Danfoss CF-RD Room Thermostat Installation guide

  • Hello! I am an AI chatbot trained to assist you with the Danfoss CF-RD Room Thermostat Installation guide. I’ve already reviewed the document and can help you find the information you need or explain it in simple terms. Just ask your questions, and providing more details will help me assist you more effectively!
088U0212
GB
Instruction CF-RD Room Thermostat with Display
D
Instruktion CF-RD Raum Thermostat mit Display
DK
Vejledning CF-RD Rumtermostat med display
F
Instruction CF-RD Thermostat avec écran
SE
Bruksanvisning CF-RD rumstermostat med display
PL
Instrukcja obsługi termostatu pomieszczenia z wyświetlaczem CF-RD
NL
Handleiding voor CF-RD Kamerthermostaat met display
I
Istruzioni Termostato ambiente con display CF-RD
1
VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
GB
Instruction . . . . . . . . . . . . . . . . . . . . . . . 3
D
Instruktion . . . . . . . . . . . . . . . . . . . . . . 11
DK
Vejledning . . . . . . . . . . . . . . . . . . . . . . . 21
F
Instruction . . . . . . . . . . . . . . . . . . . . . . 29
SE
Bruksanvisning . . . . . . . . . . . . . . . . . . 37
PL
Instrukcja obsługi . . . . . . . . . . . . . . . . 45
NL
Handleiding . . . . . . . . . . . . . . . . . . . . . 53
I
Istruzioni . . . . . . . . . . . . . . . . . . . . . . . . 61
2 VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
Instruction CF-RD Room Thermostat with Display
3VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
GB
GB
Index
1. Functional Overview.................................................4
2. Installation ....................................................................4
3. Temperature Settings ...............................................6
4. Transmission Test .......................................................7
5. Mounting ......................................................................8
6. Uninstallation ..............................................................8
7. Specications ..............................................................9
8. Troubleshooting ...................................................... 10
9. Figures and illustrations ................................A1-A2
Instruction CF-RD Room Thermostat with Display
4 VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
1. Functional Overview
Front - g. 1
Up/down selector
Push button
Red LED (behind the cover)
LED modes
Permanent light
ON
No light
OFF
Slow ashing
Flashes
Fast ashing
Flickers
Back - g. 2
Back plate
Back plate lock/unlock (turn 90°)
Screw hole for wall mounting
Battery placement
Screw and wall plug
Note: To activate batteries please remove enclosed strips
from batteries
2. Installation
Note:
To activate batteries in the Room Thermostat please
remove enclosed strips from the batteries.
The assignment of the Room Thermostats to the Master
Controller should be within 1½m distance
Instruction CF-RD Room Thermostat with Display
5VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
GB
Activate Install mode on Master Controller
- g. 1
Use the menu selection button
to select the
Install mode. Install LED ashes
Activate Install mode by pressing OK
. Install
LED goes ON
Activate Install mode on Room Thermostat
Press the push button
. LED and icker
during communication
Select output on Master Controller
All available output LEDs on Master Controller
light up, and the rst of them ashes
Press output selection button
, select desired
output (ashes) and accept with OK
All output LEDs go OFF. Selected output
stays ON shortly
Room Thermostat installation status
Satisfactory - LED
goes OFF
Not satisfactory - LED
ashes 5 times
Note: A Room Thermostat can be assigned to several
outputs if needed by repeating the installation process.
Instruction CF-RD Room Thermostat with Display
6 VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
3. Temperature Settings
Digital Display - g. 1
Set value adjustment
Minimum temperature limitation
Maximum temperature limitation
Lock icon (settings locked from
Remote Controller, CF-RC)
Transmission link icon
Low battery indicator
Alarm icon
Timer icon (time & zone control set from
Remote Controller, CF-RC)
Setting of Temperatures - g. 1
The actual room temperature is shown in the
display as default
Setting of room temperature
Press the up/down selector
to set the desired
room temperature value, SET is shown in the
display
When releasing the up/down selector
the
display returns to actual room temperature
Room temperature limitation
Press and hold the push button
until SET
MAX is shown in the display
Press the up/down selector
to set the maxi-
mum room temperature limitation
Press the push button
shortly, SET MIN is
shown in the display
Instruction CF-RD Room Thermostat with Display
7VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
GB
Press the up/down selector to set the mini-
mum room temperature limitation
Press the push button
shortly, the actual
room temperature is shown in the display
4. Transmission Test
Initiate transmission test on Room Thermostat
- g. 1
Press the push button
LED goes ON
Link test is satisfactory
LED
goes OFF
Link test is unsatisfactory
LED
ashes 5 times
No Link connection to Room Thermostat
Try to relocate Room Thermostat in the room
Or install Repeater Unit (CF-RU) and locate be
-
tween Master Controller and Room Thermostat
Note: Master Controller output LED(s) connected to the
room thermostat, ash(es) during Link test
Instruction CF-RD Room Thermostat with Display
8 VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
5. Mounting
Placing the Room Thermostat - g. 3
! Wherever possible, the room thermostat should be
installed at a place where the eect of sunlight, draught,
other heaters (eg. TVs), etc. is avoided.
Mounting with screws - g. 2
Back plate
Screw hole for wall mounting
Screw and wall plug
6. Uninstallation
Activate Uninstall mode on Master Controller
- g. 1
Use the Menu selection button
to choose the
Uninstall menu. Uninstall LED ashes
Activate Uninstall mode by pressing OK
.
Uninstall LED goes ON
Deselect output on Master Controller
Select output to be removed by output selection
button
Remove ashing output with OK
Instruction CF-RD Room Thermostat with Display
9VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
GB
7. Specications
Temperature setting range 5-35°C
Transmission frequency 868.42MHz
Transmission range in normal
buildings (up to)
30m
Transmission power < 1mW
Battery Alkaline 2xAA, 1.5V
Battery lifetime (up to) 2-3 years
Ambient temperature 0-50°C
IP class 21
Instruction CF-RD Room Thermostat with Display
10 VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
8. Troubleshooting
Error Indication Possible Cause
The LED, and
ashes every 5th minute
Low battery
The LED, and
ashes every 30 sec.
Critical low battery
The LED, , and
ashes
Critical low battery - trans-
mission has stopped
The LED, and
ashes 5 times
Installation/Link Test is
unsatisfactory
E03 and
Actuator error on output
(CF-MC)
E05 and
Room temperature below
5ºC
20
VI.UH.Q4.1C Produced by Danfoss Floor Heating Hydronics 03.2007
Vejledning CF-RD Rumtermostat med display
21VI.UH.Q4.1C
Fremstillet af Danfoss Floor Heating Hydronics 03.2007
DK
DK
Indhold
1. Funktionsoversigt ................................................... 22
2. Installation ................................................................. 22
3. Temperaturindstillinger ........................................ 24
4. Transmissionstest ................................................... 25
5. Montering .................................................................. 26
6. Anstallation ............................................................ 26
7. Specikationer ......................................................... 27
8. Fejlnding .................................................................. 28
9. Figurer og illustrationer .................................A1-A2
Instruction CF-RD Thermostat avec écran
29VI.UH.Q4.1C Produit par Danfoss Floor Heating Hydronics 03.2007
F
9. Tableaux et illustrations .................................A1-A2
1. Présentation des fonctions ..................................
30
2. Installation ................................................................. 30
3. Réglages température........................................... 32
4. Test transmission ..................................................... 33
5. Montage ..................................................................... 34
6. Désinstallation ......................................................... 34
7. Spécications ........................................................... 35
8. Dépannage................................................................ 36
F
Index
Handleiding voor CF-RD Kamerthermostaat met display
60 VI.UH.Q4.1C Geproduceerd door Danfoss Floor Heating Hydronics 03.2007
8. Probleemoplossing
Foutmelding Mogelijke oorzaken
De led, en knipperen
om de 5 minuten
Batterij bijna leeg
De led, en knipperen
om de 30 sec.
Batterij op kritisch peil
De led, , en
knipperen
Batterij op kritisch peil
– transmissie gestopt
De led, en knipperen
5 keer
Aanmelden/Verbin-
dingstest niet gelukt
E03 en
Motorfout op uitgang
(CF-MC)
E05 en
Kamertemperatuur
lager dan 5°C
/