Scotsman CME1686RLS User manual

Category
Ice cube makers
Type
User manual

This manual is also suitable for

Introduction:
This manual covers the assembly, installation, start
up, operation and maintenance of the 1300 and
1600 remote low side cuber systems.
An illustrated parts list and wiring diagram is in the
center of this manual.
Keep this manual for future reference.
Eclipseä 1300,1600
September 2003
Page 1
Table of Contents
Introduction: ·················· Page 1
Configuration: ················· Page 2
Technical Specifications ············ Page 3
Model Number Locations ··········· Page 4
Cabinet Drawings, Ice Making System ···· Page 5
Cabinet Drawings, Compressor Package and
Condensers ·················· Page 6
Proper Combinations: ············· Page 7
Create the System··············· Page 8
System Examples ··············· Page 9
System Examples ··············· Page 10
Place Remote System ············· Page 11
System Location ················ Page 12
Route Tubing ················· Page 13
Ice Making Section ·············· Page 14
Compressor Package ············· Page 15
Condensing Section Assembly ········ Page 16
Condensing Section Assembly ········ Page 17
Ice making section: ·············· Page 18
Bin Thermostat - Routing ··········· Page 19
Bin Thermostat - Bracket & Bulb ······· Page 20
Water and Drain ················ Page 21
Water and Drain ················ Page 22
Ice Making Section Set Up ·········· Page 23
Coupling Connections: ············ Page 24
Condensing Unit Connections ········· Page 25
Final Placement ················ Page 26
Controller Operation ·············· Page 27
Initial Start Up - 1300 and 1600 ········ Page 28
Purge Adjustment ··············· Page 29
System Operation:··············· Page 30
Refrigeration Details: ············· Page 31
Technicians Only: Freeze Cycle Sequence of Operation
·························Page 32
Technicians Only: Harvest Cycle Sequence of
Operation ··················· Page 33
Power and Water Interruptions ········ Page 34
Sanitation and Cleaning ············ Page 35
Other Maintenance ·············· Page 36
Water Distributors ··············· Page 37
Ice Sensors ·················· Page 38
Water Level Sensor Maintenance ······· Page 39
Service Diagnosis ··············· Page 40
Service Diagnosis ··············· Page 41
Service Diagnosis ··············· Page 42
Controller Features & Last Error Recall ···· Page 43
Operational Characteristics 1300 lb system · · Page 44
Operational Characteristics 1600 lb system · · Page 45
Refrigeration System Service ········· Page 46
Note this symbol when it appears. It
indicates a potential hazard.
Configuration:
A remote low side cuber system includes several
sub systems: an ice making section, a remote
compressor package, and a remote air cooled
condenser. Additionally, there are two models of
each sub-system and this manual covers all of
them.
The ice making sections are designed for use
indoors in a controlled environment. The remote
compressor packages and condensers are
designed to operate outdoors. Each sub-system
has limits for power, water and temperature.
Operational Limitations:
Minimum Maximum
Air Temp (IMS) 50
o
F 100
o
F.
Air Temp (CU) -20
o
F. 120
o
F.
Water Temp 40
o
F. 100
o
F.
Water Pressure 20 psi 80 psi
Voltage (IMS) 104 126
Voltage (CU) 198 253
IMS = Ice Making Section, CU= Condensing Unit
Do Not operate the machine in conditions beyond
these limitations. Doing so will void the warranty.
Scotsman ice systems are designed and
manufactured with the highest regard for safety
and performance. They meet or exceed the
standards of UL and NSF.
Scotsman assumes no liability of responsibility of
any kind for products manufactured by Scotsman
that have been altered in any way, including the
use of any part and/or other components not
specifically approved by Scotsman.
Scotsman reserves the right to make design
changes and/or improvements at any time.
Specifications and design are subject to change
without notice.
Warranty
Refer to the warranty coverage in effect when the
equipment was sold. Warranty statements are
included with each product.
Systems:
Each sub-system is a separate entity that carries
its own model and serial number. They must be
combined to create a remote cuber low side
system.
