IECC 2018 BREAKROOM / KITCHEN
SWITCHING
None I18BKRD 10/3/2018
S
101
LM
S
DW2
LM
BREAKROOM
101
LMRC
102
LMRC
Breakroom / Kitchen
2018 IECC Compliant
On/Off Switching with DLM Product
BILL OF MATERIALS
LMRC-101 (1), 1-Relay Room Controller
LMRC-102 (1), 2-Relay Room Controller
LMDW-102 (1), 2-Button Dual Tech Wall Switch Occupancy Sensor
LMSW-101 (1), 1-Button Digital Wall Switch
LMRJ-03 (1), 3' CAT5 Cable
LMRJ-15 (1), 15' CAT5 Cable
LMRJ-25 (1), 25' CAT5 Cable
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.1.1: Manual On / Partial Auto On
C405.2.2.2: Light Reduction Controls
C405.2.4: Specific Application Controls
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. General lighting (a) auto On to 50% when occupancy detected.
2. Manual On and 50% reduction control of general lighting (a, b) with wall switch
occupancy sensor.
3. Manual On/Off control under cabinet lighting (c) with switch.
4. Auto off all lighting within 20 minutes of occupants leaving.
DESIGN CONSIDERATIONS
A ceiling or corner mount occupancy sensor can be used instead of the wall
switch occupancy sensor for larger rooms or to achieve a more specific area of
occupancy detection coverage.
Time scheduling, demand response and remote programming/diagnostic
functions are enabled with installation of the LMBC-300 Network Bridge for
system connectivity.
Although not required by IECC, receptacle control can be added to this space for
additional energy savings using either an RF transmitter with receptacle RF
receivers, or hardwired receptacles using an LMPL-101 Plug Load Room
Controller.
To integrate occupancy detection control with the HVAC System, use a
LMRL-100 Isolated Relay Interface.
LIGHTING BRANCH CIRCUIT
(UNSWITCHED HOT LEG)
AUTOMATIC DAYLIGHT
RESPONSIVE CONTROLS
REQUIRED WHERE GENERAL
LIGHTING POWER IN THE
SIDELIGHT AREA IS GREATER
THAN 150W.
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 BREAKROOM / KITCHEN
SWITCHING
None I18BKRD-W 10/3/2018
SEQUENCE OF OPERATION
1. General lighting (a) auto On to 50% when occupancy
detected.
2. Manual On/Off and 50% reduction control of general
lighting (a, b) with wall switch occupancy sensor.
3. Manual On/Off control under cabinet lighting (c) with
switch.
4. Auto off all lighting within 20 minutes of occupants
leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product
placement, installation, wiring and operation.
2. Diagram is typical for space type. Provide proper
quantity and type of occupancy sensors, switches,
room controllers, daylighting sensors, etc., per code
requirement for each space.
3. When general lighting power in the sidelight daylight
area is greater than 150w, automatic daylight
responsive controls are required.
4. Use pre-terminated CAT5e cables with splitters and
couplers as needed using a free topology wiring
arrangement to connect lighting control devices.
1 Button Switch
LMSW-101
Wattstopper
2 Button Sensor
LMDW-102
B
A
B
Dual Relay On/Off
Room Controller
LMRC-102
Red
Neutral Wht
Yel
Lighting
Load
Lighting
Load
Unswitched
Hot Blk
120/277
a
b
Red
Neutral Wht
Lighting
Load
Unswitched
Hot Blk
120/277
LMRC-101
Single Relay On/Off
Room Controller
c
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 SMALL PRIVATE OFFICE
SWITCHING
None I18SODD-W 10/3/2018
2 Button Sensor
LMDW-102
SEQUENCE OF OPERATION
1. Lighting (a) auto On for 50% lighting when occupancy
detected.
2. Lighting (a, b) may be manually controlled On/Off with manual
control switches, providing manual light reduction control.
3. All lighting will auto Off within 20 minutes of occupants
leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product
placement, installation, wiring and operation.
2. Diagram is typical for space type. Provide proper quantity and
type of occupancy sensors, switches, room controllers,
daylighting sensors, etc., per code requirement for each space.
3. Use pre-terminated CAT5e cables with splitters and couplers
as needed using a free topology wiring arrangement to
connect lighting control devices.
Dual Relay On/Off
Room Controller
LMRC-102
Red
Neutral Wht
Yel
Lighting
Load
Lighting
Load
Unswitched
Hot Blk
120/277
a
b
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 CLASSROOM
0-10V DIMMING
None I18CRDD 10/3/2018
500
LMLS
213
LMRC
CLASSROOM
101
LM
D
101
LM
D
Classroom
2018 IECC Compliant
Dimming with DLM product
BILL OF MATERIALS
LMRC-213 (1), 3-Relay Room Controller, 0-10V Dimming
LMDC-100 (2), Ceiling Mount Dual Tech Occupancy Sensor
LMDM-101 (3), 1-Button Dimming Wall Switch
LMLS-500 (1), Photosensor, Open Loop
LMRJ-01 (1), 6" CAT5 Cable
LMRJ-15 (2), 15' CAT5 Cable
LMRJ-25 (3), 25' CAT5 Cable
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.1.1: Manual On / Partial Auto On
C405.2.2.2: Light Reduction Control
C405.2.3.2: Daylight Responsive Control
C405.2.4: Specific Application Controls
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. General lighting (a, adz1) auto On to 50% when occupancy detected.
2. Manual On/Off/Dim and light reduction control of general lighting (a, adz1) with
dimmer switches.
3. Manual On/Off/Dim white board lighting (b) with dimmer switch.
4. Lighting in daylight zone (adz1) will continuously dim based on daylight
contribution to maintain at least 35FC at task level.
5. Auto Off all lighting within 20 minutes of occupants leaving.
DESIGN CONSIDERATIONS
Although not required by IECC, receptacle control can be added to this space for
additional energy savings using either an RF transmitter with receptacle RF
receivers, or hardwired receptacles using an LMPL-101 Plug Load Room Controller.
To integrate occupancy detection control with the HVAC System, use a LMRL-100
Isolated Relay Interface.
101
LM
D
LIGHTING BRANCH CIRCUIT
(UNSWITCHED HOT LEG)
SIDELIGHT
PRIMARY
DAYLIGHTING
ZONE
AUTOMATIC DAYLIGHT
RESPONSIVE CONTROLS
REQUIRED WHERE GENERAL
LIGHTING POWER IN THE
SIDELIGHT AREA IS GREATER
THAN 150W.
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 CLASSROOM
0-10V DIMMING
None I18CRDD-W 10/3/2018
Dual Tech Sensor
LMDC-100
Dual Tech Sensor
LMDC-100
Dimming Switch
LMDM-101
Wattstopper
Dimming Switch
LMDM-101
Wattstopper
Dimming Switch
LMDM-101
Wattstopper
Open Loop
Photosensor
LMLS-500
A
ADZ1
B
A
ADZ1
ADZ1
SEQUENCE OF OPERATION
1. General lighting (a, adz1) auto On to 50%
when occupancy detected.
2. Manual On/Off/Dim and light reduction
control of general lighting (a, adz1) with
dimmer switches.
3. Manual On/Off/Dim white board lighting
(b) with dimmer switch.
4. Lighting in daylight zone (adz1) will
continuously dim based on daylight
contribution to maintain at least 35FC at
task level.
5. Auto Off all lighting within 20 minutes of
occupants leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for
proper product placement, installation,
wiring and operation.
2. Diagram is typical for space type. Provide
proper quantity and type of occupancy
sensors, switches, room controllers,
daylighting sensors, etc., per code
requirement for each space.
3. When general lighting power in the
sidelight daylight area is greater than
150w, automatic daylight responsive
controls are required.
4. Use pre-terminated CAT5e cables with
splitters and couplers as needed using a
free topology wiring arrangement to
connect lighting control devices.
Dimming Room
Controller
LMRC-213
Red
Neutral Wht
Yel
Lighting
Load
Blu
Lighting
Load
Lighting
Load
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Unswitched
Hot Blk
120/277
Earth
Ground
Grn
0-10VDC Dimming Ballast, LED
Driver Required
Class 2
0-10VDC Dimming
a
adz1
b
112
LMRC
ROOM
213
LMRC
CONFERENCE
500
LMLS
105
LM
S
105
LM
S
LMDI
Conference Room
2018 IECC Compliant
Dimming with DLM product
BILL OF MATERIALS
LMRC-213 (1), 3-Relay Room Controller, 0-10V Dimming
LMRC-112 (1), 2-Relay Room Controller, 0-10V Dimming
LMDC-100 (2), Ceiling Mount Dual Tech Occupancy Sensor
LMSW-105 (2), 5-Button Scene Switch
LMLS-500 (1), Photosensor, Open Loop
LMDI-100 (1), Serial Data (A/V) Interface
LMRJ-03 (2), 3' CAT5 Cable
LMRJ-15 (3), 15' CAT5 Cable
LMRJ-25 (2), 25' CAT5 Cable
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.1.1: Manual On / Partial Auto On
C405.2.2.2: Light Reduction Control
C405.2.3.2: Daylight Responsive Control
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. General lighting (a, adz1) auto On to 50% when occupancy detected.
2. Manual On/Off/Dim and reduction control of general lighting (a, adz1) and down
lighting (b, c, d) with scene switches.
3. Scene settings
a. General Lighting (a, adz1) 100%, (b) 0%, (c) 0%, (d) 0%
b. Projection (a, adz1) 0%, (b) 75%, (c) 50%, (d) 0%
c. Conferencing (a, adz1) 50%, (b) 50%, (c) 25%, (d) 50%
d. All Off (a, adz1) 0%, (b) 0%, (c) 0%, (d) 0%
4. Lighting in daylight zone (adz1) will continuously dim based on daylight
contribution to maintain at least 35FC at task level.
5. Auto Off all lighting and A/V systems within 20 minutes of occupants leaving.
DESIGN CONSIDERATIONS
Although not required by IECC, receptacle control can be added to this space for
additional energy savings using either an RF transmitter with receptacle RF
receivers, or hardwired receptacles using an LMPL-101 Plug Load Room Controller.
Time scheduling, demand response and remote programming/diagnostic
functions are enabled with installation of the LMBC-300 Network Bridge for
system connectivity.
To integrate occupancy detection control with the HVAC System, use a LMRL-100
Isolated Relay Interface.
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 CONFERENCE ROOM
0-10V DIMMING
None I18LCDD 10/3/2018
SERIAL DATA INTERFACE TO CONNECT
THIRD PARTY SYSTEMS SUCH AS AV
EQUIPMENT, SHADE CONTROLS ETC.
LIGHTING BRANCH CIRCUIT
(UNSWITCHED HOT LEG)
SIDELIGHT
PRIMARY
DAYLIGHTING
ZONE
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 CONFERENCE ROOM
0-10V DIMMING
None I18LCDD-W 10/3/2018
SEQUENCE OF OPERATION
1. General lighting (a, adz1) auto On to 50% when occupancy detected.
2. Manual On/Off/Dim and reduction control of general lighting (a, adz1) and down lighting (b, c, d)
with scene switches.
3. Scene settings
a. General Lighting (a, adz1) 100%, (b) 0%, (c) 0%, (d) 0%
b. Projection (a, adz1) 0%, (b) 75%, (c) 50%, (d) 0%
c. Conferencing (a, adz1) 50%, (b) 50%, (c) 25%, (d) 50%
d. All Off (a, adz1) 0%, (b) 0%, (c) 0%, (d) 0%
4. Lighting in daylight zone (adz1) will continuously dim based on daylight contribution to maintain at
least 35FC at task level.
5. Auto Off all lighting and A/V systems within 20 minutes of occupants leaving
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product placement, installation, wiring and
operation.
2. Diagram is typical for space type. Provide proper quantity and type of occupancy sensors,
switches, room controllers, daylighting sensors, etc., per code requirement for each space.
3. When general lighting power in the sidelight daylight area is greater than 150w, automatic daylight
responsive controls are required.
4. Use pre-terminated CAT5e cables with splitters and couplers as needed using a free
topology wiring arrangement to connect lighting control devices.
RS232 Interface
LMDI-100
Dual Tech Sensor
LMDC-100
5 Button Switch
LMSW-105
Wattstopper
Open Loop
Photosensor
LMLS-500
Dual Tech Sensor
LMDC-100
5 Button Switch
LMSW-105
Wattstopper
ADZ1
ADZ2
Dimming Room
Controller
LMRC-213
Red
Neutral Wht
Yel
Lighting
Load
Blu
Lighting
Load
Lighting
Load
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Unswitched
Hot Blk
120/277
Earth
Ground
Grn
0-10VDC Dimming Ballast, LED
Driver Required
Class 2
0-10VDC Dimming
b
c
d
Dimming Lighting
Load
Dimming
Lighting Load
Room Controller
Dimming
LMRC-112
Red
Neutral Wht
Unswitched
Hot Blk
120/277
Red
0-10VDC Dimming
Yel
Yel
0-10VDC Dimming
Ballast, LED Driver Required
Vio
Gry
Gray & Violet
Gray/Yel & Violet/Yel
0-10VDC Dimming
Deep J-Box
Vio
Gry
(a)
(b)
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 LARGE PRIVATE OFFICE
0-10V DIMMING
None I18LODD 10/3/2018
Large Private Office
2018 IECC Compliant
Dimming with DLM product
BILL OF MATERIALS
LMRC-111 (1), 1-Relay Room Controller, 0-10V Dimming
LMDX-100 (1), Corner Mount Dual Tech Occupancy Sensor
LMDM-101 (1), 1-Button Dimming Wall Switch
LMLS-400 (1), Photosensor, Closed Loop
LMRJ-25 (3), 25' CAT5 Cable
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.1.1: Manual On / Partial Auto On
C405.2.2.2: Light Reduction Control
C405.2.3.2: Daylight Responsive Control
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. Lighting auto On to 50% when occupancy detected.
2. Manual On/Off/Dim and reduction control of general lighting with dimmer switch.
3. Lighting will continuously dim based on daylight contribution to maintain at least
35FC at task level.
4. Auto Off all lighting within 20 minutes of occupants leaving.
DESIGN CONSIDERATIONS
· Although not required by IECC, receptacle control can be added to this space for
additional energy savings using either an RF transmitter with receptacle RF
receivers, or hardwired receptacles using an LMPL-101 Plug Load Room Controller.
· Time scheduling, demand response and remote programming/diagnostic
functions are enabled with installation of the LMBC-300 Network Bridge for
system connectivity.
· To integrate occupancy detection control with the HVAC System, use a LMRL-100
Isolated Relay Interface.
101
LM
D
111
LMRC
LARGE
PRIVATE
OFFICE
400
LMLS
SIDELIGHT
PRIMARY
DAYLIGHTING
ZONE
LIGHTING
BRANCH
CIRCUIT
(UNSWITCHED
HOT LEG)
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 LARGE PRIVATE OFFICE
0-10V DIMMING
None I18LODD-W 10/3/2018
SEQUENCE OF OPERATION
1. Lighting auto On to 50% when occupancy detected.
2. Manual On/Off/Dim and reduction control of general lighting
with dimmer switch.
3. Lighting will continuously dim based on daylight contribution
to maintain at least 35FC at task level.
4. Auto Off all lighting within 20 minutes of occupants leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product
placement, installation, wiring and operation.
2. Diagram is typical for space type. Provide proper quantity and
type of occupancy sensors, switches, room controllers,
daylighting sensors, etc., per code requirement for each space.
3. When general lighting power in the sidelight daylight area is
greater than 150w, automatic daylight responsive controls are
required.
4. Use pre-terminated CAT5e cables with splitters and couplers
as needed using a free topology wiring arrangement to
connect lighting control devices.
Dimming Switch
LMDM-101
Wattstopper
LMDX-100
Photosensor
LMLS-400
A
A
Room Controller
Dimming
LMRC-111
Dimming
Lighting Load
Red
Vio
Gry
Neutral Wht
Unswitched
Hot Blk
120/277
Red
0-10VDC Dimming
Gray & Violet
0-10VDC Dimming
Deep J-Box
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 MULTI-STALL RESTROOM
SWITCHING
None I18RRRD 10/3/2018
WOMENS
RESTROOM
MENS
RESTROOM
LMRLLMRL
Multi-Stall Restroom
IECC 2018 Compliant
On/Off Switching with DLM Product
BILL OF MATERIALS
LMRC-102 (2), 2-Relay Room Controller
LMDC-100 (2), Ceiling Mount Dual Tech Occupancy Sensor
LMSW-102 (2), 2-Button Digital Wall Switch
LMRL-100 (2), Isolated Relay Interface
LMRJ-03 (2), 3' CAT5 Cable
LMRJ-15 (4), 15' CAT5 Cable
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.1.1: Manual On / Partial Auto On
C405.2.2.2: Light Reduction Control
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. For each restroom independently, lighting (a) auto On to 50% and exhaust fan auto
on when occupancy detected.
2. Manual On/Off and 50% reduction control of general lighting (a, b) with switches.
3. Auto Off all lighting and exhaust fan for each restroom independently within 20
minutes of occupants leaving.
DESIGN CONSIDERATIONS
It is important that each restroom (men and women) operate independently and
be isolated for correct auto configuration and operation of each independent
exhaust fan.
The IECC standard allows restroom lighting to automatically turn on up to 100% of
lighting power if desired.
Time scheduling, demand response and remote programming/diagnostic
functions are enabled with installation of the LMBC-300 Network Bridge for
system connectivity.
S
101
LM
a
S
101
LM
a
101
LMRC
a
101
LMRC
a
LIGHTING BRANCH CIRCUIT
(UNSWITCHED HOT LEG)
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 MULTI-STALL RESTROOM
SWITCHING
None I18RRRD-W 10/3/2018
SEQUENCE OF OPERATION
1. For each restroom independently, lighting (a) auto On
to 50% and exhaust fan auto on when occupancy
detected.
2. Manual on and 50% reduction control of general
lighting (a, b) with switches.
3. Auto Off all lighting and exhaust fan for each restroom
independently within 20 minutes of occupants leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product
placement, installation, wiring and operation.
2. Diagram is typical for space type. Provide proper
quantity and type of occupancy sensors, switches,
room controllers, daylighting sensors, etc., per code
requirement for each space.
3. Use pre-terminated CAT5e cables with splitters and
couplers as needed using a free topology wiring
arrangement to connect lighting control devices.
Contact Output
LMRL-100
Dual Tech Sensor
LMDC-100
Dual Relay On/Off
Room Controller
LMRC-102
Red
Neutral Wht
Yel
Lighting
Load
Lighting
Load
Unswitched
Hot Blk
120/277
a
b
1-Button Wall Switch
LMSW-101
Wattstopper
Contact Output
LMRL-100
Dual Tech Sensor
LMDC-100
Dual Relay On/Off
Room Controller
LMRC-102
Red
Neutral Wht
Yel
Lighting
Load
Lighting
Load
Unswitched
Hot Blk
120/277
a
b
1-Button Wall Switch
LMSW-101
Wattstopper
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 OPEN OFFICE >600sqft
0-10V DIMMING
None I18OODD 10/3/2018
Open Office
2018 IECC Compliant, Space >600 ft
2
Dimming with DLM product
BILL OF MATERIALS
LMRC-213 (2), 3-Relay Room Controller, 0-10V Dimming
LMDC-100 (6), Ceiling Mount Dual Tech Occupancy Sensor
LMDM-101 (1), 1-Button Dimming Wall Switch
LMLS-500 (1), Photosensor, Open Loop
ELCU-200 (2) UL924 Emergency Control Unit
LMRJ, Pre-Terminated Cable
CODE REQUIREMENTS
C405.2.1.3: Occupancy Sensor Control Open Offices
C405.2.2.2: Light Reduction Controls
C405.2.3.2: Daylight Responsive Controls
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. General lighting in just each zone <600 ft
2
(a, b, c, adz1,
bdz1, cdz1) auto On to last set light level when
occupancy detected in each zone.
2. Manual On/Off/Dim and reduction control of general
lighting for all zones (a, b, c, adz1, bdz1, cdz1) in unison
with dimmer switches.
3. Lighting in daylight zone (adz1, bdz1, cdz1) will
continuously dim based on daylight contribution to
maintain at least 35FC at task level
4. Auto Off all lighting in individual zone within 20 minutes
of occupants leaving individual zone.
5. Emergency lighting transfers to emergency power
source and full On with loss of normal power.
DESIGN CONSIDERATIONS
Although not required by IECC, receptacle control can
be added to this space for additional energy savings
using either an RF transmitter with receptacle RF
receivers, or hardwired receptacles using an LMPL-101
Plug Load Room Controller.
Time scheduling, demand response and remote
programming/diagnostic functions are enabled with
installation of the LMBC-300 Network Bridge for system
connectivity.
To integrate occupancy detection control with the
HVAC System, use a LMRL-100 Isolated Relay Interface.
OPEN
OFFICE
500
LMLS
ELCU
200
ELCU
200
101
LM
D
SIDELIGHT
PRIMARY
DAYLIGHTING
ZONE
213
LMRC
213
LMRC
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 OPEN OFFICE
0-10V DIMMING
None I18OODD-W 10/3/2018
SEQUENCE OF OPERATION
1. General lighting in just each zone ≤600 ft
2
(a, b, c, adz1,
bdz1, cdz1) auto On to last set light level when
occupancy detected in each zone.
2. Manual On/Off/Dim and reduction control of general
lighting for all zones (a, b, c, adz1, bdz1, cdz1) in unison
with dimmer switches.
3. Lighting in daylight zone (adz1, bdz1, cdz1) will
continuously dim based on daylight contribution to
maintain at least 35FC at task level
4. Auto Off all lighting in individual zone within 20 minutes
of occupants leaving individual zone.
5. Emergency lighting transfers to emergency power
source and full On with loss of normal power.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product
placement, installation, wiring and operation.
2. Diagram is typical for space type. Provide proper
quantity and type of occupancy sensors, switches, room
controllers, daylighting sensors, etc., per code
requirement for each space.
3. Use pre-terminated CAT5e cables with splitters and
couplers as needed using a free topology wiring
arrangement to connect lighting control devices.
Dimming Switch
LMDM-101
Wattstopper
Dual Tech Sensor
LMDC-100
Open Loop
Photosensor
LMLS-500
Dual Tech Sensor
LMDC-100
Dual Tech Sensor
LMDC-100
Dual Tech Sensor
LMDC-100
Dual Tech Sensor
LMDC-100
Dual Tech Sensor
LMDC-100
Dimming Room
Controller
LMRC-213
Red
Neutral Wht
Yel
Lighting
Load
Blu
Lighting
Load
Lighting
Load
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Unswitched
Hot Blk
120/277
Earth
Ground
Grn
0-10VDC Dimming Ballast, LED
Driver Required
Class 2
0-10VDC Dimming
a
b
c
Vio
Gry
0-10VDC Dimming
Ballast, LED Driver Required
Push
to Test
Cut jumper loop
to use with
Normally Closed
-test switch
-fire alarm panel
-security panel
-other
ELCU-200
Remote
Activation
Normal
Power
Emergency
Power
Normal Power Sense
(Black 18AWG)
Normal Neutral
(White 18AWG)
Normal Switched Sense
(Red 18AWG)
Emergency Power In
(Black 12AWG)
Emergency Neutral
(White 18AWG)
Emergency Power Out
(Red 12AWG)
Emergency Line
Emergency Neutral
Emergency Lighting
Load
Normal Power Sense
(Black 18AWG)
Normal Neutral
(White 18AWG)
Normal Switched Sense
(Red 18AWG)
Emergency Power In
(Black 12AWG)
Emergency Neutral
(White 18AWG)
Emergency Power Out
(Red 12AWG)
Emergency Line
Emergency Neutral
Vio
Gry
0-10VDC Dimming
Ballast, LED Driver Required
Push
to Test
Cut jumper loop
to use with
Normally Closed
-test switch
-fire alarm panel
-security panel
-other
ELCU-200
Remote
Activation
Normal
Power
Emergency
Power
Emergency Lighting
Load
Dimming Room
Controller
LMRC-213
Red
Neutral Wht
Yel
Lighting
Load
Blu
Lighting
Load
Lighting
Load
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Unswitched
Hot Blk
120/277
Earth
Ground
Grn
0-10VDC Dimming Ballast, LED
Driver Required
Class 2
0-10VDC Dimming
adz1
bdz1
cdz1
ec
ea
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 PRIVATE RESTROOM
SWITCHING
None I18PRRL 10/3/2018
PRIVATE
TOILET
Private Restroom
2018 IECC Compliant
On/Off Switching with line voltage wallbox product
BILL OF MATERIALS
PW-301 (1), Wallbox PIR Occupancy Sensor
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. Lighting and fan are manually controlled On/Off with occupancy sensor switch.
2. Lighting and fan will auto Off within 20 minutes of occupants leaving.
DESIGN CONSIDERATIONS
Demand Response, time scheduling and remote programming functions may be
enabled by using DLM product with LMBC-300 Network Bridge connectivity for
this space.
P
W
OCCUPANCY WALL
SWITCH TO CONTROL
LIGHTS AND EXHAUST
FAN ON/OFF.
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 PRIVATE RESTROOM
SWITCHING
None I18PRRL-W 10/3/2018
SEQUENCE OF OPERATION
1. Lighting and fan are manually controlled On/Off with
occupancy sensor switch.
2. Lighting and fan will auto Off within 20 minutes of
occupants leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product
placement, installation, wiring and operation.
2. Diagram is typical for space type. Provide proper
quantity and type of occupancy sensors, switches,
room controllers, daylighting sensors, etc., per code
requirement for each space.
d
a
L
o
Single Switch
Neutral
Line
Green/Yellow
Green
Black
Ground
Ground
Red
(See installation
120V/230V/277V Ground
instructions)
or 347V (PW-301-347)
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 SMALL CONFERENCE ROOM
0-10V DIMMING
None I18SCDD 10/3/2018
SMALL CONF.
ROOM
213
LMRC
105
LM
S
Small Conference Room
2018 IECC Compliant
Dimming with DLM product
BILL OF MATERIALS
LMRC-213 (1), 3-Relay Room Controller, 0-10V Dimming
LMDC-100 (1), Ceiling Mount Dual Tech Occupancy Sensor
LMSW-105 (1), 5-Button Scene Switch
LMRJ-15 (1), 15' CAT5 Cable
LMRJ-25 (1), 25' CAT5 Cable
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.1.1: Manual On / Partial Auto On
C405.2.2.2: Light Reduction Control
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. General lighting (a) auto On to 50% when occupancy detected.
2. Manual On/Off/Dim and reduction control of general lighting (a) and down lighting
(b, c) with scene switch.
3. Scene settings
a. General Lighting (a) 100%, (b) 0%, (c) 0%
b. Video (a) 20%, (b) 75%, (c) 0%
c. Conferencing (a) 50%, (b) 50%, (c) 25%
d. All Off (a) 0%, (b) 0%, (c) 0%
4. Auto Off all lighting within 20 minutes of occupants leaving.
DESIGN CONSIDERATIONS
Although not required by IECC, receptacle control can be added to this space for
additional energy savings using either an RF transmitter with receptacle RF
receivers, or hardwired receptacles using an LMPL-101 Plug Load Room Controller.
Time scheduling, demand response and remote programming/diagnostic
functions are enabled with installation of the LMBC-300 Network Bridge for
system connectivity.
To integrate occupancy detection control with the HVAC System, use a LMRL-100
Isolated Relay Interface.
LIGHTING
BRANCH
CIRCUIT
(UNSWITCHED
HOT LEG)
AUTOMATIC DAYLIGHT
RESPONSIVE CONTROLS
REQUIRED WHERE GENERAL
LIGHTING POWER IN THE
SIDELIGHT AREA IS GREATER
THAN 150W.
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 SMALL CONFERENCE ROOM
0-10V DIMMING
None I18LCDD-W 10/3/2018
SEQUENCE OF OPERATION
1. General lighting (a) auto On to 50% when occupancy detected.
2. Manual On/Off/Dim and reduction control of general lighting (a) and down lighting
(b, c) with scene switch.
3. Scene settings
a. General Lighting (a) 100%, (b) 0%, (c) 0%
b. Video (a) 20%, (b) 75%, (c) 0%
c. Conferencing (a) 50%, (b) 50%, (c) 25%
d. All Off (a) 0%, (b) 0%, (c) 0%
4. Auto Off all lighting within 20 minutes of occupants leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product placement, installation,
wiring and operation.
2. Diagram is typical for space type. Provide proper quantity and type of occupancy
sensors, switches, room controllers, daylighting sensors, etc., per code
requirement for each space.
3. When general lighting power in the sidelight daylight area is greater than 150w,
automatic daylight responsive controls are required.
4. Use pre-terminated CAT5e cables with splitters and couplers as needed using a
free topology wiring arrangement to connect lighting control devices.
Dual Tech Sensor
LMDC-100
5 Button Switch
LMSW-105
Wattstopper
Dimming Room
Controller
LMRC-213
Red
Neutral Wht
Yel
Lighting
Load
Blu
Lighting
Load
Lighting
Load
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Vio
Gry
Unswitched
Hot Blk
120/277
Earth
Ground
Grn
0-10VDC Dimming Ballast, LED
Driver Required
Class 2
0-10VDC Dimming
a
b
c
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 SMALL PRIVATE OFFICE
SWITCHING
None I18SODD 10/3/2018
Small Office
2018 IECC Compliant
On/Off Switching with DLM product
BILL OF MATERIALS
LMRC-102 (1), 2-Relay Room Controller
LMDW-102 (1), 2-Button Dual Tech Wall Switch Occupancy Sensor
LMRJ-15 (1), 15' CAT5 Cable
CODE REQUIREMENTS
C405.2.1: Occupancy Sensor Controls
C405.2.1.1: Manual On / Partial Auto On
C405.2.2.2: Light Reduction Control
C405.2.5: Manual Controls
SEQUENCE OF OPERATION
1. Lighting (a) auto On for 50% lighting when occupancy detected.
2. Lighting (a, b) may be manually controlled On/Off with manual control switches,
providing manual light reduction control.
3. All lighting will auto Off within 20 minutes of occupants leaving.
DESIGN CONSIDERATIONS
· Although not required by IECC, receptacle control can added to this space for
additional energy savings using either an RF transmitter with receptacle RF
receivers, or hardwired receptacles using an LMPL-101 Plug Load Room
Controller.
· Time scheduling, demand response and remote programming/diagnostic
functions are enabled with installation of the LMBC-300 Network Bridge for
system connectivity.
· To integrate occupancy detection control with the HVAC System, use a
LMRL-100 Isolated Relay Interface.
S
DW2
LM
SMALL
PRIVATE
OFFICE
102
LMRC
LIGHTING BRANCH CIRCUIT
(UNSWITCHED HOT LEG)
Date
Scale
Drawing#
Title
Rev.
Wattstopper
www.legrand.us/wattstopper
Phone: 888-852-2278
legrand
®
IECC 2018 SMALL PRIVATE OFFICE
SWITCHING
None I18SODD-W 10/3/2018
2 Button Sensor
LMDW-102
SEQUENCE OF OPERATION
1. Lighting (a) auto On for 50% lighting when occupancy
detected.
2. Lighting (a, b) may be manually controlled On/Off with manual
control switches, providing manual light reduction control.
3. All lighting will auto Off within 20 minutes of occupants
leaving.
TYPICAL DRAWING DETAIL NOTES
1. Follow manufacturer instructions for proper product
placement, installation, wiring and operation.
2. Diagram is typical for space type. Provide proper quantity and
type of occupancy sensors, switches, room controllers,
daylighting sensors, etc., per code requirement for each space.
3. Use pre-terminated CAT5e cables with splitters and couplers
as needed using a free topology wiring arrangement to
connect lighting control devices.
Dual Relay On/Off
Room Controller
LMRC-102
Red
Neutral Wht
Yel
Lighting
Load
Lighting
Load
Unswitched
Hot Blk
120/277
a
b
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19

Legrand IECC (2015) Wiring Diagrams Product information

Type
Product information
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI