Faster restarts due to smarter power management
The Quick Start feature is available in two configurations,
for use with or without an uninterruptible power supply (UPS):
Quick Start feature without UPS is fast:
• Once emergency power is established, the chiller can restart
as soon as the OptiView
™
control panel reboots (75 seconds)
and the OptiSpeed drive precharges (25 seconds), assuming
coastdown of the compressor has been completed. If
emergency power is available after 15 seconds, the chiller
will restart in 115 seconds after power was lost.
Quick Start feature with UPS is faster:
• The UPS keeps the OptiView and OptiSpeed control circuits
energized and the oil heater operative until the emergency
generator is activated, which eliminates the need for control
panel reboot. The chiller will restart in 60 seconds after
power was lost.
Faster restart restores specified leaving chilled-water
temperature quicker
The Quick Start feature not only minimizes chiller restart time,
it reduces the time required for the re-establishment of the
design leaving chilled-water temperature (LCHWT). The Quick
Start feature utilizes accelerated loading logic, with the inlet
vanes fully open, to re-establish the specified leaving chilled-
water temperature faster. While the actual time to re-establish
the LCHWT will depend on plant design, compressor size, and
operating conditions, a chiller equipped with the Quick Start
option can cut the time by as much as 70%.
LCHWT:
Standard Logic
Setpoint
Quick Start with UPS
10 minutes
12 seconds
3 minutes
2 seconds
Time from power failure (minutes)
Temperature (degrees F)
–2 0 2 4 6 8 10 12
40
42
44
46
48
50
52
54
56
58
60
Standard Chiller
Quick Start without UPS
Quick Start with UPS
249 seconds =
about 4 minutes
115 seconds =
almost 2 minutes
60 seconds
15 sec.
power failure
Length of power failure (seconds)
Time to restart from power loss (seconds)
0 5 10 20 25 30 35
60
40
80
100
120
140
160
180
200
220
240
260
280
300
320
340
Additional steps required if UPS not used
*Coastdown time for a
500-ton chiller
Without UPS With UPS
60 seconds
to restart
with UPS
115 seconds
to restart
15 25
Power
failure
VSD
precharge
60
15
60
75 25
Coastdown*
Coastdown*
VSD
precharge
Power
failure
OptiView Chiller
control panel reboot
Timeline from loss of power
Figure 1: Required steps when power interruption occurs
with and without UPS.
Figure 2: Restart times for 500-ton chiller.
Figure 3: Time to re-establish LCHWT for 500-ton chiller
at low load.