Eclipseä 1300, 1600
September 2003
Page 2
System Model
Number
Condensing Unit (CU) Ice Making Section (IMS)
Compressor Package Condenser
Model Electrical Model Electrical Model Electrical
Eclipse 1300-42 CP1316-32A 208-230/60/1
ERC1086 -32A 208-230/60/1 CME1386RLS-1A 115/60/1
Eclipse 1300-43 CP1316-3A 208-230/60/3
Eclipse 1600-42 CP1316-32A 208-230/60/1
ERC1086-32A 208-230/60/1 CME1686RLS-1A 115/60/1
Eclipse 1600-43 CP1316-3A 208-230/60/3
Notes: Voltage Codes are at the end of the model number. Codes read Voltage/Hertz/Phase. Those related
to these products include:
-1 = 115/60/1
-3 = 208-230/60/3
-32 = 208-230/60/1
-42 = 115/60/1 and 208-230/60/1 (separate units)
-43 = 115/60/1 and 208-230/60/3 (separate units)
System Information
Pre-charged tubing kits are required to
interconnect the IMS to the CP.
Interconnecting 24 volt control wire ships with the
CP unit.
Technical Specifications
Ice Making Section (IMS)
Compressor Package (CP)
Condenser
* * ERC condenser fan motor is powered from CP
unit and the ERC’s ampacity is included in CP unit
numbers.
Note: The ERC1086 does NOT contain a
headmaster. The headmaster is in the CP units.
Note: 75 feet of interconnecting control wire (24
volt) is included with the CP units.
Eclipseä 1300,1600
September 2003
Page 3
Model Voltage Minimum Circuit
Ampacity
Max Fuse Size Cabinet Size Weight (lb)
CME1386RLS-1A 115/60/1 3 15 30”w x 24”d x 28”h 144
CME1686RLS-1A 115/60/1 3 15 same 154
Model Voltage Contains
Headmaster?
Minimum
Circuit
Ampacity
Max
Fuse
Size
Refrigerant
Charge (R-404A)*
Cabinet Size Weight
(lb)
CP1316-32A 208-230/60/1 Yes 24.3 30 18 lb 29 ¾”wx18dx3”h 180
CP1316-3A 208-230/60/3 Yes 15.3 20 18 lb same 180
* Includes entire system charge.
Model Voltage Contains
Headmaster?
Number
of
Circuits
Minimum
Circuit
Ampacity**
Max
Fuse
Size**
Cabinet Size, with legs Weight
(lb)
ERC1086-32A 208-230/60/1 No 1 1.25 15 29 ¾”w x 28 5/8”d x 38 ½”h 95
Model Number Locations
Ice Making Section
The dataplate on the back of the ice machine
contains the model number, serial number and
electrical data.
A second plate, located behind the front panel at
the lower left front, also lists the model and serial
numbers.
Compressor Package
The dataplate on the right side of the
compressor package contains the model
number, serial number, electrical data and
system refrigerant charge.
A second plate, located behind the front
panel in front of the compressor, also lists
the model number, serial number and
refrigerant charge.
Condenser
The dataplate lists the condenser’s
electrical information plus the model
and serial numbers.
On the ERC1086 it is located on the side
opposite the refrigeration connections.
Eclipseä 1300, 1600
September 2003
Page 4
Dataplate
location for
CP Unit
Dataplate
location for
ERC1086
Dataplate
location for
Ice Making
Section
Cabinet Drawings, Ice Making System
Eclipseä 1300,1600
September 2003
Page 5
17.08
2.53
4.85
17.31
TOP VEIW
ICEDROPAREA
TOP ACCESS
REFRIGERANT
LINE SETS
UTILITY CHASE
30.00
3.02
1.90
15.76
5.19
REAR VEIW
WATER INLET
3/8" FLARE
DRAIN
3/4" PVC
FEMALE
REFRIGERANT
LINE SETS
CONNECTIONS
24.00
3.18
Thermostat
Routing Hole,
13” from front,
4.63” from side
Cabinet Drawings, Compressor Package and Condensers
Eclipseä 1300, 1600
September 2003
Page 6
BACK VIEW
FRONT VIEW
RIGHT SIDE VIEW
1/2" COOL VAPOR LINE
0.88 ELECTRICAL INLET
3/4" SUCTION LINE
INTERFACE HARNESS
ACCESS HOLE
3/8" CONDENSER LIQUID LINE (OUT)
1/2" C
O
NDENSER DISCHARGE LINE (IN)
CONDENSER FAN WIRE ROUTING
ERC680 or ERC1086:
This Side Attaches to
CP1316
27.90
28.53
35.72
2.75
Liquid Line
Discharge
Line
29.50
38.47
33.19
6.68
22.51
29.19
9/16” Mounting Hole
9/16” Mounting Hole
23.5”
1.5”
1.5”
3/8" LIQUID LINE
15”
1.5”
1.5”
Proper Combinations:
The three sub systems are designed to be
connected together in certain combinations to meet
the user’s needs:
Eclipse 1300 System:
·
CME1386, CP1316, ERC1086
Eclipse 1600 System:
·
CME1686, CP1316, ERC1086
ERC1086 may be substituted for by an approved
central condenser coil & fan (coil must be without
headmaster - headmaster is part of CP1316).
Condenser coil internal volume target is 165 cubic
inches, BHTU target is 42,000 BTUH.
Note: The ice making section cannot be stacked
vertically.
Accessories such as bin adapters and tubing kits
are required to complete the installation.
Dispenser Adapter Kits:
·
Scotsman ID200 or ID250: KBT44
Note: Dispensers with two rotors. If possible, the
ice making head should NOT be centered left to
right between the two rotors. It should be shifted
slightly to one side, and the agitation should be
minimized.
Bin Adapter Kits:
·
BH800: KBT23
·
BH801: KBT29
·
BH900: KBT22
Tubing Kits:
·
20 foot: 3RTE20
·
35 foot: 3RTE35
·
50 foot: 3RTE50
·
75 foot: 3RTE75
·
Suction Line Trap: KSLT075
·
Interconnecting Tubing to Approved Rack
Condenser Coil: RTE10
·
Line end kit: KTE6
Items required for installation:
·
Ice making section
·
Compressor Package (includes interconnecting
control system wire)
·
Remote condenser or approved rack coil
w/tubing kit
·
20’, 35’, 50’ or 75’ triple line set (liquid, vapor
and suction)
·
Bin or dispenser adapter
Special Considerations
The ice making section’s footprint is 30” wide by
24” deep. The refrigeration connections can be
made out the top panel or out the back. The
electrical power cord and the water inlet line can
also be routed through either of those areas. The
drain may be routed out the back or to the left side.
The bin thermostat, when deployed, will be about
5” below the bottom of the cabinet, and that is
where the ice will fill to. This ice level maximizes
ice storage without overfilling the bin or dispenser.
Water
Pure water does not exist. All water supplies
contain some amounts of impurities, although
potable water is, by definition, fit for human
consumption. Because the contents of the water to
an ice machine directly impact its performance,
consideration should be given to improving the
water’s quality.
There are two ways water can contain impurities:
in suspension or in solution. Suspended solids can
be filtered out of the water. In solution or dissolved
solids must be diluted or treated. Water filters are
recommended to remove the suspended solids.
Some filters or filter systems have treatment
chemicals in them for treating the suspended
solids.
This ice machine has an adjustment for the amount
of water rinsed or purged. Water use adjustments
are customer convenience adjustments; they are
not factory defects and are not covered by
warranty.
Eclipseä 1300,1600
September 2003
Page 7
Create the System
Plan the installation. The system consists of four
parts: the ice making section, the compressor
package, the interconnecting tubing and the
remote condenser. Of these, the biggest variable is
the interconnecting tubing.
Tubing: The tubing consists of three pre-charged,
insulated and sealed soft copper tubes. They each
contain a small holding charge of R-404A. One
tube, the liquid line, is 3/8” OD. The vapor tube is
½” OD and the suction tube is ¾” OD. A site
inspection will determine what length of tubing is
required for the installation.
Excess tubing must be either shortened at the job
site (recovering the holding charge, purging with
nitrogen when brazing and evacuating to 50
microns) or coiled up inside the building.
Installations with greater than 20 feet of vertical lift
between ice machine and the compressor require
a suction line trap. The suction line requires careful
handling and large radius bends to prevent kinking.
Roof mounting: To make installation easier the
compressor and condenser are designed to be
assembled together on the roof. Some
installations will require the use of a hoist to lift the
components to the roof.
Pad mounting: The compressor and condenser
may be located below the ice making section, up to
a limit of 15 feet.
Distance from unit: Limited to the length of the
available pre-charged tubing.
Elevation: CP unit limited to 35 feet above the ice
making section.
Compressor package: Electrical power must be
supplied to the compressor package. The remote
condenser fan motor takes its power from the
compressor package.
Ice making section location and attachment:
The 115/60 Hz ice making section is cord
connected and requires an outlet within 6 feet of
the installation.
Interconnecting wires: An interconnecting wire
harness is included with the CP unit. One end
plugs into the ice making section and the other into
the compressor package. The system will NOT
operate without this harness.
Exposed tubing: Minimize the amount of tubing
exposed outdoors.
Confirm Component Availability:
·
CME1386 or CME1686
·
CP1316
·
ERC1086 unless connecting to an approved
condenser coil.
Note: Only these condensers may be used. They
do NOT contain a headmaster valve. That valve is
in the Compressor Package. Do NOT use any
other Scotsman condenser. Do NOT use these
condensers on any other Scotsman remote
product.
·
Interconnecting tubing kit
Note: Check tubing integrity before assembly by
attaching a refrigeration compound gauge onto one
of each tube’s schrader valves. If there is pressure,
the tube is OK, if not it should be checked for
damage and leaks.
·
Bin or dispenser adapter
Eclipseä 1300, 1600
September 2003
Page 8
System Examples
The Eclipse system can be installed on a bin or
dispenser. The CP unit can be installed on either a
single circuit condenser or onto a coil in a separate
rack condenser.
Separate coils must be:
·
Scotsman approved
·
The correct size and capacity
·
New or not have been part of a system that
used mineral oil.
Eclipseä 1300,1600
September 2003
Page 9
System on Ice Storage Bin
System on Ice Dispenser
System Examples
A variation of the typical system set up is one that
uses a non-Scotsman condenser. In that case the
CP unit is NOT bolted to the condenser and a
RTE10 line set is used to connect the refrigeration
system to the condenser’s coil.
Eclipseä 1300, 1600
September 2003
Page 10
IMS on Bin, CP Unit Connected to Approved Central
Condenser Coil
Place Remote System
Roof preparation
Most installations of this system will place the
compressor package and condenser on the roof of
a building. The roof must be physically stout
enough to accept the load of the equipment and
the roofing material must be prepared to prevent
water leaks.
Follow local codes for the placement and
attachment of the equipment.
Location
The air cooled condensing unit assembly requires
unobstructed air flow to operate efficiently. A four
foot space between each intake side and a wall or
other cabinet is recommended. Provide at least 2
feet of space above the air cooled condenser for
proper air flow.
Do not place where the air cooled condenser will
pick up hot discharged air from an air conditioner
or other refrigeration system condensing unit.
Space must also be reserved for service on the
compressor package.
Roof Piercing:
The roof (or wall) must have a passage large
enough for the three pre-charged, pre-bent tubes
and the control wire to pass through. The minimum
recommended size is 4” ID. In most areas the
power supply may also pass through the same
passage. If there isn’t a passage one must be
created. In most cases this must be done by a
licensed and bonded roofer in order to maintain the
roof’s integrity.
Suggestions:
Hoist the compressor package and condenser to
the roof in separate loads.
Note: In most cases a mechanical lift, boom truck
or crane will be required to hoist the condensing
unit components.
Assemble the compressor package to the
condenser and mount both to either roof rails or
pressure treated4x4s.
Orient the assembled unit so that the unit’s mounts
are parallel to the pitch of the roof to allow water to
drain freely.
Do NOT place the unit directly onto roof rock.
Eclipseä 1300,1600
September 2003
Page 11
System Location
Limitations:
Distance: Limited to the maximum length of a
single pre-charged tubing kit, 75 feet.
Condensing Unit Elevation over Ice Making
Section: 35 feet.
Note: Elevations greater
than 20 feet require
installation of a suction line
trap at the 20 foot mark.
Ice Making Section
Elevation over Condensing
Unit: 15 feet.
Line Routing:
·
Allowed: One rise after a drop.
·
Allowed: One drop after a rise.
·
Not Allowed: More than one rise after a drop
·
Not Allowed: More than one drop after a rise.
Eclipseä 1300, 1600
September 2003
Page 12
22.87"
17.15"
40.35"
Condensing Unit Distance Schematic
Max Rise:
35 Feet
Max Drop:
15 Feet
Max Length -
Limit of Line Set
Condensing
Unit Located
Below Ice
Machine
Condensing
Unit Located
Above Ice
Machine
S-Trap
Route Tubing
Scotsman’s pre-charged tubing kits are pre-bent to
fit the connection path at the ice making section.
·
If the tubing is to be routed out the back, use
the double-bend ends.
·
If the tubing is to be routed out the back and
then up, use the ends with the single 90
degree bends.
Note: Units mounted flush against the wall require
refrigerant connections out the top, water supply in
from the top, power supply routed through the top
and drain routed to the left side.
Select the correct end to send to the roof.
The method or technique used to route the tube is
left to the installer. However, in many cases it is
easier to position the tubing inside the building first,
then feed the outside portion through the tubing
passage (pitch pot). Installation of tubing will be
easier if the suction line is run first, followed by the
liquid and vapor lines. Use of two persons is
suggested to prevent kinking of the tubing, long
runs may require three people.
·
Allow enough tubing to make large radius bends
from the roof passage to the compressor unit.
Do NOT leave excess tubing on the roof.
·
If a trap must be installed, the suction line
tubing must be cut apart to install it.
·
Identify the ice machine end of the tubing. Each
tube has one end formed to route through the
hole in the unit’s top.
·
Tape the ends of the vapor and liquid line tubes
together along with the interconnecting wire.
Extend the end of the interconnecting wire
about 2 feet beyond the end of the precharged
tubes and then tape it back onto the tubes.
·
Route the three tubes and the wire from the
roof, or other entrance, to the ice making
section’s planned position. Avoid uncoiling and
recoiling the tubing, as that can lead to kinks.
·
Support long runs of tubing with hangers.
·
Repair any tears in the tubing insulation,
especially those on the suction line that are
inside the building.
Shortening Tubing
The precharged tubing kits are available in a
variety of lengths, they should only be shortened if
absolutely necessary.
To Shorten Tubes:
1. Recover the 3 ounce R-404A holding charge
from each tube.
2. Cut out the required length of tubing, do not cut
the tubing right at the quick connects.
3. Attach nitrogen bottle to one quick connect and
a hose with a depressor to the other end, purge
nitrogen through each tube while brazing.
4. Remove nitrogen, evacuate to 200 microns.
Note: If tubes are connected to the IMS, evacuate
the vapor & suction lines to get the entire system.
Eclipseä 1300,1600
September 2003
Page 13
Suction
Vapor
Liquid
Suction
Vapor
Liquid
Ice Making Section
The CME1386 and CME1686 are similar in layout.
They differ in evaporator count, controller, float
stem and vapor inlet valve.
Major Components:
TXV - one feeding a refrigerant distributor
Water Pump - same for both models
Water Level Sensor - signals reservoir water level
to the controller
Controller - operates both the ice machine section
and the compressor unit.
Drain Valve - opens to allow pump to drain the
reservoir
Water Inlet Valve - 2.77 GPM solenoid valve that
opens to fill the reservoir
Low Side Access Valve - allows connection for
diagnosis of ice machine section refrigeration
operation. Not for recovery.
