Maytag 3395316 Installation Instructions Manual

Category
Electric laundry dryers
Type
Installation Instructions Manual
Commercial Dryer
Installation Instructions
MPORTANT:
?ead and save
lhese instructions.
Important:
Read
these instructions before you start to install
the dryer.
Save
Installation Instructions for local electrical
inspector’s use.
Keep
Installation Instructions for future
reference.
J
Part No. 3395316 Rev. C
Before you start...
Check locatlon
where dryer will be
used. Proper installation is your
responsibility. The dryer must not be
installed or stored in an area where it
will be exposed to water and/or
weather. Make sure you have
everything necessary for correct
installation.
Copies of the
standards
listed above may
be obtained from:
‘American Gas Association
1515 Wilson Boulevard
Arlington, Virginia 22209
l
* National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
Fire Hazard
For your safety, the Information In
thls manual must be followed to
mlnlmlze the rlsk of flre or exploslon
3r to prevent property damage,
Dersonal InJury or loss of life.
. Do Not store or use gasoline or
other flammable vapors and
llqulds In the vlclnlty of this or any
other appliance.
. WHAT TO DO IF YOU SMELL GAS:
. Do Not try to light any
appliance.
l
Do Not touch any electrlcal
switch; Do Not use any phone
In your bulldlng.
l
Clear the room, bulldlng or area
of all occupants.
9 lmmedlately call your gas
suppller from a nelghbor’s
phone. Follow the gas suppller’s
Instructlons.
. If you cannot reach your gas
suppller, call the flre department.
- Never Install dryer up agalnst
draperies or curtains or on carpet.
. Keep any and all Items from klllng
or collecting behlnd the dryer.
nstallatlon and service must be
Defformed by CI quallfled Installer,
iervlce agency or the gas suppller.
Post this warnlng In a promlnent
locatlon.
It is recommended that the operator
post, in a prominent location,
instructions for the customer’s use in
the event that the customer smells
gas. This information should be
obtained from your local gas supplier.
Protectlon from weather:
Proper
operation requires temperatures
above 45°F (7.2%).
The wiring diagram is located on
inside of the access panel.
Check utllltles:
Proper
f
Important: Observe all governing
codes and ordinances.
Failure to meet codes and
ordinances could lead to fire
or electrical shock.
the
w
supply connections
must be available.
Ill
1 i8-l&G NPT plugged
tapplng Is required.
:l:lj:: s’.::.‘i:j:i$: i requirements, Page 3 ,
: . . .
exhausted from
bottom, rear, left
or right side. See
m Exhaust
requirements,”
Fded electrlcal outlet
is
required. See “Electrical
requirements.’ Page 4.
support the total weight of 160 pounds
Level floor:
Maximum floor slope under
dryer- 1 inch.
per dryer; 3 15 pounds for stacked dryers.
recessed area requirements and
product dimensions.
Locatlon
must be large enough to
fully open dryer door. See Page 9 for
Fire Hazard
l
Replace access pcmel before
operatlng dryers.
l
lf you Install dryers ln a garage,
carport, or areas near vehicles
where fumes from gasoline or other
vapors may be present, the vapors
may be heavier than alr and
remain near the floor. Place dryers
a mlnlmum of 18 Inches above
floor. Check wlth your bulldlng
Inspector regardlng requirements
for thls Installation.
:allure to follow these lnstructlons
:ould result In a llre or exploslon.
Electrlcal Shock Hazard
It Is the customer’s responslblllty:
l
To contact a licensed electrlclan.
l
To have dryers Installed
according to all natlonal and
local codes and ordinances.
Failure to do so could result In a flre,
electrlcal shock or other personal
InJury.
Personal InJury Hazard
More than one person Is required to
IIR, tilt, or move the dryers because
of their welght and size.
Failure to follow these lnshuctlons
may result In personal InJury.
Page 2
Tools and
matetials needed
for installation:
adjustable wrench
level
utility knife
pliers
Phillips screwdriver
duct tape
flat-blade screwdriver I” socket wrench
Gas supply
requirements
Fire Hazard
l
These dryers must be connected
to a regulated gas supply.
Failure to do so could result In hlgh-
pressure gas release, resulting In a
flre or exploslon.
l
Have L.P. gas checked by a
quallfled person before lnstalllng
the dryer. The L.P. gas supply must
not exceed a pressure
0r
13”
water column.
. New flexible tublng should be
used. Reuslng old, flexible tublng
mlght result In possible leaks or
flre hazard.
Failure to follow these lnstructlons
could result In fire or exploslon.
OBSERVE ALL GOVERNING CODES
AND ORDINANCES.
w This installation must conform
with American National Standard,
National Fuel Gas Code ANSI 2223.1
- latest edition, and all local codes
and ordinances.
B
n
The desian of this drver has
been certified byThe American Gas
Association for use at altitudes up to
10,000 feet above sea level at the
B.T.U. rating indicated on the
model/serial plate. Burner input
adjustments are not required when
the dryer is operated up to this
elevation.
When installed above 10,000 feet, a
four percent (4%) reduction of the
burner B.T.U. rating shown on the
model/serial plate is required for
each 1,000 foot increase in elevation,
For assistance when converting to
other gas types and/or installing
above 1 O,ooO feet elevation, contact
your local service company.
C
w Check that dryer is
equipped with the correct burner for
the particular type of gas used.
Burner information will be found on
the rating plate in door well of the
appliance. If this information does not
agree with the type of gas available,
see your dealer.
D
n
This dryer is shipped for use
with NATURAL GAS. It is certified by
the American Gas Association for
manufactured, mixed and L.P.
(propane and butane) gases with
appropriate conversion. No attempt
shall be made to convert the
appliance from the gas specified on
the rating plate for use with a
different gas without consulting the
serving gas supplier.
Converslon must
be done by a quallfled servlce
technlclan. Gas converslon klt part
numbers are llsted on the gas valve
burner base.
E
I Provide a
rlgld gas supply
line
of l/2-inch IPS pipe to the dryer
location, If the total length of the
supply line is more than 20 feet, larger
pipe will be needed. For L.P. gas
usage, 3/8-inch, approved copper
tubing may be used. Pipe-joint
compounds suitable for use with L.P.
gas should be used.
F
w If local codes and ordinances
permit, it is recommended that new
flexible metal tubing, design-certified
by the American Gas Association, be
used for connecting the dryer to the
gas supply line.
G
n
The supply line shall be
equipped with a shutoff valve. Thls
valve should be located in the same
room as the dryer and should be in a
location that allows ease of opening
and closing. Do Not block access to
shutoff valve.
H
n
If rigid pipe is used to
connect the dryer to the main gas
supply line, a combination of fittings
must be used to obtain an in-line
connection to the dryer.
n
Make sure lower edges, back
and sides of the cabinet are free of
obstructions to permit adequate
clearance of air openings for
combustion air. See “Recessed area
and closet installation instructions” for
minimum spacing requirements.
J
n
For ease of Installation.
operating and servicing (if ever
needed), adequate space should be
provided around the dryer.
K
n
A l/8-inch, NPT plugged
tapping, accessible for test gauge
connection, must be installed
immediately upstream of the gas
supply connector to the dryer.
The dryer and their individual shutoff
valves must be disconnected from
the gas supply piping system during
any pressure testing of that system at
test pressures in excess of l/2 pslg
(3.45 kPa).
The dryer must be isolated from the
gas supply piping system by closing
it’s individual manual shutoff valves
during any pressure testing of the gas
supply piplng system at test pressures
equal to or less than l/2 psig
(3.45 kPa).
Page 3
ttexlble
/
connector
(use A.G.A.
dwl n-
1 certl ed
connector)
\
L
W If the dryer is installed in a
confined area such as a bathroom or
closet, it must be exhausted to the
outside and provision made for
enough air for combustion and
ventilation. (Check governing codes
and ordinances. Also refer to the
section of this instruction covering
“Recessed and closet installations.“)
Electrical
reauirements
*
Electrlcal Shock IHazard
l
Electrlcal ground Is required on
thls appliance.
l
Do Not ground to a gas pipe.
l
Do Not modlty the power supply
cord plugs. It plugs will not tit the
outlet, have a proper outlet
Installed by a quallfled
electrlclan.
l
Do Not have a fuse In the neutral
or groundlng clrcult. A tuse In the
neutral or groundlng 8clrcult could
result In an electrlcal shock.
l
Do Not use an extension cord
wlth thls appliance.
l
Check wlth a qualltled
electrlclan It you are In doubt as
to whether the appliance Is
properly grounded.
Failure to tallow these lnstructlons
could result In serious ln)ury or
death.
It codes permit and a separate
groundlng wire Is used, It Is
recommended that a qualltled
electrlclan determlne that the
groundlng path Is adequate
OBSERVE ALL GOVERNING
CODES AND ORDINANCES.
A 120-volt, XI-Hz, AC-only, 15- or 20
ampere fused electrical supply is
required. Time-delay fuse or circuit
breaker is recommended. It is
recommended that a separate
circuit serving only these appliances
be provided.
T
zcordmended grounding
For your personal safety, these dryers
must be grounded. Each dryer is
equipped with a power supply cord
having a 3-prong grounding plug. To
minimize shock hazard, the cords
must be plugged into mating 3-prong
grounding-type wall receptacles,
grounded in accordance with
National Electrical Code ANSVNFPA
70 - latest edition, and all local
codes and ordinances. If a mating
wall receptacle is not available, it is
the personal responsibility and
obligation of the customer to have a
properly grounded, 3-prong wall
receptacle installed by a qualified
technician, See Figure 1.
3-pron
groun ng-type
8
wall receptacle 1
I
groundlng
POT SUPPM
prong
Figure 1
Page 4
Exhaust
requirements
Fire/Health Hazard
l
Do Not use non-metal, flexible
duct.
l
Do Not use metal duct smaller
than four Inches In diameter.
l
Do Not use exhaust hoods with
metal latches.
l
Check that exhaust system Is not
longer than speclfled. Exhaust
system longer than speclfled will:
- Accumulate Ilnt.
- Shorten the Ilfe of the dryer.
- Reduce the performance,
resulting In longer drylng times
and Increased energy usage.
Failure to follow speclflcatlons may
result In a rite.
l
Do Not exhaust dryers Into a
chimney, furnace cold alr duct,
attlc or crawl space, or any other
duct used for ventlng.
l
Clean the exhaust system every
other year.
l
Do Not Install flexible duct In
enclosed walls, celllngs or rloors.
Accumulated lint could result In a
tire or cause molsture damage.
l
Exhaust dryers outslde to prevent
exposure to substances In gas
fuels and combustion which may
be harmful to your health.
rhe moisture and lint Indoors may
cause:
- FIRE HAZARD from lint collected In
dryer.
- Moisture damage to woodwork,
furniture, paint, wallpaper, carpet,
etc.
- Housecleanlng problems and
possible health problems.
Failure to
r0ii0w
these Instructlons
could result In flre damage 01
personal Injury.
Exhaust materials are not
supplied.
0
better
exhaust
aitilow
-
fi%rt
airflow
1
L#-
Four-Inch metal exhaust duct
is
required. Plan installation to use the
fewest number of elbows and turns.
Use duct tape
to seal all joints.
Metal flexible duct
must be fully
extended and supported when the
dryer is in final position. DO NOT KINK
OR CRUSH THE DUCT. The metal
flexible duct must be completely open
to allow adequate exhaust air to flow.
Allow as much room as possible when
using elbows or making turns. Bend
duct gradually to avoid kinking.
Remove excess flexible duct to avoid
sagging and kinking that may cause
reduced airflow.
The external exhaust d
T
t
can be
routed up, down, left, ri ht or straight
out the back of the dryer. Product
dimensions and recessed area
requirements are given on Page 8.
Side or bottom exhaust:
The maximum
length of the exhaust system if dryer is
exhausted out the side or bottom is 16
feet with two external elbows and
hood.
Rear exhaust:
The maximum length of
the exhaust system depends on the
type of duct, the number of elbows
and the type of exhaust hood. The
maximum length for both rigid and
flexible duct is shown in the chart.
Thls chart applies only to lndlvldually
exhausted unlts.
EXHAUST HOOD TYPE
t2.s 5igi qi 2s
MAXIMUM LENGTH OF I-INCH DIAMETER RIGID METAL DUCT
0
43 Fr.
41 Fr 36 Fr.
1
2 Z:
31 Fr. 26FI.
21Fr. 16FI.
MAXIMUM LENGTH OF I-INCH DIAMETER FLEXIBLE METAL DUCT
ri
Service check:
The back pressure in
any exhaust system used must not
exceed 0.6 inches of water column
measured with an inclined
manometer at the point that the
exhaust system connects to the dryer.
Page 5
If dryer Is Installed In a confined area
such as a bedroom, bathroom or
closet, it must be exhausted to the
outside and provision must be made
for enough air for combustion and
ventilation. (Check governing codes
and ordinances. Also refer to the
“Recessed area and closet installation
instructions, - Page 8.)
An
exhaust hood
should cap the
exhaust duct to prevent exhausted air
from returning into the dryer. The
outlet hood must be at least 12 inches
from the ground or any object that
may be in the path of the exhaust.
Four-Inch outlet hood Is preferred.
However, a 2.l/2-inch outlet exhaust
hood may be used. (A 2-l/2-inch
outlet creates greater back pressure
than other hoods.)
A maln exhaust duct
can be used for
exhausting a group of dryers. Main
exhaust duct should be sized to
remove 200 CFM of air per dryer.
Large-capacity lint screens of proper
design may be used in the main
exhaust duct if checked and cleaned
frequently. The room where the dryers
are located should have make-up air
equal to or greater than the CFM of
all the dryers in the room.
Back-draft damper kit
(Part No.
3391910) should be Installed in each
dryer exhaust duct to prevent
exhausted air from returning into the
dryers and to keep the exhaust
balance within the main exhaust
duct. Unobstructed air openings are
required.
Each exhaust duct
should enter the
main duct at an angle pointing in the
direction of the airflow. Ducts
entering from the opposlte side
should be staggered to reduce the
exhausted air from interfering with the
other ducts.
The
maxlmum angle
of each duct
entering the main duct should be no
more than 30”.
Product Damage
Keep alr openlngs free of dry-
cleaning fluld rumes.
Fumes create acids which, when
drawn through the dryer heating
units, can damage dryers and
loads being dried.
A
clean-out cover
should be located
on the main exhaust duct for
periodically cleaning the exhaust
system,
An
exhaust hood
should cap the
outside end of the main duct to
prevent exhausted air from returning
to the dryers. If an exhaust hood
cannot be used, the outside end of
the main duct should have a sweep
elbow directed downward. If the
main duct travels vertically through
the roof rather than through the wall,
install 180” sweep elbow on the end
of duct at least 2 feet above the
highest part of the building. The
opening wall or roof shall have a
diameter l/2 inch larger than the
exhaust duct diameter. The exhaust
duct should be centered in the
opening.
exhaust hood
or sweep
elbow
horlrontal duct
2 1. mln.
highest polnt of
bulldlng
\
Do Not install screening cap over end
of duct.
Exhaust duct
connection
Electrlcal Shock Hazard
Dlxonnect both power supply
cords before maklng these
changes.
Failure to do so may result In
electrlcal shock or personal Injury.
I
Determine which direction you need
to attach the exhaust ducts to the
dryer. Dryer can be exhausted
straight out the back or from the right
or left side or through bottom.
Next, determine the length of exhaust
duct you will need to connect the
dryer to exhaust hoods or the main
exhaust.
To connect exhaust duct
straight out the back-
Attach exhaust duct to dryer duct.
Then connect exhaust duct to
exhaust hood or main exhaust. Use
duct tape to seal all joints.
Page 6
To connect exhaust duct
;rFeugh the right or left
-
1. Remove access panel by releasing
two locking clips with a small, flat-
blade screwdriver. The clips are
located four inches in from each
side
of the access panel.
Personal Injury Hazard
Wear gloves to protect hands from
sharp edges that may be present.
Failure to do so may result In
personal InJury.
2. Remove the duct tape from the
internal exhaust duct and the straight
duct.
3. Remove the screw from the duct
clip that attaches the straight duct to
the back of the cabinet. Depress the
clip to remove the straight duct using
a twisting motion through the rear
exhaust opening.
4. Reach through the rear exhaust
opening and depress center of tabs
on the plastic opening cover on the
side you want to exhaust through.
Remove the cover.
5
plain
end
90” elbow
5. Attach a three- or four-section
elbow to the straight duct using duct
tape.
90”
elbow
.
6. Insert elbow end of duct pieces
through the side opening. Reach
through the access panel opening
and attach elbow to the internal
exhaust duct. Check the length of
straight duct extending out the side
of the cabinet. If duct extends too far
to make the exhaust duct
connection, mark a line around the
straight duct one inch out from the
cabinet. Remove the duct and elbow
and cut the straight pipe to the
length needed. Reinsert the duct
pieces. Use duct tape to connect the
elbow to the internal exhaust duct.
7. Insert the plastic cover into the
rear exhaust opening.
8. Replace the access panels.
9. Use duct tape to seal all Jolnts.
To connect exhaust duct
through the bottom of the
dryer -
Note: You must use a three-section
elbow to connect exhaust duct
through the bottom of the dryer.
1. Check that the legs extend one
inch from the bottom of the dryer.
2. Remove the access panel by
releasing the two locking clips with a
small, flat-blade screwdriver. The clips
are located four inches in from each
side of the access panel. Lift access
panel off the bottom clips and set
aside.
Page 7
Wear gloves to protect hands from
sharp edges that may be present.
Failure to do so may result In
personal Injury.
3. Remove duct tape from internal
exhaust duct and the straight duct.
4. Remove the screw from the duct
clip that attaches the straight duct to
the back of the cabinet. Depress the
clip and remove the straight duct
using a twisting motion through the
rear exhaust opening.
5. Measure from the large end of the
straight duct and mark at four inches,
Cut the straight duct to that length.
6. Reach through the rear exhaust
opening and depress center of tabs
on one of the side, plastic opening
covers. Remove the cover.
7. With a Phillips screwdriver, reach
through the rear exhaust opening
and remove the screw that attaches
the cover to the dryer base. Carefully
remove the cover and screw through
the rear exhaust opening.
Floor Damab
Slide dryers onto cardboard or
hardboard before mating across
floor.
Failure to do so may cuuse
damage to floor coverlng.
8. Move dryer into operating position.
Reach through the access opening
and mark the exhaust opening
location on the floor. Move dryer out
of the operating position.
9. Cut opening through the floor.
T!zB
i
I
I
h
10. Push the four-inch, straight duct
through the rear exhaust opening
and onto the internal duct as far as it
will go.
11. Insert the elbow through the rear
exhaust opening. Insert elbow into
the bottom exhaust opening.
lkza!i
I
I
I
-I
\
front
of
dryer
12. Slide the straight duct into the
elbow approximately one inch.
Use
duct tape to seal both Jolnts.
screw head
Wablnet
(fastens
:
rear
yg;&y-b
tab
bottom
I-
of dryer
$
13. Insert the bottom exhaust cover
through the side exhaust opening. Put
the cover over the rear exhaust
opening with the tab pointing down
to bottom of dryer. Insert screw
through the hole in the cover that is
on the inside of the cabinet. Tighten
screw.
14. Replace the side exhaust cover.
15. Move the dryer into operating
position. Check that the elbow is
through the bottom exhaust opening.
Replace the access panel.
16. Connect elbow to exhaust duct.
Then connect exhaust duct to
exhaust hood or main exhaust.
Use
duct tape to seal all Jolnts.
Page8
Recessed area
and closet
installations
Fire/Health Hazard
Exhaust dryers to the outslde to
prevent exposure to substances In
the gas fuels and combustion
byproducts which may be harmful
to your health.
Failure to do so may result In a flre
or health hazard.
Thls appliance may be Installed In a
recessed area.
The installation spacing is the
minimum allowable. Additional
spacing should be considered for
ease of installation, servicing and
compliance with local codes and
ordinances.
If closet door is installed, the minimum
unobstructed air openings in the top
and bottom are required. Door
must
have two centered openings as
illustrated. Both openings must
provide a minimum of 72 square
inches of unobstructed airflow as
shown. Louvered doors with
equivalent air openings are
acceptable.
Do Not block airflow at the bottom
front of the dryer with laundry or rug.
Airflow from the bottom of the dryer is
needed for operating efficiency.
AddItIonal
clearances
maybe
required for
wall, door
and floor
mokiln
If
T
extema
exhousf
elbow Is
Used.
o”-B
P-
O”-D
Recessed front view
Closet view
Side view
0” -D
Additional
clearances
may be
rx:f
door aid
iloor
moldings
if external
exhaust
elbow is
used.
r
Additional
may be required.
Front view
Closet
0
door Am
I
3
L
3”
Opening is minimum for closet door.
Louvered door with equivalent air openings
is acceptable.
Companion appliance spacing
should be considered.
FOR CLOSET INSTALLATIONS, TO
PREVENT LARGE AMOUNTS OF LINT
AND MOISTURE FROM
ACCUMULATING, TO MAINTAIN
DRYING EFFICIENCY, AND TO PREVENT
EXPOSURE TO POSSIBLE HEALTH
HAZARDS, DRYERS MUST BE
EXHAUSTED OlKDOORS.
No other fuel-burnlng appliance may
be Installed In the same closet.
Page 9
Now start...
With dryer in laundry area.
Personal InJury Hazard
More than one person Is required to
lift. tilt. or move stacked dryers
because of weight and size.
Failure to follow these lnstructlons
may result In personal InJury.
n
Take two of the cardboard
corners from the carton and place
them on the floor in back of the dryer.
Firmly grasp the body of the dryer and
gently lay it on its back on the
cardboard corners.
2
n
Check that each lea is
approximately 1” from base-That Is
how far the rear leg is supposed to go
into the hole. A little liquid detergent
to lubricate the screw will help. Use a
1” wrench or socket to finish turning
the legs to the diamond mark.
3
n
Now stand dryer up.
4
n
Wipe the interior of the drum
thoroughly with a damp cloth.
Page 10
T
Numbers
correspond
to steps.
5.
6.
9.
1.
12
5
n Remove the red cap from
the gas pipe.
6
n Connect gas s
pply to each
dryer. Use pipe-joint co
ll
pound
made for use with L.P. gas for gas
connections.
All connectlons must be wrench-
tightened.
7
n Open the shutoff valve in the
gas supply line.
Fire Hazard
Do Not use an open flame to test
for leaks from gas connections.
Checking for leaks wlth a flame
may result In a fire or explosion.
8
l
Use a brush and liauid
detergent to test all gas connections
for leaks, Bubbles around connections
will indicate a leak. If a leak appears,
shut off gas valve controls and adjust
connections, Then check
connections again.
NEVER TEST FOR
GAS LEAKS WlTH A FLAME.
Close the
access panels.
9
n
Plug power supply cords
-
grounded outlets. Turn on electrical
power supply.
‘0
Floor Damage
Slide dryers onto cardboard or
hardboard betore movlng across
floor.
Failure to do so may result In
damage to tloor coverlng.
gra;t;yer to its permanent
.
.
10
n
Turn drver on to remove
air fTom the gas supply line. Using a
full heat cycle (not the air cycle), let
the dryer run for at least five minutes.
If the burner does not ignite and you
can feel no heat inside the dryer, shut
off the dryer for five minutes. Check
that all supply valve controls are in
“ON” position and that the power
supply cord is plugged in. Repeat the
five-minute test.
11
W Check levelness of drver
by placing a carpenter’s level on top
of the dryer, first side to side, then
front to back. If dryer is not level,
adjust the front legs up or down.
Make the final check with the level.
12
w To exhaust the dryer, see
‘Exhaust requirements” and ‘F!xhaust
duct connection,” pages 5 to 7.
Personal Injury fiazard
To prevent tlpplng, tetlher bracket
must be secured to wall studs or
concrete wall.
Failure to do so could result In
personal Injury.
Tether bracket, located at
rear of the top dryer.
13
n
Attach both ends of
tether located at the rear of the top
dryer to a secured 2 x 4.
14
W
Check to make sure you
have all your tools.
The installation is now
complete.
Page 11
If dryer does not
operate properly...
Check the tollowlng to be sure that:
1. Power supply cord is connected
2. Circuit breaker is not tripped or
fuses blown.
3. Dryer door is closed.
4. Controls are set in a running or
‘ON” position.
5. Gas shutoff valves are open, both
on dryer and supply line.
Part No. 3395316 Rev. C
01994
I
Move dryers to a
new location...
Floor Damahe
Slide dryer onto cardbpard or
hardboard before moving across
tloor.
Failure to do so may result In
damage to tloor covelng.
l
Shut off electric supply to dryers.
l
Disconnect power supply cord.
Tape securely to dryer.
l
Shut off the gas supply valves in the
gas supply line.
l
Disconnect gas pipe and fittings
from dryer and cap the gas supply
line. Tape end of dryer gas pipe.
l
Tape the drum to the front panel.
l
Tape door closed.
l
Adjust leveling legs all the way in.
Before installing dryer In a new
location, check with your gas supplier
or dealer to see that your dryer is
equipped with the correct burner for
the particular type of gars in your new
building. Burner information may be
found on the rating plate in the door
well of the dryer.
If you need
as&stance...
Check your Use and Care guide for a
toll-free number to call or call the
dealer from who you purchased this
appliance. The dealer is listed in the
Yellow Pages of your phone directory
under “Appliances - Household -
Major - Service and Repalr.’
When you call, you will need the
dryer model number and serial
number. Both numbers can be found
on the serial/rating plate located In
the door well behind the dryer door
and on the front of the opening.
Printed on recycled paper.
10% post consumer waste/
50% recovered matertals.
Printed in U.S.A.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12

Maytag 3395316 Installation Instructions Manual

Category
Electric laundry dryers
Type
Installation Instructions Manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI