
If the Mar
q
uee
L
ED is red solid, the UC800 is
p
owered, but
there are
p
roblems
p
resent.
A
larm. The Mar
q
uee LED blinks Red when an
a
l
a
rm exists.
LINK
,
M
BU
S
, IM
C
Th
e
TX
LED blinks
g
reen at the data transfer
rate when the UC800 transfers data to other
d
evices
o
n the link.
Th
e
Rx
LED blinks
y
ellow at the data transfer
rate when the UC800 receives data from
o
ther
d
evices
o
n the link.
E
th
e
rn
e
t
L
ink
Th
e
LINK
LED is solid
g
reen if the Ethernet
link is connected and communicatin
g
.
Th
e
A
CT LED blinks
y
ellow at the data
tr
a
nsfer r
a
te when
da
t
a
o
w is
a
ctive
o
n the
link.
S
ervice
The Service LED is solid
g
reen when pressed.
F
or
q
uali ed service technicians onl
y
. Do not
u
s
e
.
NOTICE
:
El
ectrica
l
N
oise
!
Maintain at least 6 inches between low-volta
g
e (<30V)
and high voltage circuits. Failure to do so could result in
e
l
ectrica
l
noise that cou
l
d distort the signa
l
s carried by
the low-volta
g
e wirin
g
, includin
g
IPC.
Tracer TD7 Operator Interfac
e
I
nformation is tailored to o
p
erators, service technicians,
a
nd owners
.
W
hen operatin
g
a chiller, there is specifi c information
you need on a day-to-day basis—setpoints, limits,
d
iagnostic information, and reports.
D
ay-to-day operational information is presented at the
d
isplay. Logically organized groups of information—
chiller modes o
f
operation, active diagnostics, settings
a
nd reports put in
f
ormation conveniently at your
ngertips
.
Tr a c
e
r™ T
U
The RTHD o
p
erator interface allows for daily o
p
erational
t
as
k
s and setpoint chan
g
es. However, to adequately
service chillers
T
racer
TU
service tool is re
q
uired.
(Non-Trane
p
ersonnel, contact your local Trane offi ce
for software
p
urchase information.) Tracer TU adds a
level of so
p
histication that im
p
roves service technician
effectiveness and minimizes chiller d
o
wntime. This
p
ortable PC-based service-tool software su
pp
orts service
a
nd maintenance tasks, and is required
f
or so
f
tware
up
g
rades, confi
g
uration chan
g
es and major service
ta
s
k
s
.
Tracer TU serves as a common interface to all Trane
®
chillers, and will customize itself based on the properties
of the chiller with which it is communicating. Thus, the
service technician learns only one service interface.
T
he panel
b
us is easy to trou
b
leshoot usin
g
LED
sensor
verifi cation.
O
nly the defective device is replaced. Tracer
TU
can communicate with individual devices or
g
roups
o
f devices.
All chiller status, machine con
guration settings,
customiza
b
le limits, and up to 100 active or historic
d
iagnostics are displayed through the service-tool
s
of
tware inter
f
ace.
LED
s and their respective
T
racer
TU
indicators visually
con
rm the availability o
f
each connected sensor, relay,
a
nd actuat
o
r.
T
racer
TU
is designed to run on a customer
s laptop,
connected to the Tracer control
p
anel with a USB cable.
Your laptop must meet the
f
ollowin
g
hardware and
so
f
tware requirements:
1 GB RAM
(
minimum
)
1024 x 768 screen res
ol
uti
on
CD-R
O
M driv
e
Ethernet 10
/
100 LAN c
a
rd
An available U
S
B 2.0
p
ort
Microsoft® Windows® XP Professional operation
system with Service Pack 3 (SP3) or Windows 7
Enterprise or Professional operatin
g
system (32-bit or
64-bit)
Microso
f
t .NET Framework 4.0 or later
RLC-
S
VU006A-E
4
15
Note
:
Tracer TU is designed and validated for this
:
m
inimum laptop confi guration. Any variatio
n
f
rom this confi guration may have different results.
T
herefore, su
pp
ort for Tracer TU is limited to onl
y
t
hose laptops with the confi guration previousl
y
s
peci
ed.
N
ote
:
For more information, see TTU-SVN01A-EN
:
T
racer TU Gettin
g
Started Guid
e
Figure 5. Tracer TU
Co
ntr
o
ls
RLC-
S
VU006A-E4
1
6
D
i
a
g
nost
i
c
s
Dia
g
nostic Name and Source: Name of Diagnostic and
its source. Note that this is the exact text used in the
User Interface and/or Service Tool displays.
A
ff
ects Tar
g
et
:
Defi nes the “target” or what is affected
by the diagnostic. Usually either the entire Chiller,
or a particular Circuit or Compressor is affected by
the diagnostic (the same one as the source), but in
special cases functions are modifi ed or disabled by the
diagnostic. None implies that there is no direct a
ff
ect to
the chiller, sub components or functional operation.
Design Note:
T
racer
TU
does not support the display
o
f
certain targets on its Diagnostics pages although
the
f
unctionality implied by this table is supported.
Targets such as Evap Pump, Ice Mode, Chilled Water
Reset, External Set
p
oints etc. – are dis
p
layed as sim
p
ly
C
hiller” even though they do not imply a chiller
shutdown – only a com
p
romise of the s
p
ecifi c feature
.
Severit
y:
De
nes the severit
y
o
f
the above e
ff
ect.
Immediate means immediate shutd
o
wn
o
f the affected
p
ortion, Normal means normal or
f
riendly shutdown
of the affected
p
ortion, S
p
ecial Action means a s
p
ecial
action or mode of operation
(
limp alon
g)
is invoked, but
without shutdown
,
and In
f
o means an In
f
ormational
Note or Warnin
g
is
g
enerated. Desi
g
n Note: Tracer TU
does not support display of
S
pecial Action”, on its
Dia
g
nostics pa
g
es, so that if a dia
g
nostic has a special
action de
ned in the table below, it will be displayed
only as “In
f
ormational Warning” as long as no circuit
o
r chiller shutd
o
wn results. If there is a shutd
o
wn and
special action de
ned in the table, then the Tracer TU
Dia
g
nostics Pa
g
e display will indicate the shutdown
type on
l
y
.
Persistence
:
Defi nes whether or not the diagnostic and
i
ts effects are to be manually reset (Latched), or can be
either manually or automatically reset when and if the
condition returns to normal (Nonlatched).
Active Modes [Inactive Modes]
:
States the modes or
periods of operation that the diagnostic is active in
a
n
d
, as necessary, t
h
ose mo
d
es or perio
d
s t
h
at it is
specifi cally “not active” in as an exception to the active
m
odes. The inactive modes are enclosed in brackets, [ ].
N
ote that the modes used in this column are internal and
not generally annunciated to any o
f
the
f
ormal mode
d
is
p
lays.
C
riteria
:
Q
uantitatively defi nes the criteria used in
generating the diagnostic and, if nonlatching, the criteria
for auto reset. If more ex
p
lanation is necessary a hot link
t
o the Functional Specifi cation is used
.
R
eset Level: De
nes the l
o
west level
of
manual
d
iagnostic reset comman
d
w
h
ic
h
can c
l
ear t
h
e
d
ia
g
nostic. The manual dia
g
nostic reset levels in order of
priority are:
L
ocal or
R
emote.
F
or example, a dia
g
nostic
t
hat has a reset level of Remote, can be reset b
y
either
a
remote dia
g
nostic reset command or
b
y a local
d
ia
g
nostic reset comman
d
.
H
e
l
p
T
ext: Provides
f
or a brie
f
descri
p
tion o
f
what kind
of problems mi
g
ht cause this dia
g
nostic to occur. Both
control system component related pro
b
lems as well as
chiller a
pp
lication related
p
roblems are addressed (as
can possibly be anticipated
)
. These help messa
g
es will
be u
p
dated with accumulated fi eld ex
p
erience with the
c
h
i
ll
ers
.
RLC-
S
VU006A-E
4
1
7
Starter Diagnostic
s
H
ex
C
o
d
e
D
ia
g
nostic Name
a
nd S
o
urc
e
E
ffect
s
T
ar
g
et
Severit
y
P
er
s
i
s
tenc
e
A
ctive M
o
des
[
Inactive Modes
]
Criteri
a
R
e
s
et
L
evel
E5
P
h
a
se Revers
a
l
C
hiller
I
mme
d
i
a
te
La
tch
C
om
p
ressor
e
ner
g
ized
t
o
tr
a
nsiti
o
n
c
ommand
[
All
Other Times
]
A
p
hase reversal was detected on the
incomin
g
current.
O
n a compressor startup
the phase reversal lo
g
ic must detect and
tri
p
in a maximum of 0.3 second from
c
om
p
ressor s
t
ar
t
.
Lo
c
al
1
8
8
S
tarter Dr
y
Run Tes
t
C
hiller
I
mme
d
i
a
te
La
tch
S
tarter Dr
y
Run
Mod
e
W
hile in the Starter Dr
y
Run Mode either
50% Line Volta
g
e was sensed at the Potential
Tr
a
nsf
o
rmers
o
r 1
0
% RLA C
u
rrent w
a
s
s
ense
d
a
t the C
u
rrent Tr
a
nsf
o
rmers.
Lo
c
al
E4
P
h
a
se L
o
ss
C
hiller
I
mme
d
i
a
te
La
tch
S
tart
S
e
q
uence
a
n
d
R
u
n m
od
e
s
a)
No current was sensed on one or two
o
f the current transformer in
p
uts while
runnin
g
or startin
g
(See Nonlatchin
g
Power
L
oss Dia
g
nostic for all three phases lost
w
hile runnin
g
). Must hold = 20% RLA.
M
ust tri
p
= 5% RLA. Time to tri
p
shall be
lon
g
er than
g
uaranteed reset on Starter
M
odule at a minimum, 3 seconds maximum.
A
ctual desi
g
n trippoint is 10%. The actual
desi
g
n trip time is 2.64 seconds. b) If Phase
reversal
p
rotection is enabled and current
is n
o
t sense
d
o
n
o
ne
o
r m
o
re c
u
rrent
x
former inputs. Lo
g
ic will detect and trip in
a
maximum of 0.3 second from com
p
ressor
sta
r
t
.
Lo
c
al
E2
M
omentar
y
P
ower
Lo
ss
C
hiller
I
mme
d
i
a
te
No
nl
a
tch
A
ll com
p
ressor
runnin
g
and
s
toppin
g
modes
[
all com
p
ressor
s
tartin
g
and non-
runnin
g
modes]
M
omentar
y
Power Loss o
p
tion disabled: No
e
ff
ec
t.
M
omentar
y
Power Loss o
p
tion enabled: A
loss of
p
ower on three line c
y
cles or more
w
as detected. Dia
g
nostic is reset in 30
s
ec
o
n
d
s.
S
ee Momentar
y
Power Loss Protection
sp
eci cation for additional information.
R
em
o
te
1
A
0
Po
wer
Lo
ss
C
hiller
I
mme
d
i
a
te
No
nL
a
tch
A
ll com
p
ressor
runnin
g
modes
[
all com
p
ressor
s
tartin
g
and non-
runnin
g
modes]
The com
p
ressor had
p
reviousl
y
established
c
urrents while runnin
g
and then all three
phases of current were lost. Desi
g
n: Less
than 10% RLA, tri
p
in 2.64 seconds. This
dia
g
nostic will preclude the Phase Loss
D
ia
g
nostic and the Transition Complete Input
Opened Dia
g
nostic from bein
g
called out.
To prevent this dia
g
nostic from occurrin
g
w
ith the inten
d
e
d
d
isc
o
nnect
o
f m
a
in
p
ower, the minimum time to tri
p
must be
g
reater than the
g
uaranteed reset time o
f
the Starter module. Note: This dia
g
nostic
prevents nuisance latchin
g
dia
g
nostics due
to a momentar
y
p
ower loss – It does not
p
rotect motor/com
p
ressor from uncontrolled
p
ower rea
pp
lication. See Momentar
y
Power
L
oss Dia
g
nostic for this protection. This
dia
g
nostic will auto reset in 10 seconds from
its occurrence, and is not active durin
g
the
s
tart mode before the transition com
p
lete
in
p
ut is
p
roven. This
p
revents the chiller from
c
yclin
g
due to some internal starter problem,
a
s the st
a
rter w
ou
l
d
l
a
tch
ou
t
o
n either
a
Starter Fault T
yp
e 3” or a “Starter Did Not
Transition” latchin
g
dia
g
nostic. However true
power loss occurrin
g
durin
g
a start would
result in a misdia
g
nosis and the chiller would
not automaticall
y
recover.
R
em
o
te
E3
S
evere
Cu
rrent
Im
ba
l
a
nce
C
hiller
No
rm
al
La
tch
A
ll Runnin
g
Modes
A
30
% c
u
rrent im
ba
l
a
nce h
a
s
b
een
d
etecte
d
o
n one phase relative to the avera
g
e of all
3
p
hases for 90 continuous seconds.
Lo
c
al
D
i
a
g
nost
i
cs
RLC-
S
VU006A-E4
1
8
D
i
a
g
nost
i
c
s
H
ex
C
o
d
e
D
ia
g
nostic Name
a
nd S
o
urc
e
E
ffect
s
T
ar
g
et
Severit
y
P
er
s
i
s
tence
A
ctive M
o
des
[
Inactive Modes
]
Criteri
a
R
e
s
et
L
evel
1
E9 Starter Fault T
yp
e
I
C
hiller
I
mmediate
L
atch
Startin
g
- Y Delta
Starters Onl
y
This is a s
p
eci c starter test where 1M
(
1K1
)
is cl
o
se
d
rst
a
n
d
a
check is m
ad
e t
o
ens
u
re
that there are no currents detected b
y
the
CT's. If currents are detected when onl
y
1M
is closed rst at start, then one of the other
c
ontactors is shorted.
L
oca
l
1
ED Starter Fault T
yp
e I
I
C
hiller
I
mme
d
i
a
te
La
tch
Startin
g
All types
o
f st
a
rter
s
a
. This is a s
p
eci c starter test where the
Shortin
g
Contactor (1K3) is individually
e
ner
g
ized and a check is made to ensure that
there are no currents detected b
y
the CT's. I
f
c
urrent is detected when only S is ener
g
ized
a
t Start, then 1M is shorted. b. This test in a.
a
bove a
pp
lies to all forms of starters
(
Note:
I
t is understood that man
y
starters do not
c
onnect to the Shortin
g
Contactor.).
Lo
c
al
1
F
1
Starter Fault T
yp
e III
C
hiller
I
mme
d
i
a
te
La
tch
S
tartin
g
[
Ada
p
tive
F
re
q
uenc
y
S
tarter
T
yp
e]
A
s
p
art of the normal start se
q
uence to
a
pply power to the compressor, the Shortin
g
Contactor
(
1K3
)
and then the Main Contactor
(1K1) were ener
g
ized. 1.6 seconds later
there were no currents detected b
y
the
CT's f
o
r the l
a
st 1.2 sec
o
n
d
s
o
n
a
ll three
p
hases. The test above a
pp
lies to all forms
o
f st
a
rters.
Lo
c
al
1
89
S
o
li
d
St
a
te St
a
rter
Fau
lt
C
hiller
I
mme
d
i
a
te
La
tch
A
ll The Solid State Starter Fault Rela
y
is o
p
en
Lo
c
al
7
01
A
FD Drive F
au
l
t
C
hiller
I
mme
d
i
a
te
La
tch
A
ll The AFD Drive Fault Rela
y
is o
p
en
Lo
c
al
F0
St
a
rter Di
d
N
o
t
T
r
a
nsiti
o
n
C
hiller
I
mme
d
i
a
te
La
tch
O
n the rst check
a
fter tr
a
nsiti
o
n.
The St
a
rter M
odu
le
d
i
d
n
o
t receive
a
transition complete si
g
nal in the desi
g
nated
time fr
o
m its c
o
mm
a
n
d
t
o
tr
a
nsiti
o
n. The
m
u
st h
o
l
d
time fr
o
m the St
a
rter M
odu
le
tr
a
nsiti
o
n c
o
mm
a
n
d
is 1 sec
o
n
d
. The M
u
st
tri
p
time from the transition command is
6
seconds. Actual desi
g
n is 2.5 seconds. This
dia
g
nostic is active only for Y-Delta, Auto-
Transformer, Primar
y
Reactor, and X-Line
S
t
a
rters.
Lo
c
al
1
F
5
Com
p
ressor Did Not
A
ccelerate Full
y
C
hiller
I
mme
d
i
a
te
La
tch St
a
rt M
od
e
The starter module did not receive an “U
p
to Speed” or “End of Ramp” si
g
nal from the
SSS within 2.5 seconds after commandin
g
a
b
yp
ass, or after the maximum acceleration
time had expired, whichever is lon
g
er. This
dia
g
nostic only applies to SSS/AFD.
Lo
c
al
1
FA
Com
p
ressor Did Not
A
ccel: Tr
a
nsiti
o
n
C
hiller
I
nf
o
La
tch St
a
rt M
od
e
The com
p
ressor did not come u
p
to s
p
eed
(
g
et to <85%RLA) in the allotted time
de ned b
y
the Maximum Acceleration Timer
a
nd a transition was forced
(
motor
p
ut across
the line
)
at that time. This a
pp
lies to all
s
tarter t
yp
es. Note: Since RTHD SSS has no
forced transition capability, this info warnin
g
c
an be followed with a “Com
p
ressor did not
a
ccelerate fully” dia
g
nostic above and an
abo
rte
d
st
a
rt.
R
em
o
te
EE
Com
p
ressor Did Not
A
cceler
a
te: Sh
u
t
do
wn
C
hiller
I
mme
d
i
a
te
La
tch St
a
rt M
od
e
The com
p
ressor did not come u
p
to s
p
eed
(
g
et to <85%RLA) in the allotted time
de ned b
y
the Maximum Acceleration Timer
a
nd and the start was aborted
p
er the starter
c
on
g
uration selected.
R
em
o
te
3
D
5
Transition Com
p
lete
I
n
p
ut Shorted
C
hiller
I
mme
d
i
a
te
La
tch
P
re-
S
t
a
r
t
The Transition Com
p
lete in
p
ut is shorted
before the com
p
ressor was started. This is
a
ctive f
o
r
a
ll electr
o
mech
a
nic
a
l st
a
rters.
Lo
c
al
3
D
6
A
t S
p
eed In
p
ut
Sh
o
rte
d
C
hiller
I
mme
d
i
a
te
La
tch
P
re-
S
t
a
r
t
The “At S
p
eed” in
p
ut is shorted before the
c
om
p
ressor was started. This is active for
so
li
d
st
a
te st
a
rters
a
n
d
AFD.
Lo
c
al
RLC-
S
VU006A-E
4
19
H
ex
C
o
d
e
D
ia
g
nostic Name
a
nd S
o
urc
e
E
ffect
s
T
ar
g
et
Severit
y
P
er
s
i
s
tenc
e
A
ctive M
o
des
[
Inactive Modes
]
Criteri
a
R
e
s
et
L
evel
3
D7
Transition Com
p
lete
I
n
p
ut O
p
ened
C
hiller
I
mme
d
i
a
te
La
tch
A
ll Runnin
g
Modes
a
fter tr
a
nsiti
o
n
c
om
p
leted
The Transition Com
p
lete in
p
ut is o
p
en
w
ith the compressor motor runnin
g
after a
s
uccessful com
p
letion of transition. This is
a
ctive onl
y
for all electromechanical starter
s
Lo
c
al
3
D
8
A
t S
p
eed In
p
ut
O
p
ened
C
hiller
I
mme
d
i
a
te
La
tch
A
ll Runnin
g
Modes
a
fter At S
p
eed
p
r
o
v
en
The “At S
p
eed” in
p
ut was found to be
o
pened with the compressor motor runnin
g
a
fter successfully obtainin
g
an at speed and
b
yp
assed condition. This is active for solid
s
t
a
te st
a
rters
a
n
d
AFD
Lo
c
al
EC
Mo
t
o
r
Cu
rrent
O
verl
oad
C
hiller
I
mme
d
i
a
te
La
tch Chiller Ener
g
ized
Com
p
ressor current exceeded overload time
v
s. tri
p
characteristic. For A/C
p
roducts Must
tri
p
= 140% RLA, Must hold=125%, nominal
tri
p
132.5% in 30 seconds
Lo
c
al
C
A
S
t
a
rter
Co
nt
a
ct
o
r
I
nterru
p
t Failure
C
hiller
I
mme
d
i
a
te
a
nd S
p
ecial
A
cti
o
n
La
tch
S
t
a
rter
Co
nt
a
ct
o
r
not Ener
g
ized
[
Starter Contactor
E
ner
g
ized]
D
etected compressor currents
g
reater than
1
0% RLA on an
y
or all
p
hases when the
c
om
p
ressor was commanded off. Detection
time sh
a
ll
b
e
5
sec
o
n
d
s minim
u
m
a
n
d
10
sec
o
n
d
s m
a
xim
u
m.
O
n
d
etecti
o
n
a
n
d
u
ntil
the controller is manually reset:
g
enerate
dia
g
nostic, ener
g
ize the appropriate alarm
relay, continue to ener
g
ize the Evap and
Cond Pum
p
Out
p
uts, continue to command
the affected com
p
ressor off, full
y
unload the
e
ffected compressor. For as lon
g
as current
c
ontinues,
p
erform li
q
uid level and oil return
g
as pump contro
l
Lo
c
al
D7
Over Volta
g
e
C
hiller
No
rm
al
No
nL
a
tch
A
l
l
a
. Avera
g
e of all monitored Line volta
g
es
a
bove + 10% of nominal.
[
Must hold =
+
10% of nominal. Must tri
p
= + 15% o
f
n
o
min
a
l. Reset
d
ifferenti
a
l = min.
o
f 2%
a
nd max. of 4%. Time to tri
p
= minimum
o
f 1 min. and maximum of 5 min.
)
D
esi
g
n: Nom. trip: 60 seconds at
g
reater
than 112.5%, + or - 2.5%, Auto Reset at
10
9%
o
r less.
R
em
o
te
D8
U
nder Volta
g
e
C
hiller
No
rm
al
No
nL
a
tch
A
l
l
a
. Avera
g
e of all monitored Line volta
g
es
below - 10% of nominal or the Under
/
Overvolta
g
e transformer(s) are not
c
onnected.
[
Must hold = - 10% of nominal.
M
ust tri
p
= - 15% of nominal. Reset
d
ifferenti
a
l = min.
o
f 2%
a
n
d
m
a
x.
o
f 4%.
Time to tri
p
= min. of 1 min. and max. o
f
5 min.) Desi
g
n: Nom. trip: 60 seconds at
less than 87.5%, + or - 2.8% at 200V or
+
or - 1.8% at 575V, Auto Reset at 90%
o
r
g
rea
t
er.
R
em
o
te
D
i
a
g
nost
i
cs
RLC-
S
VU006A-E4
20
D
i
a
g
nost
i
c
s
Main Processor Diagnostic
s
H
ex
C
o
d
e
D
ia
g
nostic Nam
e
E
ffect
s
T
ar
g
et
Severit
y
P
er
s
i
s
tence
A
ctive M
o
des
[
Inactive Modes
]
Criteri
a
R
e
s
et
L
evel
D
9
MP
:
R
eset
Ha
s
O
cc
u
rre
d
C
hiller
I
nf
o
No
nL
a
tch
A
l
l
The main
p
rocessor has successfull
y
come
o
ut of a reset and built its a
pp
lication.
A
reset ma
y
have been due to a
p
ower u
p
,
installin
g
new software or con
g
uration. This
dia
g
nostic is immediately and automatically
c
leared and thus can onl
y
be seen in the
H
istoric Dia
g
nostic List in TechView
R
em
o
te
6
B
5
Unex
p
ected Starter
Sh
u
t
do
wn
C
hiller
No
rm
al
No
nl
a
tch
A
ll Cprsr Runnin
g
modes, Startin
g
,
R
unnin
g
and
P
reparin
g
to
Sh
u
t
do
wn
The Starter module status re
p
orted back that
it is stopped when it should be runnin
g
and
no Starter dia
g
nostic exists. This dia
g
nostic
w
ill be lo
gg
ed in the active buffer and then
c
le
a
re
d
.
NA
FB
L
ow Eva
p
orator
R
efri
g
erant
T
em
p
erature
C
hiller
I
mme
d
i
a
te
La
tch
A
ll Ckt Runnin
g
Mod
es
a
. The inferred Saturated Evap Refri
g
erant
Tem
p
erature
(
calculated from suction
p
ressure transducer
(
s
))
dro
pp
ed below the
L
ow Refri
g
erant Temperature Cutout Setpoint
for 450°F-sec
(
10°F-sec max rate
)
while the
c
ircuit was runnin
g
after the i
g
nore period
had expired. The inte
g
ral is held at zero for
the 1 minute i
g
nore time followin
g
the circuit
s
tartup and the inte
g
ral will be limited to
never tri
p
in less than 45 seconds, i.e. the
e
rror term shall be clam
p
ed to 10°F. The
minimum LRTC set
p
oint is -5°F
(
18.7 Psia
)
the
p
oint at which oil se
p
arates from the
refri
g
erant. b. Durin
g
the timeout of the
trip inte
g
ral, the unload solenoid(s) of the
runnin
g
compressors on the circuit, shall be
e
ner
g
ized continuously and the load solenoid
s
hall be off. Normal load/unload o
p
eration
w
ill be resumed if the trip inte
g
ral is reset by
return to tem
p
s above the cutout set
p
oint.
R
em
o
te
1
9
8
Lo
w
O
il Fl
o
w
C
hiller
I
mme
d
i
a
te
La
tch
Chiller Ener
g
ized
a
n
d
Delt
a
P
abo
ve
15
Psi
d
The oil
p
ressure was out of the acce
p
table
pressure ran
g
e for 15 seconds, while the
D
elta Pressure was
g
reater than 15 Psid.:
A
cceptable ran
g
e is 0.50 or 0.60 > (PC-Po) /
(
PC-PE
)
for the rst 2.5 minutes of o
p
eration,
a
nd 0.40 or 0.50 >
(
PC-Po
)
/
(
PC-PE
)
thereafter. The hi
g
her ratios used if the
sy
stem DP is less than 23
p
sid
Lo
c
al
5
9
C
Lo
ss
o
f
O
il
a
t
C
om
p
ressor
(Runnin
g
)
C
hiller
I
mme
d
i
a
te
La
tch
S
t
a
rter
Co
nt
a
ct
o
r
E
ner
g
ized
I
n runnin
g
modes , Oil Loss Level Sensor
detects lack of oil in the oil tank feedin
g
the
c
ompressor (distin
g
uishin
g
a liquid ow from
a
va
p
or ow
)
Lo
c
al
5
9D
Lo
ss
o
f
O
il
a
t
C
om
p
ressor
(
Sto
pp
ed
)
C
hiller
I
mme
d
i
a
te
a
nd S
p
ecial
A
cti
o
n
La
tch
C
om
p
ressor Pre-
s
tart
[
all other
modes
]
O
il L
o
ss Level Sens
o
r
d
etects
a
l
a
ck
o
f
o
il in
the oil tank feedin
g
the compressor for 90
s
econds after EXV
p
re
p
osition is com
p
leted.
N
ote: Com
p
ressor start is dela
y
ed while
w
aitin
g
for oil to be detected.
Lo
c
al
1
A
E
Lo
w Differenti
a
l
R
efri
g
erant Pressure
C
hiller
I
mme
d
i
a
te
La
tch Chiller Ener
g
ized
The s
y
stem differential
p
ressure was either
below 15 Psid for more than 164 Psid-sec,
o
r
b
el
o
w 2
3
.
0
Psi
d
f
o
r
3000
Psi
d
-sec. The
latter inte
g
ral’s value is not cleared for any
reason includin
g
dia
g
nostic trip, manual
reset, or power up reset (ie. Inte
g
ral is saved
nonvolatily on power down). The inte
g
ral will
decay while circuit is runnin
g
at a max rate
o
f –10 PSID, and while sto
pp
ed at a rate o
f
0.4 PSID. This same inte
g
ral is associated
w
ith the operatin
g
mode “Compressor Cool
D
own”. Also see dia
g
nostic below
R
em
o
te
2
97
No
Differenti
a
l
R
efri
g
erant Pressure
C
hiller
I
mme
d
i
a
te
La
tch Chiller Ener
g
ized
The s
y
stem differential
p
ressure was below
7.7 Psid. The occurrence of this dia
g
nostic
w
ill saturate the above “Low Diff Rf
g
t Press
I
nte
g
ral and invoke the same “Compressor
Cool Down” o
p
mode.
R
em
o
te
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32

Trane Tracer TD7 User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI