SBC PCD7.L6xx room operation device Owner's manual

Category
Serial switch boxes
Type
Owner's manual
Document 26-859; Edition ENG07 │ 2015-06-04
Manual
Room controller units PCD7.L6xx,
Extension modules, Accessories
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Content
0-1
0
0 Content
0 Content
0.1 Document History ............................................................................................... 0-2
0.2 About this manual .............................................................................................. 0-2
0.3 Brands and trademarks ..................................................................................... 0-2
1 Assembly instructions
2 Analogue room control units
2.1 Techn.specicationsofanalogueroomcontrolunitsPCD7.L630-.L632 ......... 2-2
2.1.1 TechnicaldataforPCD7.L630 ........................................................................ 2-4
2.1.2 TechnicaldataforPCD7.L631 ....................................................................... 2-5
2.1.3 TechnicaldataforPCD7.L632 ........................................................................ 2-6
3 Digital room control units
3.1 TechnicalspecicationsofdigitalroomcontrolunitsPCD7.L640-.L644 .......... 3-2
3.1.1 TechnicaldataforPCD7.L640 ........................................................................ 3-4
3.1.2 TechnicaldataforPCD7.L641 ........................................................................ 3-5
3.1.3 TechnicaldataforPCD7.L642 ........................................................................ 3-6
3.1.4 TechnicaldataforPCD7.L643 ........................................................................ 3-8
3.1.5 TechnicaldataforPCD7.L644 ........................................................................ 3-10
Operation / Menu structur ............................................................................... 3-12
3.1.6 TechnicaldataforPCD7.L660/PCD7.L661(versionsSV1.5andSV6.1) ..... 3-13
3.1.7 TechnicaldataforPCD7.L662/PCD7.L663(versionSV2.8K) ...................... 3-18
3.2 TechnicaldataforPCD7.L650 ........................................................................... 3-23
3.2.1 Light: 2lightgroupswithsensorcommands'on'and'off'
Shade: 2groupsup/downviaelectronicsensor ............................. 3-25
3.2.2 Light: 1lightgroupsensoron,automaticoffaftertimedelay
Shade: 2groupsshadesup/down ..................................................3-26
3.2.3 Light: 1lightgroupsensoron,offvianetworkcommand
Shade: 2groupsshadesup/down ..................................................3-27
3.2.4 Light: 2groupsviaswitch
Shade: 2groupsviachangeovercontactsup/down ....................... 3-28
4 Cables for room controllers and room control units
A Appendix
A.1 Icons ................................................................................................................... A-1
A.2 Order codes ....................................................................................................... A-2
A.3 Contact .............................................................................................................. A-4
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Content
0-2
0
0.1 Document History
Date Version Changes Remarks
2008-09-30 EN01 - TranslationofGermanversion
2010-05-03 EN02 PCD7.L630 Connectionwithspringterminalblock,
notwithRJ-11
2010-09-15 EN03 PCD7.L67x Newtypesofconnectingcablesintegrated
2013-02-15 EN04 PCD7.L670
PCD7.L672
Newnumberingofthestrands
2013-09-27 EN05 Newlogoandnewcompanyname
2013-11-13 EN06 A.2 PCD7.L666don’tworkwithIR
2015-06-04 ENG07 Ch01
A.3
Newchapter:Assemblyinstructions
Newphonenumbers
0.2 About this manual
Seethesectionintheappendixinrelationtosomeoftheterms,abbreviationsand
thereferencesusedinthismanual.
0.3 Brands and trademarks
SaiaPCD
®
andSaiaPG5
®
areregisteredtrademarksofSaia-BurgessControlsAG.
Technicalmodicationsarebasedonthecurrentstate-of-the-arttechnology.
Saia-BurgessControlsAG,2015.
©
Allrightsreserved.
PublishedinSwitzerland
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Assembly instructions
1-1
1
1.5 m
Avoid direct exposure to sunlight or
light from powerful lamps.
Donotinstallnexttoheatsourcessuch
asheaters,refrigerators,lampsetc.
Donotinstallnexttowindowsanddoors
becauseofdraughts.
1 Assembly instructions
Theroomcontrolunitsmustonlybeinstalledandconnectedbyanexpertin
accordancewiththewiringdiagram.Existingsafetystandardsmustalsobe
observed.
Theroomcontrolunitscanonlybeusedtoregulatethetemperatureindry,
closedrooms.Themaximumpermissiblerelativehumidityis 90%,non-
condensing.
Precisetemperaturemeasurementissubjecttocertainrequirementsastothe
positioningofthetemperaturesensors.Thisappliesbothtotheroomcontrol
deviceitselfandtotheexternallyconnectedtemperaturesensor.
Thedevicecanbemounteddirectlyonthewallorush-mountedwithina
pattressbox.
Donotlocatedthecontroldevice/
compact room controller in the path
ofdraughtsfromclimatecontrolor
ventilationsystems.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Assembly instructions
1-2
1
Saia® DDC
Saia®
DDC
1
Assemblingthe
housingbase
2
Wiringtothedevice
3
Unlocking
Please ensure:
●
thatallwiresarescreweddowntight
●
thattheconnectingplugisproperlyengaged
●
thattheventilationslotsareplacedaboveandbelow(positioning)
●
thatthedeviceismountedhorizontally.
To prevent a premature oxidation and yellowness of the plastic enclosure of
the room control unit, the following installation conditions has to be prevent
(non-exhaustive list):
Exposuretointensivesunlightorintensivearticiallights(intensiveneontubes
lightinparticular)
Exposuretochemicalproductssuchas:intensive&frequentuseofcleaning
chemicalproducts(Bleach,…),disinfectantspraysetc.
Exposuretohighhumidityrates;saltedhumiditycouldincreasefurtherthe
oxidation
Exposuretohighratioofoxygen
Exposuretohighheat
4
Removethecase
Mounting
Removal
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Analogue room controller units
2-1
2
2 Analogue room control units
PCD7.L63x Generaltechnicalspecication
- - -
PCD7.L630 Room temperature sensor
PCD7.L631 Roomtemperaturesensorwithsetpointsetting
PCD7.L632 Roomtemperaturesensorwithsetpointsetting,
presencesensorandLED
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Analogue room controller units
2-2
Technicalspecications
2
2.1 Techn.specicationsofanalogueroomcontrolunitsPCD7.L630-.L632
RJ 11
PCD7.L671
potentiometer
consigne
LED
comfort
cateur de temperature
button d'occupation
10k, linear
bleu
jaune 5V
1k5
P1
GND
S
verte
rouge
noir
blanc
GND
Pin allocation PCD7.L630 - .L632
Signal
Terminal Description
Temperature sensor
S,GND TemperaturesensorNTC10kΩ,
measurementrange0…40°C.
Presencesensor
S,GND Floatingsensorusingthetemperaturesensor.
Setpointsetting
5V,P1,GND Potentiometer(10kΩ,linear)forsettingacong-
urablesetpointdisplacement.Seedescriptionof
CongFBoxorregisters(reg.104)
LED
LED,GND LEDtodisplayComfortmode.Comfortmode=5V,
otherwise0V.(5V,2mAmax.)
PCD7.L671 connecting cable - colour table
Colour Terminal
Description
White S
Temperature/presence sensor
Black GND
Ground
Red P1
Potentiometercentretap
Green
Not used
Yellow 5V
Potentiometerpowersupply
Blue LED
LEDwith1.5kΩseriesresistance.(max.2mA)
Note
AllinformationpointscanbereadbytheSBCS-BusviaaRoomFBoxorviaregis-
tersindependentlyoftheapplication.
Theuseofananalogueroomcontrolunitmustbeindicatedintheroomcontroller
conguration.SeedescriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Analogue room controller units
2-3
Technicalspecications
2
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Analogue room controller units
2-4
Technical data
2
2.1.1 TechnicaldataforPCD7.L630
GND
S
Temperature sensor
black
white
Room temperature sensor
Pin allocation for PCD7.L630
Signal
Terminal Description
Temperature sensor
S,GND TemperaturesensorNTC10kΩ,
measurementrange0…40 °C.
Pin allocation for connecting cable PCD7.L671
Colour Terminal
Description
White S
Temperature/presence sensor
Black GND
Groundforthetemperaturesensor
Note
All informationpointscanbereadbytheSBCS-BusviaaRoomFBoxorviaregis-
tersindependentlyoftheapplication.
Theuseofananalogueroomcontrolunitmustbeindicatedintheconguration.
SeedescriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Analogue room controller units
2-5
Technical data
2
2.1.2 TechnicaldataforPCD7.L631
RJ 11
PCD7.L671
potentiometer
Consigne
capteur de
température
10k, linéare
bleu
jaune 5V
P1
GND
S
verte
rouge
noir
blanc
GND
Roomcontrolunitwithtemperaturesensorandsetpointsetting.
Pin allocation for PCD7.L631
Signal
Terminal Description
Temperature sensor
S,GND TemperaturesensorNTC10kΩ,
measurementrange0…40 °C.
Setpointsetting
5V,P1,GND Potentiometertosetacongurablesetpointdis-
placement.SeedescriptionofCongFBoxorregis-
ters(reg.104)
PCD7.L671 connecting cable - colour table
Colour Terminal
Description
White S
Temperature sensor
Black GND
Ground
Red P1
Setpointpotentiometer
Green
Not used
Yellow 5V
Setpointpotentiometerpowersupply
Blue LED
LEDwith1.5kΩseriesresistance.(max.2mA)
Note
All informationpointscanbereadbytheSBCS-BusviaaRoomFBoxorviaregis-
tersindependentlyoftheapplication.
Theuseofananalogueroomcontrolunitmustbeindicatedintheconguration.
SeedescriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
Analogue room controller units
2-6
Technical data
2
2.1.3 TechnicaldataforPCD7.L632
RJ 11
PCD7.L671
potentiometer
consigne
LED
comfort
cateur de temperature
button d'occupation
10k, linear
bleu
jaune 5V
1k5
P1
GND
S
verte
rouge
noir
blanc
GND
Roomcontrolunitwithtemperaturesensor,setpointsettingandilluminatedpresence
sensor.WhenthecontrollerisworkinginComfortmode,thesemi-transparentsensor
lightsup.
Pin allocation for PCD7.L632
Signal
Terminal Description
Temperature sensor
S,GND TemperaturesensorNTC10kΩ,
measurementrange0…40 °C.
Setpointsetting
5V,P1,GND Potentiometertosetacongurablesetpointdis-
placement.SeedescriptionofCongFBoxorregis-
ters(reg.104)
LED
LED,GND Thepresencesensorlightsupwhenthecontrolleris
runninginComfortmode.
PCD7.L671 connecting cable - colour table
Colour Terminal
Description
White S
Temperature sensor
Black GND
Ground
Red P1
Setpointpotentiometer
Green
Not used
Yellow 5V
Setpointpotentiometerpowersupply
Blue LED
Presencesensorillumination
White S
Temperature/presence sensor
Note
All informationpointscanbereadbytheSBCS-BusviaaRoomFBoxorviaregis-
tersindependentlyoftheapplication.
Theuseofananalogueroomcontrolunitmustbeindicatedintheconguration.See
descriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-1
3 Digital room control units
PCD7.L64x Generaltechnicalspecication
- - -
PCD7.L640 Roomtemperaturesensorwithsetpointsetting
PCD7.L641 Roomtemperaturesensorwithsetpointsetting,
presencesensorandLED
PCD7.L642 Roomtemperaturesensorwithsetpointsetting,
presencesensor,LEDandfancontrol
PCD7.L643 Roomtemperaturesensorwithfunctionkeysand
LCDdisplayforHeaVACfunctions.
PCD7.L644 Roomtemperaturesensorwithfunctionkeysand
LCDdisplayforHeaVACfunctions,andlightand
shadefunctions
- - -
PCD7.L660 Mobileroomcontrolunitwithinfraredinterface,
temperaturesensor,functionkeysanddisplay
PCD7.L661 infraredreceiver
PCD7.L662 Mobileroomcontrolunitwithinfraredinterface,
temperaturesensor,functionkeysanddisplay
PCD7.L663 wirelessreceiver
- - -
PCD7.L650 Interfacemoduletoconnectupto8oatingcontactsin
combinationwitharoomcontroller
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-2
3.1 TechnicalspecicationsofdigitalroomcontrolunitsPCD7.L640-.L644
RJ 9
Controller
PCD7.L670-xx
PCD7.L642
yellow
green
red
black
LED
comfort mode
Setpoint
potentiometer
temp.-sensor
Occupancy button
Occupancy button
RJ 9
Controller
PCD7.L670-xx
Set
Display
PCD7.L643
yellow
green
red
black
temp.-sensor
Occupancy button
HEVAC function
Pin allocation for PCD7.L640 - .L644
Interface Terminal Description
Serialbus RC Theconnectiontotheroomcontrollerisdonewiththe
cablePCD7.L670-xxdirectlyonthecontrollerortheuse
ofexpansionmodulesforlightingandshadingonthelast
module.
Thepowercable,PCD7.L670-xx,isprefabricatedonboth
sidesandhasalengthofeither10,30or50m.
Themaximumlengthbetweentheroomcontrollerandthe
controlroomcontrolunitmustnotexceed50meters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-3
Functions for PCD7.L640 - .L644
Function Description
Sensor Roomtemperaturesensor.Measurementrange0…40°C.
Setpointsetting Tosetacongurablesetpointdisplacement.Depend-
ingontheroomcontrolunit,thesettingisenteredwitha
potentiometerorviatheintegrateddisplaywithHeaVAC
function.Thebasesetpointheldintheroomcontrollercan
beincreasedordecreasedinupto6steps.Thestepsize
isstoredintheroomcontrollerconguration.Seedescrip-
tionofCongFBoxorregisters(reg.104).
WhenthePlus,SetandMinuskeysarepressedtogether,
thecurrentsetpointisdisplayedforapprox.20seconds.
Presencesensor Thepresencesensorcanbeusedtochangetheoperat-
ingmodemanuallytoComfortorStandby/unused.Onthe
L640-L642controlunits,thepresencesensorlightsupin
Comfortmode.Ontheunitswithdisplays,theoperating
modeisshownonthedisplay.Thepersoniconoutside
thelittlehouseindicatesnon-use;ifthisiconisashing,
thecontrollerisinStandbymode.InComfortmode,the
personiconmovesintothehouse.
Note
AllanalogueinputsontheroomcontrollercanbereadbytheS-BusviaaRoom
FBoxorviaregistersindependentlyoftheapplication.
Theuseofadigitalroomcontrolunitmustbeindicatedintheconguration.
SeedescriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-4
3.1.1 TechnicaldataforPCD7.L640
RJ 9
Controller
PCD7.L670-xx
PCD7.L640
yellow
green
red
black
Setpoint
potentiometer
temp.-sensor
Roomcontrolunitwithtemperaturesensorandsetpointsetting.
Pinallocation
Interface Terminal Description
Serialbus RC Theconnectiontotheroomcontrollerismadewiththe
PCD7.L670-xxdirectlytothecontroller,orwhereexten-
sionmodulesareusedforlightandshade,tothelast
module.ThePCD7.L670-xxconnectingcableisprecon-
guredatbothendsandiseither10,30or50mlong.
Themaximumlengthbetweentheroomcontrollerandthe
roomcontrolunitmustnotexceed50m.
Functions
Function Description
Sensor Roomtemperaturesensor.Measurementrange0…40°C.
Setpointsetting Tosetacongurablesetpointdisplacement.Thesetting
isenteredviaapotentiometer.Therangeisconvertedinto
+/-6stepsandpassedtotheroomcontroller.Thebase
set point held in the room controller can be increased or
decreasedinsteps.Thestepsizeisstoredintheroom
controllerconguration.SeedescriptionofCongFBoxor
registers(reg.104).WhenthePlus,SetandMinuskeys
arepressedtogether,thecurrentsetpointisdisplayedfor
approx.20seconds.
Note
AllanalogueinputsontheroomcontrollercanbereadbytheS-BusviaaRoom
FBoxorviaregistersindependentlyoftheapplication.
Theuseofadigitalroomcontrolunitmustbeindicatedintheconguration.
SeedescriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-5
3.1.2 TechnicaldataforPCD7.L641
RJ 9
Controller
PCD7.L670-xx
PCD7.L641
yellow
green
red
black
LED
comfort mode
Setpoint
potentiometer
temp.-sensor
Occupancy button
Roomcontrolunitwithtemperaturesensor,setpointsettingandilluminatedpresence
sensor.
Pin allocation
Interface Terminal Description
Serialbus RC Theconnectiontotheroomcontrollerismadewiththe
PCD7.L670-xxdirectlytothecontroller,orwhereexten-
sionmodulesareusedforlightandshade,tothelast
module.ThePCD7.L670-xxconnectingcableisprecon-
guredatbothendsandiseither10,30or50mlong.
Themaximumlengthbetweentheroomcontrollerandthe
roomcontrolunitmustnotexceed50m.
Functions
Function Description
Sensor Roomtemperaturesensor.Measurementrange0…40°C.
Setpointsetting Tosetacongurablesetpointdisplacement.Thesetting
isenteredviaapotentiometer.Therangeisconvertedinto
+/-6stepsandpassedtotheroomcontroller.Thebase
set point held in the room controller can be increased or
decreasedinsteps.Thestepsizeisstoredintheroom
controllerconguration.SeedescriptionofCongFBoxor
registers(reg.104).WhenthePlus,SetandMinuskeys
arepressedtogether,thecurrentsetpointisdisplayedfor
approx.20seconds.
PresenceSensor Thepresencesensorcanbeusedtochangetheoperating
modemanuallytoComfortorStandby/unused.InComfort
mode,thesemi-transparentsensorlightsup.
Note
AllanalogueinputsontheroomcontrollercanbereadbytheS-BusviaaRoom
FBoxorviaregistersindependentlyoftheapplication.
Theuseofadigitalroomcontrolunitmustbeindicatedintheconguration.
SeedescriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-6
3.1.3 TechnicaldataforPCD7.L642
RJ 9
Controller
PCD7.L670-xx
PCD7.L642
yellow
green
red
black
LED
comfort mode
Setpoint
potentiometer
temp.-sensor
Occupancy button
Occupancy button
Roomcontrolunitwithtemperaturesensor,setpointsetting,illuminatedpresence
sensorandfancontrol.
Pin allocation
Interface Terminal Description
Serialbus RC Theconnectiontotheroomcontrollerismadewiththe
PCD7.L670-xxdirectlytothecontroller,orwhereexten-
sionmodulesareusedforlightandshade,tothelast
module.ThePCD7.L670-xxconnectingcableisprecon-
guredatbothendsandiseither10,30or50mlong.
Themaximumlengthbetweentheroomcontrollerandthe
roomcontrolunitmustnotexceed50m.
Functions
Function Description
Sensor Roomtemperaturesensor.Measurementrange0…40°C.
Setpointsetting Tosetacongurablesetpointdisplacement.Thesetting
isenteredviaapotentiometer.Therangeisconvertedinto
+/-6stepsandpassedtotheroomcontroller.Thebase
set point held in the room controller can be increased or
decreasedinsteps.Thestepsizeisstoredintheroom
controllerconguration.SeedescriptionofCongFBoxor
registers(reg.104).WhenthePlus,SetandMinuskeys
arepressedtogether,thecurrentsetpointisdisplayedfor
approx.20seconds.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-7
Function Description
PresenceSensor Thepresencesensorcanbeusedtochangetheoperating
modemanuallytoComfortorStandby/unused.InComfort
mode,thesemi-transparentsensorlightsup.
Fan control Thefanselectionswitchcanbeusedtosetthefanspeed
manually.Theroomcontrollercanonlyswitchtothe
desiredstepifthisisallowedbythefanoperatingwindow.
SeedescriptionofCongFBoxorregisters(reg.63,64)
Note
AllanalogueinputsontheroomcontrollercanbereadbytheS-BusviaaRoom
FBoxorviaregistersindependentlyoftheapplication.
Theuseofadigitalroomcontrolunitmustbeindicatedintheconguration.
SeedescriptionofCongFBoxorregisters.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-8
3.1.4 TechnicaldataforPCD7.L643
RJ 9
Controller
PCD7.L670-xx
Set
Display
PCD7.L643
yellow
green
red
black
temp.-sensor
Occupancy button
HEVAC function
Roomcontrolunitwithtemperaturesensor,functionkeysanddisplayforHeaVAC
functions.
Pin allocation
Interface Terminal Description
Serialbus RC Theconnectiontotheroomcontrollerismadewiththe
PCD7.L670-xxdirectlytothecontroller,orwhereexten-
sionmodulesareusedforlightandshade,tothelast
module.ThePCD7.L670-xxconnectingcableisprecon-
guredatbothendsandiseither10,30or50mlong.
Themaximumlengthbetweentheroomcontrollerandthe
roomcontrolunitmustnotexceed50m.
Functions
Function Description
Sensor Roomtemperaturesensor.Measurementrange0…40°C.
Setpointsetting Tosetacongurablesetpointdisplacement.Setin+/-6
stepsviathedisplay.Thebasesetpointheldintheroom
controller can be increased or decreased in steps. The
stepsizeisstoredintheroomcontrollerconguration.
SeedescriptionofCongFBoxorregisters(reg.104).
WhenthePlus,SetandMinuskeysarepressedtogether,
thecurrentsetpointisdisplayedforapprox.20seconds.
Saia-Burgess Controls AG
Manual for PCD7.L6xx room operator units │ Document 26-859  ENG07 │ 2015-06-04
3
Digital room controller units
3-9
Function Description
PresenceSensor Thepresencesensorcanbeusedtochangetheoperat-
ingmodemanuallytoComfortorStandby/unused.The
operatingmodeisshowninthedisplay.Thepersonicon
outsidethelittlehouseindicatesnon-use;ifthisiconis
ashing,thecontrollerisinStandbymode.InComfort
mode,thepersoniconmovesintothehouse.
Fan control TheHeaVACmenucanbeusedtosetthefanspeed
manually.Theroomcontrollercanonlyswitchtothe
desiredstepifthisisallowedbythefanoperatingwindow.
SeedescriptionofCongFBoxorregisters(reg.63,64)
HeaVAC functions
ThedesiredfunctionisactivatedbypressingandholdingtheovalSETkey(for
approx.2seconds).Theactivefunctionisshowninthedisplaybytheashingicon.
Thesettingcanbechangedwiththeup/downarrowkeys.Ashortkeystrokeapplies
thecurrentsetting.
Note
AllanalogueinputsontheroomcontrollercanbereadbytheS-BusviaaRoom
FBoxorviaregistersindependentlyoftheapplication.
Theuseofadigitalroomcontrolunitmustbeindicatedintheconguration.
SeedescriptionofCongFBoxorregisters.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40