Liquid, Vapor and Suction
Connections - where the
pre-charged tubing kits
connect to.
Eclipseä 1300, 1600
September 2003
Page 14
Water
Pump
Water
Level
Sensor
Drain Valve
Water Inlet
Solenoid
Valve
Freezing
Compartment
Low Side
Access Valve
Vapor
Connection
Liquid
Connection
Suction
Connection
TXV
Controller
Front Ice
Sensor
Bin
Thermostat
Vapor Inlet
Valve
Compressor Package
Both compressor packages are similar in layout,
they only differ in compressor and charge.
Major Components:
CPR Valve - limits refrigeration pressures
inside the dome of the compressor.
Condenser By Pass Valve - opens during
harvest to allow discharge gas to flow to the
vapor line.
Headmaster - maintains a minimum
discharge pressure during freeze
Liquid Inlet Valve - Normally Open, closes
during harvest.
Receiver - stores liquid refrigerant for
freeze and provides vapor for harvest
Suction Access Valve - provides a place to
attach a refrigeration manifold for diagnostics
and recovery.
Eclipseä 1300,1600
September 2003
Page 15
CP Unit Refrigeration Connection ID
Power
Routing Hole
Vapor Line
Connection
24 volt comm line
Routing Hole
Liquid Line
Connection
Suction Line
Connection
Liquid from
Cond.
Discharge to
Cond.
Condenser
Wire Routing
Hole
CP Component Location
CPR Valve
Liquid
Access
Valve
Headmaster
Condenser By
Pass Valve
Hi
Pressure
Cut Out
Liquid Inlet
Valve
Receiver
Suction
Access
Valve
Condensing Section Assembly
(CP1316 to ERC1086):
1. Remove cartons from compressor package and
condenser.
2. Remove top from both units.
3. Remove front panel from CP unit.
4. Locate legs, secured to ERC unit.
5. Locate fasteners, inside junction box of ERC
unit.
6. Assemble rear legs to ERC using fasteners from
prior step.
7. Locate wire package in CP unit. Remove short
wires and two wire nuts.
8. Use wire & wire nuts from step 7 to connect to
the wires inside the junction box of the condenser.
Return junction box cover to its original position.
9. Place front of ERC on back flange of CP unit.
10. Secure CP unit to ERC.
11. Attach leg brace between ERC unit and CP
unit.
12. Route wires from condenser through hole in
back of CP unit to the CP unit control box.
13 Pull ERC female refrigerant connections
forward to engage male connections on CP unit.
14. Rotate swivel nuts to tighten refrigerant
connections. Use a back up wrench to hold female
connection to prevent tearing of the diaphragms.
15. Connect wire to T1 and T2 of the contactor.
Use the two wire nuts to connect the other end to
the two black wires in the condenser junction box.
16. Return tops to their original positions.
Eclipseä 1300, 1600
September 2003
Page 16
CP Unit Contactor, Three Phase Shown
Connect
Fan Motor
Leads
Connect
Power
Here
Rotate Swivel
Nuts to Connect
Condenser
System to
Compressor
Unit
Locate
Fastener
Package
Condensing Section Assembly
Alternate Assembly:
The CP unit may be connected to an approved
condenser coil in a central condenser rack. In
those cases, the CP unit must be connected to the
condenser coil using special kit RTE10.
Position the CP unit in its final spot. It must be
within 6 feet of the condenser coil connections.
Route tubing from kit RTE10 from the CP unit to
the condenser coil.
Connect tubing per the Coupling Instructions in this
manual.
No wire connection is required between the CP
unit at the condenser.
Note: Approved condensers must maintain power
to their fan motor at all times.
Note: For local codes requiring a pressure relief
valve: Recover charge and connect valve to
receiver liquid outlet tubing.
All Assemblies:
Route interconnecting control wire through proper
hole in side of CP unit and plug into the connection
on the bottom of the control box.
Route power conduit (liquid tight) and wires to the
hole in the side of the CP unit. Secure with the
proper type of connector.
Note: The power supply wires must be the correct
size and type per the National Electric Code.
Locate the nameplate on the CP unit for the
Voltage, Phase, Minimum Circuit Ampacity and
Maximum Fuse Size. Either fuses or HACR type
circuit breakers may be used.
Follow all Local, State and National Codes.
Connect power wires to the contactor, L1 and L2 if
single phase, L1, L2 and L3 if three phase. Note: If
there is a “wild leg” in the three phase power
supply place it on L3.
Connect electrical power to the CP unit.
Return front of CP unit to its original position.
Eclipseä 1300,1600
September 2003
Page 17
Control Wire Connection in CP Unit
Interconnecting
Control Wire Plug
CP Unit Contactor, Three Phase Shown
Connect
Power
Here
Connect
Fan Motor
Leads
Approved
Central
Condenser
Unit
Scotsman
Condensing
Unit
Ice making section:
Remove from carton.
Remove all panels.
Utility Connection Route:
Electrical: The unit is supplied with a power cord.
The power cord can be routed out the back, left
side or top. There is also an interconnecting control
wire that must be routed between the ice making
head and the CP unit. That wire can be routed out
the back or top.
Water Supply: The water supply can be routed
from the top, back or left side.
Drain: The drain can be routed out the back or the
left side.
Refrigeration Tubing: The tubing can be routed out
the top or the back.
Adapters:
In many cases an adapter kit will be required when
placing the head unit on a bin or dispenser. See
sales information for the correct kit. Place adapter
kit onto bin or dispenser top. If adapter does NOT
have gasket tape install tape such as Scotsman
part number 19-0503-04.
Attachment:
If the unit is a direct fit, place it on the bin. If the
unit is in a position that it need not be moved to
complete the installation, secure it to the bin with
the hardware provided with the head unit.
On some bins or dispensers it may be necessary
to drill small holes and use field supplied sheet
metal screws to secure the ice making head to that
bin, dispenser or adapter.
Control Wire
Plug the interconnecting control wire into the
harness at the back of the head unit’s electrical
box.
Eclipseä 1300, 1600
April 2003
Page 18
Ice Making Section Control Wire Connection
IMS Shown on Ice Dispenser
Control
Wire
Connector
Electrical Box in
Ice Making Head
Bin Thermostat - Routing
Install the bin thermostat after the ice making
head has been placed on the bin or dispenser.
Note: Dispensers may require special attention to
keep ice or agitator/sweep arm from moving the
thermostat from its installed position. Place the
head on the dispenser and install the thermostat
before connecting refrigerant tubing.
Before starting, remove the left side and front
panels and any baffle in the bin.
1. Locate bin thermostat bulb.
2. Route bulb thru routing tube (located behind the
reservoir).
3. Locate bin thermostat bracket.
4. Carefully position the thermostat bulb on the
bracket (see the diagram on the next page).
5. Fasten the bracket to the bottom of the ice
machine with the two 3-pronged knob head screws
supplied with the unit.
6. Pull back into the ice machine any excess
capillary tubing.
7. Return the baffle to the bin and continue with the
installation.
Note: If the machine is located at an altitude higher
than 2,000 ft., adjust the thermostat by removing
the plastic cover and rotating the adjustment screw
per the table.
Eclipseä 1300,1600
September 2003
Page 19
Bin Thermostat Altitude Correction Table
CW Turns of Range Screw (under plastic cover)
Feet Turns Feet Turns
2000 55
o
8000 340
o
4000 160
o
9000 385
o
6000 250
o
10000 405
o
Bin
Thermostat
Bulb
Thermostat
Bulb Routing
Tube
Bin Thermostat - Bracket & Bulb
Eclipseä 1300, 1600
September 2003
Page 20
Attach Thermostat Bulb to Bracket
Mount Bracket to Bottom of ice Head
Bracket
Thermostat
Capillary Tube
Insert Tip into
Hole
Snap Tube
Through Slot
Bulb
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46

Scotsman CME1686RLS User manual

Category
Ice cube makers
Type
User manual
This manual is also suitable for

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI