■ Introduction
This guide provides reference information when designing NB screens. It does not provide safety
Information. Be sure to obtain the NB-series Programmable Terminal User's Manuals, read and
understand the safety points and other information required for use, and test sufficiently before
actually using the equipment.
(1) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or
otherwise, without the prior written permission of OMRON.
(2) No patent liability is assumed with respect to the use of the information contained herein.
Moreover, because OMRON is constantly striving to improve its high-quality products, the
information contained in this guide is subject to change without notice.
(3) Copyrights and Trademarks
Sysmac and SYSMAC are trademarks or registered trademarks of OMRON Corporation in
Japan and other countries for OMRON factory automation products.
WindowsExcel is a registered trademark or registered trademarks of Microsoft Corporation in
the USA, Japan and other countries.
Company names and product names in this document are the trademarks or registered trademarks
of their respective companies.
Screenshots are used with permission from Microsoft Corporation.
The pictures and graphics of products used in this guide contain image graphics, which may
differ from the actual products.
3
Terms and Conditions Agreement
Warranty, Limitations of Liability
Warranties
Exclusive Warranty
Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship for a
period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron).
Omron disclaims all other warranties, express or implied.
Limitations
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS
WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on
infringement by the Products or otherwise of any intellectual property right.
Buyer Remedy
Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally
shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be
responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products
unless Omron’s analysis confirms that the Products were properly handled, stored, installed and
maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of
any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies
shall not be liable for the suitability or unsuitability or the results from the use of Products in
combination with any electrical or electronic components, circuits, system assemblies or any other
materials or substances or environments. Any advice, recommendations or information given orally or
in writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR
CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED IN CONTRACT,
WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on
which liability is asserted.
OMRON shall have no liability for any losses, damages or other costs incurred directly or indirectly by
DDoS attacks (Distributed Denial of Service), computer viruses or other harmful technical programs,
or unauthorized accesses in the event of any infection of “OMRON products”, installed software, or all
computer devices, computer programs, networks or databases.
Customers must take sufficient measures to (1) protect against antiviruses, (2) data input/output (3)
restore lost data, (4) prevent "OMRON products" and installed software from being infected by
4
computer virus, and (5) prevent unauthorized access to "OMRON products".
Application Considerations
Suitability of Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations
which apply to the combination of the Product in the Buyer’s application or use of the Product. At
Buyer’s request, Omron will provide applicable third party certification documents identifying ratings
and limitations of use which apply to the Product. This information by itself is not sufficient for a
complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness
of the particular Product with respect to Buyer’s application, product or system. Buyer shall take
application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
Programmable Products
Omron Companies shall not be responsible for the user’s programming of a programmable Product,
or any consequence thereof.
Disclaimers
Performance Data
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for
the user in determining suitability and does not constitute a warranty. It may represent the result of
Omron’s test conditions, and the user must correlate it to actual application requirements. Actual
performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications
Product specifications and accessories may be changed at any time based on improvements and
other reasons. It is our practice to change part numbers when published ratings or features are
changed, or when significant construction changes are made. However, some specifications of the
Product may be changed without any notice. When in doubt, special part numbers may be assigned to
fix or establish key specifications for your application. Please consult with your Omron’s
representative at any time to confirm actual specifications of purchased Product.
Errors and Omissions
Information presented by Omron Companies has been checked and is believed to be accurate;
however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
5
Contents
Terms and Conditions Agreement ........................................................................ 3
Warranty, Limitations of Liability ............................................................................................. 3
Application Considerations ..................................................................................................... 4
Disclaimers ............................................................................................................................. 4
Related Manuals ............................................................................................. 7
Precautions .................................................................................................... 8
NB Remote Solution ...................................................................................... 9
- Overview .................................................................................................................. 9
Creating and Operating New Functions .................................................... 10
- CSV Import/Export ................................................................................................. 10
-- PT Setting .......................................................................................... 10
-- Related System Memories ................................................................ 11
-- The Number of Data per File ............................................................. 11
-- Regulations for File Names ............................................................... 11
-- Creating Sample Screens and Setting Components ......................... 12
-- Operating the Sample Screens ......................................................... 12
-- Combination Example of CSV Import/Export and FTP Server .......... 14
- Update Graphics .................................................................................................... 16
-- Setting Example ................................................................................ 16
-- Related System Memories ................................................................ 18
-- Operating the Sample Screens ......................................................... 18
-- Combination with FTP Server............................................................ 19
-- Combination with VNC Server ........................................................... 19
- FTP Server ............................................................................................................. 19
-- Setting Example ................................................................................ 20
-- Related System Memories ................................................................ 21
-- Setting and Operation Example of FTP Software ............................. 21
- VNC Server ............................................................................................................ 22
-- Setting Example ................................................................................ 22
-- Related System Memories ................................................................ 23
-- Switching Modes ............................................................................... 23
-- Connection Example to PC Using VNC Software ............................. 24
- Disable Auto Resize ............................................................................................... 25
-- PT Setting .......................................................................................... 25
6
Combination Example of Existing Function and FTP Server .................. 26
- Screenshots and FTP Server ................................................................................. 26
- Logging Function and FTP Server ......................................................................... 27
-- Event History ..................................................................................... 27
-- Data History and Data Log ................................................................ 27
-- Operation Log .................................................................................... 27
Revision History ................................................................................................... 28
7
Related Manuals
The following manuals are related to this manual.
Cat.No.
Model
Manual Name
V106 NB[]Q-TW0[]B
NB[]W-TW[][]B
NB-series Programmable Terminals NB-Designer Operation
Manual
V107 NB[]Q-TW0[]B
NB[]W-TW[][]B
NB-series Programmable Terminals Setup Manual
V108 NB[]Q-TW0[]B
NB[]W-TW[][]B
NB-series Programmable Terminals Host Connection Manual
V109 NB[]Q-TW0[]B
NB[]W-TW[][]B
NB-series Programmable Terminals Startup Guide Manual
8
Precautions
(1) When building an actual system, check the specifications of the component devices of the system,
use within the ratings and specified performance, and implement safety measures such as safety
circuits to minimize the possibility of an accident.
(2) For safe use of the system, obtain the manuals of the component devices of the system and check
the information in each manual, including safety precautions, precautions for safe use.
(3) It is the responsibility of the customer to check all laws, regulations, and standards that the system
must comply with.
(4) All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or
transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or
otherwise, without the prior written permission of OMRON.
(5) The information in this guide is current as of April 2018.
No patent liability is assumed with respect to the use of the information contained herein. Moreover,
because OMRON is constantly striving to improve its high-quality products, the information contained
in this guide is subject to change without notice.
Special information in this document is classified as follows:
Precautions for Safe Use
Indicates precautions on what to do and what not to do to ensure safe usage of
the product.
Precautions for Correct Use
Indicates precautions on what to do and what not to do to ensure proper operation
and performance.
Additional Information
Additional information to read as required.
This information is provided to increase understanding or make operation easier.
Copyrights and Trademarks
Sysmac and SYSMAC are trademarks or registered trademarks of OMRON Corporation in
Japan and other countries for OMRON factory automation products.
Screenshots are used in accordance with Microsoft Corporation guidelines.
Windows is a registered trademark of Microsoft Corporation in the USA and other
countries.
Apple, Apple logo, and iPad Air are registered trademarks of Apple Inc. in the USA and
other countries. App Store is a service mark of Apple Inc.
Android and Google Play are the trademarks or registered trademarks of Google LLC.
Company names and product names in this document are the trademarks or registered
trademarks of their respective companies.
9
NB Remote Solution
- Overview
The following features have been added to NB-DesignerV1. 46.
1. CSV import/export
2. Update graphics
3. FTP server
4. VNC server
5. Disable auto resize
By combining the features 1 to 4 above with NB-series existing features, following operations can be
remotely performed between the machine builder’s PC in designing division and the NB Unit installed
on the site.
Machine builders designing division
1. CSV import/export
Conversion between the CSV and ERP files in the USB memory
2. Update graphics
Dynamic change of graphics
4. VNC server
The NB installed on the site can be remotely monitored and
operated from the machine builder’s PC by using VNC function.
3. FTP server
Remote transfer of CSV files, graphics, etc.
10
Creating and Operating New Functions
- CSV Import/Export
This function copies data in the CSV file inside the USB memory into the ERW area, and writes the data in
the ERW area into the CSV file.
The data in the ERW area will be stored into the external memory in “erp” format with the storage path of
“/exmem/erwx.erp”. (x = 0, 1, 2)
-- PT Setting
1.
Click the [External Memory] tab of
[PT property] and select the [CSV
Import/Export] check box for the
ERW area to be converted.
After selecting the check box, the
[Parameter Setting>>] button will be
enabled.
2.
After clicking the [Parameter
Setting>>] button, dialog on the right
will appear.
[Memory Type]
Set a data type
[Subfolder]
Set a subfolder name where the
CSV file to be converted is stored.
[CSV to ERP Trigger]
Make setting for writing the data in
CSV file into the ERW area. You
can set any trigger type and
address.
[ERP to CSV Trigger]
Make setting for writing the data in
the ERW area into CSV file. You
can set any trigger type and
address.
Refer to
Edit
CSV import/export
Save
Managed by
ordinary software
EXCEL etc.
PLC
ERW
Existing function
Data transmission
component
11
-- Related System Memories
The following system memories are used for this function.
Addresses
Descriptions
LB9221 When this address is ON, ERP is currently being converted to CSV
While this address is ON (conversion in progress), even when the writing
conditions are met, it will be ignored.
It may take several tens of seconds to write data depending on the file size to
be converted. Therefore, if a file size is expected to be large, it is
recommended that you first confirm that the writing processing has been
completed using this address, and then perform the next operation.
LB9231 When this address is ON, CSV is currently being converted to ERP.
While this address is ON (conversion in progress), even when the writing
conditions are met, it will be ignored.
It may take several tens of seconds to write data depending on the file size to
be converted. Therefore, if a file size is expected to be large, it is
recommended that you first confirm that the writing processing has been
completed using this address, and then perform the next operation.
-- The Number of Data per File
The maximum capacity per CSV file is up to 4M word. The number of data that can be saved
in one file varies depending on the memory type you set in [Memory Type].
Memory type
Number of data/files
16 bit signed/unsigned
4194304
32 bit signed/unsigned/Float
2097152
Double
1048576
-- Regulations for File Names
When ERW0 is converted into CSV file, ERW0 is named asERW0_X.csv.”, ERW1 is
“ERW1_X.csv, and ERW2 isERW2_X.csv.”
“X” will be numbered from 0 to 511 according to the memory area.
Additional Information
For NB Designer V1. 46, “X” ranges from 0 to 255. For V1.47 and later, the “X” ranges
from 0 to 511.
When ERW0 memory type is 16 bit, from ERW0 0 to 4194303 are named as ERW0_0.csv”,
from ERW04194304 to 8388607 are named asERW0_1. csv”.
If the data is a sequential number and exists across the boundary of memory area, the CSV
may be divided when outputting. To prevent this, do not set memory area across the
boundary of memory area.
12
-- Creating Sample Screens and Setting Components
As an example, this section uses the following screen that employs buttons for performing
the CSV to ERP” and ERP to CSVconversions and lamps for indicating that the
conversion is in operation.
-- Operating the Sample Screens
1.
Create buttons to perform the addresses
that you registered in [CSV to ERP
Trigger] and [ERP to CSV Trigger] in the
external memory setting.
2.
Set lamp components as follows so that
you can check whethe
r the conversion is
in progress on the NB Unit.
LB9221ERP is being converted to CSV
LB9231
CSV is being converted to ERP
1.
Enter any value in the ERW area, and
press the [ERP->CSV] button.
2.
Return the value in the ERW area to the
original value, and press the
[CSV->ERP] button.
3.
The value that you entered in the step 1
has been read to the CSV file.
13
4.
The CSV file has been saved to
“exmemCSVfolderin the USB
memory.
* The folder name after “exmem” can be
changed from the external folder
settings.
5.
After opening the CSV file, the data will
be stored in the format on the right.
(Left: Excel Right: Text editor)
6.
By using the existing data transmission
component, PLC address can be
transferred to the ERW area, and
transferred from the ERW to the PLC
address.
By combining the data transmission
component with the CSV import / export
function, PLC address can be output in
the CSV format via the ERW area.
7.
Create a function that copies the 5-word
PLC addresses into the ERW area.
8.
Press the Data transfer” button to copy
the PLC addresses into the ERW area,
and then press the [ERP->CSV] button.
9.
The data will be output to the CSV file.
As shown on the right, consecutive PLC
address areas and NB internal
addresses can be output in the CSV
format.
14
-- Combination Example of CSV Import/Export and FTP Server
After copying the CSV file generated by the CSV import/export function to the PC using the
FTP server function, the CSV file can be updated on the PC and copied back to the NB
internal memory ERW area.
As an example, the following procedure shows how to transfer the CSV file onto PC,
process, and overwrite it back to the external memory again. Perform this procedure after
copying the data in the ERW area into the CSV file in the external memory as shown in the
step 9 of Section 4-1-5 Operating the Sample Screens
1.
Access “exmem/csvin which the
CSV file is stored using FTP server
function.
2.
Copy the CSV file namederw0
_0.csvto any folder on your PC.
3.
Modify the contents of the CSV file
that you copied on your PC in the
step 2.
4.
Copy the modified file to the USB
memory.
Ethernet
FTP server
CSV import/export
15
5.
Press the [CSV->ERP] button.
6.
After the conversion is completed,
the data will be updated according
to the value that you modified in the
step 3.
16
- Update Graphics
Previously, the NB Unit needs to be restarted in order to read the graphics used for bitmap
components and lamp components directly from an external memory and display them on the screen.
For NB-Designer Ver.1.46 or later, by turning LB9108 ON, the graphics displayed on the NB screen
called from the external memory can be updated.
Together with FTP server function, graphics can be updated without restarting the NB Unit or
inserting/removing the USB memory.
Additional Information
The formats of the graphics which can be called from external memory are BMP, JPG,
and GIF only, not PNG.
This function cannot be used for models without a USB host port.
-- Setting Example
1.
Specify the graphic in which you
want to use the update graphics
function. Select [Add Graphics] in
the [Draw] menu.
3. Turn ON the system memory!
NB screen
External memory
2. The graphics in the external memory
will be updated.
1. NB refers to graphics of object from
an external memory.
4. NB refers to the graphics of object
from the external memory again.
Reflect!
17
2.
After the [New Graphics] dialog box
appears, set the dialog as follows.
[Name]
Set any name.
In this case, usb1 is set.
[Type]
Select an appropriate type by
checking the file format.
In this case, Bitmap is selected.
[State No.]
Set 1.
[Width]/[Height]
Set the width and height according
to the graph size used.
3.
Select [Load Graphic from External
Memory] by right-clicking in status
editing area.
4.
Select the [Save File in External
Memory] check box on the
[Extended Saving File Setting]
dialog, and enter a file name of the
graphic to be displayed including the
extension in [File Name].
In this case, usb1.jpg is set.
5.
Assign the graphic that you set in
the steps 1 to 4 to the component.
Create a bitmap component and
click the [Graphics] tab, and then
select usb1 that you created in the
step 4.
6.
Create a button for graphic updates.
Set LB9108 to [Address].
18
-- Related System Memories
The following system memories are used for this function.
Addresses
Descriptions
LB9108
When this address is ON, the graphics on the screen will be updated.
After completing the processing, the address turns OFF.
-- Operating the Sample Screens
This section shows the procedure to update graphics by using LB9108.
As an example, this section uses a screen that updates graphics in the USB memory by
pressing the [Update] button.
1.
Prepare two graphics named
usb1.jpg. Place one graphic in the
root folder of USB memory
and inset
it into the NB Unit. Place the other
graphic in any folder on the PC.
2.
After the NB Unit is turned on, the
graphic saved in the root folder of
USB memory will appear.
3.
Remove the USB memory from the
NB Unit and overwrite the graphic
into the root folder of the USB
memory. After overwriting, insert the
USB memory into the NB Unit again.
4.
While the graphic has been
overwritten, the graphic on the NB
Unit has not been updated yet.
5.
The graphic will be updated by
turning LB9108 ON by pressing the
[Update] button.
1. By clicking the [Update] button,
2. The graphic will be updated.
19
-- Combination with FTP Server
Previously, USB memory needed to be removed and inserted in order to change graphics in
the external memory.
In combination with FTP server, NB-Designer Ver.1.46 or later can perform the following;
Update graphics of the remotely installed-machines without going to the site.
Update graphics without removing or inserting the USB memory in the control panel.
For information on how to use FTP server, refer to Section 4-3 FTP Server.
-- Combination with VNC Server
In combination with VNC server, graphics can be remotely updated in real time by pressing
the button for graphic updates of VNC server, which eliminates the need for going to the site
to update graphics.
For information on how to use VNC server, refer to Section 4-4 VNC Server.
- FTP Server
Now, files in the USB memory inserted into the NB Unit can be acquired/ transferred upon request of
the host PC.
Previously, the USB memory needed to be removed and inserted in order to copy the data in the USB
memory to the PC. With this function, removing/inserting the USB memory is no longer required.
FTP transfer
Update graphics
Ethernet
FTP client
Graphics,
parameter etc.
Log file
FTP Server
Ethernet
20
Additional Information
This function cannot be used for models without an Ethernet port or USB host port.
-- Setting Example
Set to enable FTP server from NB-Designer.
Additional Information
A password setting is required for FTP server function. The password only supports
numbers ranging from 0 to 99999999. (The default is 888888)
No restriction on the number of digits as long as it is within the above range.
You can set values start with 0, such as "001234", as a password on the NB-Designer,
however, 0 will be ignored and the password will be set as "1234".
1.
Select the [Enable FTP] check box
on the [PT] tab in [PT property].
2.
Set the password.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29

Omron Programmable Terminals NB-SEries Remote Solution Owner's manual

Type
Owner's manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI