Danfoss EvoFlat Operating instructions

Type
Operating instructions
InstallationGuide
EvoFlat
1.0TableofContents
1.0TableofContents.............................................1
2.0Safetynotes.....................................................2
2.1SafetyNotesgeneral............................................2
3.0Mounting........................................................3
3.1Mounting...........................................................3
3.2Start-up..............................................................4
3.3Electricalconnections.............................................5
4.0Design.............................................................6
4.1Design,A............................................................6
4.2Schematic,Adiagram.............................................7
4.3Design,Std..........................................................8
4.4Schematic,Std.diagram..........................................9
5.0Controls..........................................................11
5.1Controls.............................................................11
5.2Maintenance........................................................15
6.0Troubleshooting..............................................16
6.1Troubleshootingingeneral......................................16
6.2TroubleshootingDHW............................................16
6.3TroubleshootingHE...............................................17
6.4Disposal.............................................................18
7.0Declaration......................................................19
7.1Declarationofconformity........................................19
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
1
InstallationGuideEvoFlat
2.0Safetynotes
2.1SafetyNotesgeneral
Thefollowinginstructionsrefertothestandarddesignof
substation.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedtobeconnectedtodecentralized
heatinginstallationswithvariousenergysources,suchasdistrict
heating,centralboiler(gas,oil,biomass,etc.),solar,heatpumpora
combinationbetweenthemiftheoperatingconditionsallowit.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed80%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallationspermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
95°C.
Themaximumoperatingpressureofthesubstationis10bar.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.Checkthatallhairpinsinclickconnections
arecompletelypushedin.
2
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
3.0Mounting
3.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
HeatSource(HS)-Inthefollowingsections,HSreferstotheheat
sourcewhichsuppliesthesubstations.Avarietyofenergysources,
suchasoil,gasorsolarpower,couldbeusedastheprimarysupply
toDanfosssubstations.Forthesakeofsimplicity,HScanbetaken
tomeantheprimarysupply.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
3.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Thightening
Duetovibrationduringtransport,allsubstationconnections
mustbecheckedandtightenedbeforeinstallation.Checkthatall
hairpinsinclickconnectionsarecompletelypushedin.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Connectiontothehouseholdinstallationanddistrictheatingpipes
connectionsmustbemadeusingthreaded,angedorwelded
connections.
Theinternalconnectionsofthesubstationismadebyclick-t
connections(see5.1.11).
Keyholeformounting.
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
3
InstallationGuideEvoFlat
3.2Start-up
Start-up,Directheating
Theshut-offvalvesshouldbeopenedandtheunitobservedas
itentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.Checkthatall
hairpinsinclickconnectionsarecompletelypushedin.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.Checkthatallhairpins
inclickconnectionsarecompletelypushedin.
Start-up,Heatingwithmixingloop
Start-up:
1:Pumpspeed
Setthepumptoitshighestspeedofrotationbeforestart-up.On
radiatorsystems,theselectorswitchisnormallysetin“Variable
curve/Proportionalcurvesetting,inmax.pos. .Foroorheating
systems,theselectorswitchisnormallysetinConstantcurve
setting,inmax.pos. .
2:Startpump
Startthepumpandheatthroughthesystem.
3:Openshut-offvalves
Theshut-offvalvesshouldthenbeopenedandtheunitobserved
asitentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Ifthesystemoperatesinaccordancewithdesign,itcanbeput
toregularuse,-alwaystakingintoaccounttheconditionsinthe
building.
4:Ventsystem
Switchoffthepumpandventtheinstallationafterthesystemhas
beenwarmedup.Pleasenotethatsomepumptypesfeaturea
built-inventingfunction.Forotherstheinstallationcanbevented
byusingaventvalveinthesubstationorontheradiators,or,if
appropriate,theairvalveatthehighestpointofthesystemFor
additionalinformation,pleasereferstotheenclosedpumpand
manual.
5:Adjustpumpspeed
Setthepumptothelowestpossibleposition,dependingonthe
heatingrequirementforthebuilding-takingintoaccountaspects
suchascoolingandpowerconsumption.
Iftheheatingrequirementincreasesthepumpsettingcanbe
changedbymeansoftheselectorswitch.Pleaserefertothe
enclosedinstructionmanualfordetailedinformationaboutsetting
ranges.
Inthesummer,youcanswitchoffthepowertothepumpatthe
mainsifyouwanttosaveelectricitybynotheatingyourhome.It
shouldbeensuredthatnoinappropriatehydraulicsituationwill
occur,whenthepowertoyourpumpisturnedoff.
Forstart-upandventingseeaboveandtheenclosedpump
manual.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.Checkthatallhairpins
inclickconnectionsarecompletelypushedin.
Pump
Thepumpmustbeswitchedoffduringsystemll.
4
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
3.3Electricalconnections
Beforemakingelectricalconnections,pleasenotethe
following:
Safetynotes
Pleasereadtherelevantpartsofthesafetynotes.
230V
Thesubstationmustbeconnectedto230VACandearth.
Disconnection
Thesubstationmustbeelectricallyconnectedsothatitcanbe
disconnectedforrepairs.
Grounding/potentialcompensation
Thestationshouldbeconnectedtoagroundingpointontheright
sideofthestationmountingrail.
Authorizedelectrician
Electricalconnectionsmustbemadebyanauthorizedelectricianonly.
Localstandards
Electricalconnectionsmustbemadeinaccordancewithcurrent
regulationsandlocalstandards.
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
5
InstallationGuideEvoFlat
4.0Design
4.1Design,A
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
FSSA26-40(leftphoto)
MSSA26-40(rightphoto)
2
Plateheatexchanger
2
Plateheatexchanger
5
Strainer
5
Strainer
21
Returntemperaturelimiter
6
Checkvalve
23
Sensorpocket
10
Circulationpumpmixingcircuit
24
Fittingpiece,energymeter
23
Sensorpocket
38
Hotwater/dpcontroller
24
Fittingpiece,energymeter
40
Summerby-pass
29
Actuator
58
Fittingpiece,watermeter
30
ValveHE
59A
Fittingpiece,watermeter
38
Hotwater/dpcontroller
59BFittingpiece,watermeter
40
Summerby-pass
64
Flowlimiter
54
Safetyswitch
58
Fittingpiece,watermeter
59A
Fittingpiece,watermeter
59BFittingpiece,watermeter
64
Flowlimiter
6
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
4.2Schematic,Adiagram
FSSA26-40
DHW
DCW
DCW
HS
Supply
HE
Supply
HS
Return
HE
Return
MSSA26-40
DHW
DCW
DCW
HS
Supply
HE
Supply
HS
Return
HE
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
7
InstallationGuideEvoFlat
4.3Design,Std.
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
FSS26-40(leftphoto)
MSS26-40(rightphoto)
2
Plateheatexchanger
2
Plateheatexchanger
5
Strainer
5
Strainer
21
Returntemperaturelimiter
6
Checkvalve
23
Sensorpocket
10
Circulationpumpmixingcircuit
24
Fittingpiece,energymeter
23
Sensorpocket
38
Hotwater/dpcontroller
24
Fittingpiece,energymeter
40
Summerby-pass
29
Actuator
59
Fittingpiece,watermeter
30
ValveHE
38
Hotwater/dpcontroller
40
Summerby-pass
59
Fittingpiece,watermeter
8
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
4.4Schematic,Std.diagram
FSS26-40
DHW
DCW
DCW
HS
Supply
HE
Supply
HS
Return
HE
Return
MSS26-40
DHW
DCW
DCW
HS
Supply
HE
Supply
HS
Return
HE
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
9
InstallationGuideEvoFlat
4.4.1EVOFlatTechnicalparameters
Technicalparameters
Nominalpressure:FSSPN10/PN10andMSSPN6/PN10
Max.DHsupplytemperature:
95°C
Min.DCWstaticpressure:
1.0bar
Brazingmaterial(HEX):
Copper
Heatexchangerstestpressure:25bar
10
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
5.0Controls
5.1Controls
5.1.1TPCmultifunctionalcontroller
Multifunctionalcontrollerwithintegratedzonevalve,airvent,
differentialpressureandDHWtemperaturecontroller.
DHWtemperaturecontrol
Byturningthehandlefortemperaturetemperaturein(+/MAX)
directionthetemperatureisincreased,byturningitin(-/MIN)
directionthetemperatureisdecreased.
Settingrange40-60°C.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilizationofDHwater.AtDHWtemperaturesabove55°C
thepossibilityoflimescaledepositsincreasessignicantly.
Differentialpressurecontroller
Thedifferentialpressurecontrollerequalizesthehighuctuations
inpressurearrivingfromtheheatsource,ensuringconstant
operatingpressure
Zonevalve
Thestationissuppliedwithazonevalveandthusprepared
formountingofathermalactuatorTWA-ZNC,whichenables
connectionofanelectronicprogrammableroomthermostat
TP7000.
5.1.2Airvent
Airvent
Thestationshouldbeventedduringstartup.
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
11
InstallationGuideEvoFlat
5.1.3TP7000
TP7000electronic7dayprogrammableroomthermostat.
Signalsfromtheroomthermostatcanbeusedtocontrolzone
valves.
Note:Beforemountingofelectronicprogrammableroom
thermostat,thermoactuatorTWA-ZNCmustbemountedonthe
zonevalve.
5.1.4Strainer
Strainersshouldbecleanedregularlybyauthorizedpersonnel.The
frequencyofcleaningwoulddependonoperatingconditions.
5.1.5Summerbypass
Thebypassthermostatisdesignedtokeepthesupplylinewarm.
Settingrange:10-50°C.
Scalesetting(indicative).
Factorysetting2,5.
12
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
5.1.6Mixingloop
Themixingloopcreatesasuitabletemperaturelevele.g.foroor
heating.
5.1.7FTCcontrol
TheFTCcontrolsthemixingloopHEsupplytemperature.
Settingrange15-50°C.
Thesettingvaluesmayvarydependingontheoperating
conditions.Itisimportanttosetthesupplytemperaturetothe
radiatorsaslowpossible.
NB!Forhousesthatareheatedexclusivelywithoorheating.
ALWAYSrefertotheinstructionsfromtheoorsupplier.
Factorysetting:50°C.
5.1.8Safetythermostat
ThesafetythermostatwillshutthezonevalveiftheHEsupply
temperatureisabove55°C.
5.1.9Safetyvalve
Thepurposeofthesafetyvalveistoprotectthesubstationfrom
excessivepressure.
Theblow-offpipefromthesafetyvalvemustnotbeclosed.The
blow-offpipeoutletshouldbeplacedsothatitdischargesfreely
anditispossibletoobserveanydrippingfromthesafetyvalve.
Itisrecommendedtochecktheoperationofsafetyvalvesat
intervalsof6months.Thisisdonebyturningthevalveheadin
directionindicated.
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
13
InstallationGuideEvoFlat
5.1.10ReturntemperaturelimiterFJVR(10-55°C)
ThereturnlimitertypeFJVRautomaticallycontrolsthereturn
temperaturefromheatingsystem.
Thereturntemperaturelimitershouldbesettotherequired
maximumreturntemperature,incompliancewiththelocal
demands.
Factorysetting:3.
5.1.11Fittingpiece
Thesubstationisequippedwithattingpieceforenergymeter.
Mountingofenergymeters:
1:Closeballvalves
ClosetheballvalvesonDHSupplyandDHReturn,ifthereiswater
onthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththeenergymeter.Do
notforgetthegaskets.
4:Tightenconnections
Aftermountingoftheenergymeterremembertocheckand
tightenallthreadedconnections.
5.1.12Sensorpocket
Sensorpocket,energymeter
Thesensoroftheenergymeterismountedinthesensorpockets.
Thesensorpocketisplacedinthestrainer.
14
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
5.1.13Clickconnection
Theclickconnectioncanbedismantledduringservice.
5.2Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasHSsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
15
InstallationGuideEvoFlat
6.0Troubleshooting
6.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
thesubstationisconnectedtoelectricity,
thestrainerontheHSsupplypipeisclean,
thesupplytemperatureoftheHSisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheHSnetworkifindoubt,ask
theHSplantsupervisor.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
6.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.(onlyifDHWcirculation
isinstalled).
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.
Replaceclean.
Noelectricity.OnlyifstationarewithDHW
circulation.
Check.
Scalingoftheplateheatexchanger.
Replacerinseout.
Defectivetemperaturesensors.
Checkreplace.
ToolittleornoDHW.
Defectivecontroller.
Checkreplace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Checkreplace. Hotwaterinsometapsbutnotinall.
DHWcirculationpumpoutoforderorwith
toolowsetting.(onlyifDHWcirculation
isinstalled).
Replaceclean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.Thermostatisdefect.
Checksetreplace.
Scalingoftheplateheatexchanger.
Replacerinseout.
Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
16
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
6.3TroubleshootingHE
ProblemPossiblecauseSolution
Toolittleornoheat.StrainercloggedinHSorHEcircuit
(radiatorcircuit).
Cleangate/strainer(s).
ThelterintheenergymeteronHScircuit
clogged.
Cleanthelter(afterconsultingtheHS
plantoperator).
Defectivedifferentialpressurecontroller.
Replacemaincontroller,TPC.
Sensordefective.Checktheoperationofthethermostat
cleanthevalveseatifrequired.
Automaticcontrols,ifany,wronglysetor
defective-possiblypowerfailure.
Checkifthesettingofthecontroller
iscorrectseeseparateinstructions.
Checkthepowersupply.Temporary
settingofmotortomanual”controlsee
instructionsonautomaticcontrols.
Pumpoutofoperation.Checkifthepumpisreceivingpowerand
thatitturns.Checkifthereisairtrappedin
thepumphousingseepumpmanual.
Thepumpissetattoolowspeedof
rotation.
Setthepumpathigherspeedofrotation.
Airpocketsinthesystem.Venttheinstallationthoroughly.
Limitingofthereturntemperature
adjustedtoolow.
Adjustaccordingtoinstructions.
Defectiveradiatorvalves.
Checkreplace.
Unevenheatdistributioninbuilding
becauseofincorrectlysetbalancingvalves,
orbecausetherearenobalancingvalves.
Adjust/installbalancingvalves.
Diameterofpipetosubstationtoosmallor
branchpipetoolong.
Checkpipedimensions.
Unevenheatdistribution.Airpocketsinthesystem.Venttheinstallationthoroughly.
HSsupplytemperaturetoohigh.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callautomaticcontrolsmanufactureror
replacetheregulator.
Defectivesensoronself-actingthermostat.
Replacethermostat.
HSsupplytemperaturetoolow.
Defectivecontroller.Thecontrollerdoes
notreactasitshouldaccordingtothe
instructions.
Callinautomaticcontrolsmanufactureror
replacecontroller.
Strainerclogged.Cleangate/strainer.
ToohighHSreturntemperature.
Toosmallheatingsurface/toosmall
radiatorscomparedtothetotalheating
requirementofthebuilding.
Increasetotalheatingsurface.
Poorutilizationofexistingheatingsurface.
Defectivesensoronself-actingthermostat.
Makesuretheheatisdistributedevenly
acrossthefullheatingsurfaceopenall
radiatorsandkeeptheradiatorsinthe
systemfromheatingupatthebottom.It
isextremelyimportanttokeepthesupply
temperaturetotheradiatorsaslowas
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
17
InstallationGuideEvoFlat
possible,whilemaintainingareasonable
levelofcomfort.
Thesystemissinglepipeloop.
Thesystemshouldfeatureelectronic
controlsaswellasreturnsensors.
Pumppressuretoohigh.Adjustpumptoalowerlevel.
Airinsystem.
Ventthesystem.
Defectiveorincorrectlysetradiator
valve(s).Singlepipeloopsystemsrequire
specialone-piperadiatorvalves.
Checkset/replace.
Dirtinthedifferentialpressurecontroller.
Checkcleanout.
Defectivemotorizedvalve,sensoror
automaticcontroller.
Checkreplace.
Noiseinsystem.
Pumppressuretoohigh.Noicefrom
radiatorvalves.
Adjustpumptoalowerlevel.Checkow
direction.
Heatloadtoohigh.
Defectivemotorizedvalve,sensoror
electroniccontroller.
Checkreplace.
6.4Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
18
DEN-LDS
VI.IQ.C3.02
DanfossDistrictEnergy
InstallationGuideEvoFlat
7.0Declaration
7.1Declarationofconformity
7.1.1Category0withelectricalequipment
ECDeclarationofConformity
DanfossRedanA/S
Omega7
DK-8382Hinnerup
Denmark
Declaresonoursoleresponsibilitythatthebelowproducts:
EvoFlat
coveredbythisdeclarationareinconformitywiththefollowingdirectives,standardsandothernormative
documents,providedthattheyareusedaccordingtoourinstructions.
EMCDirective2004/108/EC
DS/EN61000-6-12007.Electromagnetic
compatibilityGenericstandard:Immunityfor
residentialcommercialandlightindustry.
DS/EN61000-6-32007.Electromagnetic
compatibilityGenericstandard:Emissionfor
residential,commercial&lightindustry.
PressureEquipmentDirective97/23/EC
Equipmentcategory:0(article3.3).
MachineryDirective2006/42/EC
EN14121-1.SafetyofmachineryRiskassessment
EN60204-1.SafetyofmachineryElectrical
equipmentofmachinesPart1:General
requirements.
Hinnerup2013.09.05
PlaceanddateofissueFinnMortensen
ThomasBruunHansen
DanfossDistrictEnergy
VI.IQ.C3.02
DEN-LDS
19
InstallationGuideEvoFlat
ProducedbyDanfossA/S©05/2014
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20