Eaton 93PM IBC-L Operating instructions

Category
Uninterruptible power supplies (UPSs)
Type
Operating instructions
Eaton
®
93PM Integrated Accessory Cabinet-Distribution
50 kW (480V/208V) IAC-D
50 kW (208V/208V) IAC-D
100 kW (480V/208V) IAC-D
100 kW (208V/208V) IAC-D
150 kW (480V/208V) IAC-D
200 kW (480V/208V) IAC-D
Installation and Operation Manual
Eaton
®
93PM Integrated Accessory Cabinet-Distribution
50 kW (480V/208V) IAC-D
50 kW (208V/208V) IAC-D
100 kW (480V/208V) IAC-D
100 kW (208V/208V) IAC-D
150 kW (480V/208V) IAC-D
200 kW (480V/208V) IAC-D
Installation and Operation Manual
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during installation and
maintenance of the UPS system and batteries. Read all instructions before operating the
equipment and save this manual for future reference.
CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS
Ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute
procédure d'installation et de maintenance des batteries et de l'onduleur. Veuillez consulter
entièrement ces instructions avant de faire fonctionner l'équipement et conserver ce manuel afin
de pouvoir vous y reporter ultérieurement.
Eaton and Cutler-Hammer are registered trademarks of Eaton Corporation or its subsidiaries and affiliates.
National Electrical Code and NEC are registered trademarks of National Fire Protection Association, Inc. All
other trademarks are property of their respective companies.
©Copyright 2013-2014 Eaton Corporation, Raleigh, NC, USA. All rights reserved. No part of this document may
be reproduced in any way without the express written approval of Eaton Corporation.
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality i
Table of Contents
1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1.2 Installation Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.3 Model Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1.4 Using This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1.5 Conventions Used in This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1.6 Symbols, Controls, and Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1.7 For More Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
1.8 Getting Help . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
2 SAFETY WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
SECTION 1 — INSTALLATION
3 INSTALLATION PLAN AND UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 Creating an Installation Plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2 Preparing the Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2.1 Environmental and Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.2.2 IAC-D Power Wiring Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
3.2.3 208V/208V IAC-D Power Wiring Preparation with Maintenance Bypass. . . . . . . . . . . . . . . . . . . . . . . 3-9
3.3 Inspecting and Unpacking the IAC-D. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
4 INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.1 Preliminary Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.2 Unloading the IAC-D Cabinet from the Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
4.3 Installing IAC-D External Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4.3.1 Input Wiring (480V/208V). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4.3.2 Input Wiring (208V/208V). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4.3.3 50 kW and 100 kW Output Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
4.3.4 Two-Hole Barrel Lug Terminations to Bus Bar Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
4.3.5 150 kW and 200 kW Output Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
4.4 Adjustable Subfeed Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
4.5 Neutral CT Interface Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31
4.5.1 Line-Up-and-Match Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31
4.6 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-38
4.7 Completing the Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-38
SECTION 2 — OPERATION
5 ONELINES AND SCHEMATICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 Onelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.2 Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
6 INTEGRATED ACCESSORY CABINET-DISTRIBUTION OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.1 IAC-D Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
6.2 IAC-D Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Table of Contents
ii Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
7 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1 Important Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2 Performing Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2.1 DAILY Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2.2 PERIODIC Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.2.3 ANNUAL Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.3 Maintenance Training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
8 PRODUCT SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1 Model Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2.1 Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2.2 Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.2.3 Environmental and Safety Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . W-1
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality iii
List of Figures
Figure 1-1. Eaton 93PM IAC-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Figure 1-3. Eaton 93PM 50 kW, 100 kW, and 150 kW Capacity UPS with Right-Mounted Eaton 93PM IAC-D . . . . . . . 1-6
Figure 1-4. Eaton 93PM 150 kW Redundant and 200 kW UPS with Left-Mounted Eaton 93PM IAC-D. . . . . . . . . . . . . 1-7
Figure 1-5. Eaton 93PM 150 kW Redundant and 200 kW UPS with Right-Mounted Eaton 93PM IAC-D. . . . . . . . . . . . 1-7
Figure 3-1. 93PM IAC-D Cabinet Dimensions (Front, Right Side, and Back Views) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Figure 3-6. Cabinet Ventilation – 50 kW and 100 kW (208V/208V), and
150kW and 200 kW (480V/208V) Top Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Figure 3-7. Eaton 93PM IAC-D as Shipped on Metal and Wood Pallet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Figure 4-4. Input Power Terminal Locations – 480V/208V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Figure 4-5. UPS Output Breaker Power Terminal Detail – 480V/208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Figure 4-6. Input Power Terminal Locations – 208V/208V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
Figure 4-7. 208 VAC Input to IAC-D from Utility Source Terminal Detail – 208V/208V . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Figure 4-8. UPS Input Breaker Power Terminal Detail – 208V/208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Figure 4-9. 480 VAC Input to IAC-D from UPS Terminal Detail – 208V/208V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Figure 4-12. Bottom Subfeed Breaker Output Power Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
Figure 4-14. Subfeed Breaker Output Power Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
Figure 4-16. Output Breaker Output Power Terminal Detail – 50 kW and 100 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
Figure 4-17. Typical Bus Bar Barrel Lug Mounting – Hardware Assembly Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
Figure 4-19. Single Subfeed Breaker Output Power Terminal Detail – 150 kW and 200 kW . . . . . . . . . . . . . . . . . . . . . . 4-27
Figure 4-21. Output Breaker Output Power Terminal Detail – 150 kW and 200 kW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
Figure 4-22. 93PM IAC-D Neutral CT Interface Terminal Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
Figure 4-23. 93PM IAC-D Neutral CT Interface Terminal Detail . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
Figure 4-24. 50 kW UPS Neutral CT Interface Terminal Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35
Figure 4-25. 100 kW and 150 kW Capacity UPS Neutral CT Interface Terminal Location. . . . . . . . . . . . . . . . . . . . . . . . . 4-36
Figure 4-26. 150 kW Redundant and 200 kW UPS Neutral CT Interface Terminal Location . . . . . . . . . . . . . . . . . . . . . . . 4-37
Figure 5-1. 93PM IAC-D (480V/208V) Internal Oneline – 50 kW, 100 kW, 150 kW, and 200 kW with
Two PRL1A Panelboards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Figure 5-2. 93PM IAC-D (480V/208V) Internal Oneline – 150 kW and 200 kW with
Two PRL1A Panelboards and Optional Single Subfeed Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Figure 5-3. 93PM IAC-D (480V/208V) Internal Oneline – 50 kW, 100 kW, 150 kW, and 200 kW with
Top PRL1A Panelboard and Three 100–250A Adjustable Subfeed Breakers . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-4. 93PM IAC-D (480V/208V) Internal Oneline – 50 kW, 100 kW, 150 kW, and 200 kW with
Five 100–250A Adjustable Subfeed Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 5-5. 93PM IAC-D (480V/208V) Internal Oneline – 175A, 350A, 600A, or 700A Output Breaker. . . . . . . . . . . . . . 5-3
Figure 5-6. 93PM IAC-D (208V/208V) Internal Oneline – 50 kW and 100 kW with
Top PRL1A Panelboard and Three 100–250A Adjustable Subfeed Breakers . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Figure 5-7. 93PM IAC-D (208V/208V) Internal Oneline – 50 kW and 100 kW with
Five 100–250A Adjustable Subfeed Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Figure 5-8. 93PM IAC-D (208V/208V) Internal Oneline – 50 kW with
175A Output Breaker or 100 kW with 350A Output Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Figure 6-1. 93PM IAC-D Breakers – Two Panelboards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 6-3
Figure 6-2. 93PM IAC-D Breakers – Top Panelboard with Subfeed Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Figure 6-3. 93PM IAC-D Breakers – Subfeed Breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Figure 6-4. 93PM IAC-D Breakers – Output Breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
List of Figures
iv Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
This page intentionally left blank.
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality v
List of Tables
Table 3-1. Air Conditioning or Ventilation Requirements During Full Load Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Table 3-2. IAC-D Cabinet Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Table 3-3. IAC-D Cabinet Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Table 3-4. External Input Power Wiring Requirements for the Eaton 93PM IAC-D (480V/208V). . . . . . . . . . . . . . . . . . 3-10
Table 3-5. External Input Power Wiring Requirements for the Eaton 93PM IAC-D (208V/208V). . . . . . . . . . . . . . . . . . 3-10
Table 3-6. External Output Power Wiring Requirements for the Eaton 93PM IAC-D (480V/208V) . . . . . . . . . . . . . . . . 3-11
Table 3-7. External Output Power Wiring Requirements for the Eaton 93PM IAC-D (208V/208V) . . . . . . . . . . . . . . . . 3-12
Table 3-8. External Input Power Cable Terminations for the Eaton 93PM IAC-D (480V/208V) . . . . . . . . . . . . . . . . . . . 3-13
Table 3-9. External Input Power Cable Terminations for the Eaton 93PM IAC-D (208V/208V) . . . . . . . . . . . . . . . . . . . 3-14
Table 3-10. External Critical Load Output Power Cable Terminations for the Eaton 93PM IAC-D. . . . . . . . . . . . . . . . . . 3-15
Table 3-11. Supplied External Wiring Terminal Hardware Kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Table 3-12. Recommended Installation Parts and Tools (Not Supplied by Eaton) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Table 3-13. Recommended 208 Vac Input Circuit Breaker Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Table 4-1. Subfeed Breaker Continuous Current (Ir) Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
Table 4-2. IAC-D Neutral CT Interface Wiring Terminal Block Terminations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
List of Tables
vi Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
This page intentionally left blank.
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality 1-1
Chapter 1 Introduction
The Eaton
®
93PM Integrated Accessory Cabinet-Distribution (IAC-D) is designed for use with the Eaton 93PM
Series Uninterruptible Power Supplies (UPSs). The IAC-D provides power distribution options for servers, racks,
and other equipment via distribution panelboards, or distributes power to larger loads via distribution subfeed
circuit breakers. The distribution options are custom configurable, enabling adaptation and expansion without
costly electrical rework. Four 480V/208V models are available, the 93PM 50 kW IAC-D, the 93PM 100 kW
IAC-D, 93PM 150 kW IAC-D, and the 93PM 200 kW IAC-D. Two 208V/208V models are available, the
93PM 50 kW IAC-D and the 93PM 100 kW IAC-D.
The IAC-D is housed in a single free-standing cabinet with safety shields behind the front door for hazardous
voltage protection. The cabinets match the UPS cabinet in style and color.
Figure 1-1 shows the Eaton 93PM IAC-D.
Figure 1-1. Eaton 93PM IAC-D
NOTE Startup and operational checks must be performed by an authorized Eaton
Customer Service Engineer, or the warranty terms specified on page W-1 become
void. This service is offered as part of the sales contract for the UPS. Contact an
Eaton service representative in advance (usually a two-week notice is required) to
reserve a preferred startup date.
Introduction
1-2 Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
1.1 Features
l
50 kW features:
- 480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for applications
that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the critical load.
- Up to two optional output distribution panels distributes the output power from the UPS to the load. The
distribution panels are behind the door on the front of the IAC-D. Each 225A distribution panel with a 225A
main breaker can hold up to the equivalent of 42 single-pole branch circuit breakers (Cutler-Hammer
®
bolt-on type BAB or QBHW) that can be configured to meet facility needs.
- Up to five optional 100-250A adjustable output distribution breakers are available to distribute the output
power from the UPS to larger critical loads. The breakers have adjustable trip rating and are enclosed
behind the hinged doors and trim panels on the front of the IAC-D.
- A no distribution option provides a single 175A output breaker.
- Neutral Current Monitoring available at the UPS display.
- Optional factory pre-wiring to allow subfeed breakers to be field installed.
l
50 kW (208V/208V) features:
- Optional 208/480 Vac input transformer provides conversion from 208 Vac facility power to feed the
93PM UPS 480 Vac input.
- 480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for applications
that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the critical load.
- Can be used with a three-breaker Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) or wall mount
maintenance bypass.
- One optional output distribution panel distributes the output power from the UPS to the load. The
distribution panel is behind the door on the front of the IAC-D. The 225A distribution panel with a 225A
main breaker can hold up to the equivalent of 42 single-pole branch circuit breakers (Cutler-Hammer
bolt-on type BAB or QBHW) that can be configured to meet facility needs.
- Up to five optional 100-250A adjustable output distribution breakers are available to distribute the output
power from the UPS to larger critical loads. The breakers have adjustable trip rating and are enclosed
behind the hinged doors and trim panels on the front of the IAC-D.
- A no distribution option provides a single 175A output breaker.
- Neutral Current Monitoring available at the UPS display.
- Optional factory pre-wiring to allow subfeed breakers to be field installed.
l
100 kW features:
- 480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for applications
that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the critical load.
- Up to two optional output distribution panels distributes the output power from the UPS to the load. The
distribution panels are behind the door on the front of the IAC-D. Each 225A distribution panel with a 225A
main breaker can hold up to the equivalent of 42 single-pole branch circuit breakers (Cutler-Hammer
bolt-on type BAB or QBHW) that can be configured to meet facility needs.
- Up to five optional 100-250A adjustable output distribution breakers are available to distribute the output
power from the UPS to larger critical loads. The breakers have adjustable trip rating and are enclosed
behind the hinged doors and trim panels on the front of the IAC-D.
- A no distribution option provides a single 350A output breaker.
- Neutral Current Monitoring available at the UPS display.
- Optional factory pre-wiring to allow subfeed breakers to be field installed.
Introduction
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality 1-3
l
100 kW (208V/208V) features:
- Optional 208/480 Vac input transformer provides conversion from 208 Vac facility power to feed the
93PM UPS 480 Vac input.
- 480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for applications
that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the critical load.
- Can be used with a three-breaker Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) or wall mount
maintenance bypass.
- One optional output distribution panel distributes the output power from the UPS to the load. The
distribution panel is behind the door on the front of the IAC-D. The 225A distribution panel with a 225A
main breaker can hold up to the equivalent of 42 single-pole branch circuit breakers (Cutler-Hammer
bolt-on type BAB or QBHW) that can be configured to meet facility needs.
- Up to five optional 100-250A adjustable output distribution breakers are available to distribute the output
power from the UPS to larger critical loads. The breakers have adjustable trip rating and are enclosed
behind the hinged doors and trim panels on the front of the IAC-D.
- A no distribution option provides a single 350A output breaker.
- Neutral Current Monitoring available at the UPS display.
- Optional factory pre-wiring to allow subfeed breakers to be field installed.
l
150 kW features:
- 480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for applications
that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the critical load.
- Up to two optional output distribution panels distributes the output power from the UPS to the load. The
distribution panels are behind the door on the front of the IAC-D. Each 225A or 400A distribution panel
can hold up to 42 single-pole branch circuit breakers (either Cutler-Hammer bolt-on type BAB or QBHW
that can be configured to meet facility needs.
- An optional single 225A distribution breaker for use with two panel board configurations.
- Up to five optional 100-250A adjustable output distribution breakers are available to distribute the output
power from the UPS to larger critical loads. The breakers have adjustable trip rating and are enclosed
behind the hinged doors and trim panels on the front of the IAC-D.
- A no distribution option provides a single 600A output breaker.
- Optional Neutral Current Monitoring available at the UPS display.
- Optional factory pre-wiring to allow subfeed breakers to be field installed
Introduction
1-4 Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
l
200 kW features:
- 480/208 Vac output transformer provides 208 Vac output from the 480 Vac UPS output for applications
that require 208 Vac, and for use with the distribution panels suppling 208/120 Vac to the critical load.
- Up to two optional output distribution panels distributes the output power from the UPS to the load. The
distribution panels are behind the door on the front of the IAC-D. Each 225A or 400A distribution panel
can hold up to 42 single-pole branch circuit breakers (either Cutler-Hammer bolt-on type BAB or QBHW
that can be configured to meet facility needs.
- An optional single 225A distribution breaker for use with two panel board configurations.
- Up to five optional 100-250A adjustable output distribution breakers are available to distribute the output
power from the UPS to larger critical loads. The breakers have adjustable trip rating and are enclosed
behind the hinged doors and trim panels on the front of the IAC-D.
- A no distribution option provides a single 700A output breaker.
- Neutral Current Monitoring available at the UPS display.
- Optional factory pre-wiring to allow subfeed breakers to be field installed.
1.2 Installation Features
l
The IAC-D is designed to be installed in line-up-and-match or standalone configurations:
- In line-up-and-match configurations input power wiring is routed through the side panels between the
UPS and the IAC-D.
- In standalone configurations input power wiring is routed using external conduit through top or bottom
entry conduit plates.
- Output wiring is routed using external conduit through top or bottom entry conduit plates.
l
To reduce installation time, connections to the input, distribution panel, and output breakers are made to
easily accessible mechanical lug terminals on the breakers located at the front of the cabinet. Subfeed
breaker output connections are made to mechanical lug terminal blocks also located at the front of the
cabinet
l
Top exhaust or rear ventilation is available
l
The cabinet can be leveled and secured in place using leveling feet
A line-up-and-match IAC-D is installed adjacent to the UPS or other accessory cabinet. The recommended
installation location is on the left side of the UPS cabinet as viewed from the front of the cabinets. However,
the IAC-D may be installed on the right side of the UPS cabinet. See Figure 1-2 through Figure 1-5 for
line-up-and-match configuration views.
1.3 Model Configurations
The following 93PM IAC-D model configurations are available for use with the 93PM UPS Series:
l
50 kW IAC-D with 480/208 Vac output transformer and:
l
Up to two PRL1A 225A 42-pole distribution panels.
l
One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable subfeed
distribution breakers.
l
Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
l
One K-Frame 3-pole 175A output breaker.
Introduction
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality 1-5
l
50 kW IAC-D with 208/480 input transformer, 480/208 Vac output transformer and:
- One PRL1A 225A 42-pole distribution panel.
- One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
- Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
- One LG-Frame 3-pole 175A output breaker.
l
100 kW IAC-D with 480/208 Vac output transformer and:
- Up to two PRL1A 225A 42-pole distribution panels.
- One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
- Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
- One LG-Frame 3-pole 350A output breaker.
l
100 kW IAC-D with 208/480 input transformer, 480/208 Vac output transformer and:
- One PRL1A 225A 42-pole distribution panel.
- One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
- Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
- One LG-Frame 3-pole 350A output breaker.
l
150 kW IAC-D with 480/208 Vac output transformer and:
- Up to two PRL1A 225A 42-pole distribution panels.
- Up to two PRL1A 225A 42-pole distribution panels and one FD-Frame 3-pole 225A subfeed distribution
breaker.
- One PRL1A 225A 42-pole distribution panel and one PRL1A 400A 42-pole branch distribution panel.
- One PRL1A 225A 42-pole distribution panel, one PRL1A 400A 42-pole branch distribution panel, and one
FD-Frame 3-pole 225A subfeed distribution breaker.
- One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
- Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
- One LG-Frame 3-pole 600A output breaker.
l
200 kW IAC-D with 480/208 Vac output transformer and:
- Up to two PRL1A 225A 42-pole distribution panels.
- Up to two PRL1A 225A 42-pole distribution panels and one FD-Frame 3-pole 225A subfeed distribution
breaker.
- One PRL1A 225A 42-pole distribution panel and one PRL1A 400A 42-pole branch distribution panel.
- One PRL1A 225A 42-pole distribution panel, one PRL1A 400A 42-pole branch distribution panel, and one
FD-Frame 3-pole 225A subfeed distribution breaker.
- One PRL1A 225A 42-pole distribution panel and up to three JG-Frame 3-pole 100-250A adjustable
subfeed distribution breakers.
- Up to five JG-Frame 3-pole 100-250A adjustable subfeed distribution breakers.
- One MD-Frame 3-pole 700A output breaker.
Introduction
1-6 Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
Figure 1-2. Eaton 93PM 50 kW, 100 kW, and 150 kW Capacity UPS with Left-Mounted Eaton 93PM IAC-D
Figure 1-3. Eaton 93PM 50 kW, 100 kW, and 150 kW Capacity UPS with Right-Mounted Eaton 93PM IAC-D
93PM IAC-D 93PM UPS
93PM IAC-D93PM UPS
Introduction
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality 1-7
Figure 1-4. Eaton 93PM 150 kW Redundant and 200 kW UPS with Left-Mounted Eaton 93PM IAC-D
Figure 1-5. Eaton 93PM 150 kW Redundant and 200 kW UPS with Right-Mounted Eaton 93PM IAC-D
93PM IAC-D 93PM UPS
93PM IAC-D93PM UPS
Introduction
1-8 Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
1.4 Using This Manual
This manual describes how to install the IAC-D. Read and understand the procedures described to ensure
trouble-free installation and operation.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to the
UPS system being installed or operated.
1.5 Conventions Used in This Manual
This manual uses these type conventions:
l
Bold type highlights important concepts in discussions, key terms in procedures, and menu options, or
represents a command or option that you type or enter at a prompt.
l
Italic type highlights new terms where they are defined.
l
Screen type represents information that appears on the screen or LCD.
In this manual, the term UPS refers only to the UPS cabinet and its internal elements. The term UPS system
refers to the entire power protection system – the UPS cabinet, an external battery system, and options or
accessories installed.
The term line-up-and-match refers to accessory cabinets that are physically located adjacent to the UPS. The
term standalone refers to accessory cabinets that are located separate from the UPS.
1.6 Symbols, Controls, and Indicators
The following are examples of symbols used on the UPS or accessories to alert you to important information:
Icon Description
NOTE Information notes provide pertinent information about important features or instructions.
[Keys] Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk
of electric shock symbol.
CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's
manual for additional information, such as important operating and
maintenance instructions.
This symbol indicates that you should not discard the UPS or the UPS
batteries in the trash. This product contains sealed, lead-acid batteries and
must be disposed of properly. For more information, contact your local
recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or
electronic equipment (WEEE) in the trash. For proper disposal, contact your
local recycling/reuse or hazardous waste center.
Introduction
Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality 1-9
1.7 For More Information
Refer to the Eaton 93PM UPS (20–50 kW, 480V – 50 kW Frame) Installation and Operation Manual, the Eaton
93PM UPS (20-100 kW, 480V – 100 kW Frame) Installation and Operation Manual, the Eaton 93PM UPS (20–150
kW, 480V – 150 kW Capacity Frame) Installation and Operation Manual, the Eaton 93PM UPS (20–150 kW, 480V
– 150 kW Redundant Frame) Installation and Operation Manual, or the Eaton 93PM UPS (20–200 kW, 480V –
200 kW Frame) Installation and Operation Manual for the following additional information:
l
UPS, optional components, and accessory installation instructions, including site preparation, planning for
installation, wiring and safety information, and detailed illustrations of cabinets and optional accessories with
dimensional and connection point drawings
l
UPS operation, including UPS controls, functions of the UPS, standard features and optional accessories,
procedures for starting and stopping the UPS, and information about maintenance and responding to
system events
l
Communication capabilities of the UPS system
Refer to the Eaton 93PM Sidecar Integrated Accessory Cabinet-Bypass (100 kW SIAC-B) Installation and
Operation Manual for the following additional information:
l
Installation instructions, including site preparation, planning for installation, wiring and safety information,
and detailed illustrations of cabinets with dimensional and connection point drawings
l
Operation, including breakers, standard features and optional accessories, procedures for using the bypass
functions, and information about maintenance
Visit www.eaton.com/powerquality or contact an Eaton service representative for information on how to obtain
copies of these manuals.
1.8 Getting Help
If help is needed with any of the following:
l
Scheduling initial startup
l
Regional locations and telephone numbers
l
A question about any of the information in this manual
l
A question this manual does not answer
Please call the Customer Reliability Center at:
United States: 1-800-843-9433
Canada: 1-800-461-9166 ext 260
All other countries: Call your local service representative
Please use the following e-mail address for manual comments, suggestions, or to report an error in this manual:
E-ESSDocumentation@eaton.com
Introduction
1-10 Eaton 93PM Integrated Accessory Cabinet-Distribution (50–200 kW) Installation and Operation Manual P-164000229—Rev 6 www.eaton.com/powerquality
This page intentionally left blank.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118