Allen-Bradley 1407-CGCM-DLR User manual

Type
User manual
Combination Generator Control Module
Catalog Numbers 1407-CGCM-DLR
User Manual
Original Instructions
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Labels may also be on or inside the equipment to provide specific precautions.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 3
Table of Contents
Preface
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Studio 5000 Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
General Information Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Generator Regulation and Control Functions. . . . . . . . . . . . . . . . 11
Generator Protection Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Metering Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2
Installation Mounting Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Excitation Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Excitation Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Control Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chassis Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
AC Voltage and Current Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Auxiliary Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Remote Excitation Enable Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Discrete Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Real-power Load Sharing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Cross-current Compensation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Communication Connectors and Settings . . . . . . . . . . . . . . . . . . . 37
Chapter 3
CGCM-DLR Unit Operation Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Power Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Discrete Inputs - Remote Excitation Enable. . . . . . . . . . . . . . . . . . 44
Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Discrete Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Com 0 Factory Test Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Com 1 Redundancy Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
EtherNet/IP Network Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Software Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Operational Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Excitation Control Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Table of Contents
Limiting Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Protection Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Synchronizing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Real-power Load Sharing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Redundancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Watchdog Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Chapter 4
CGCM-DLR Unit Configuration Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Overview of the Configuration Process. . . . . . . . . . . . . . . . . . . . . . . . . . 75
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Record System Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Equipment Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Create a New Module in the ControlLogix Controller . . . . . . . . . . . 76
Create the New 1407-CGCM-DLR Module in the I/O
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Electronic Keying. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Manually Configure a Static IP Address . . . . . . . . . . . . . . . . . . . . . . . . . 81
Device Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Applying the Configuration to the CGCM Unit . . . . . . . . . . . . . 88
Configuration Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Chapter 5
CGCM-DLR Unit Startup Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Recommended Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Programming Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Two-channel Chart Recorder or Other Suitable
Data-recording Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Test Current and Voltage Source . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Recommended Start-up Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Initial Checkout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Apply Power to the CGCM-DLR Unit (24V DC) . . . . . . . . . . 121
Verify the Network Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Statically Test CGCM-DLR System Redundancy Operation. 122
Simulate AC Gen and Bus Inputs and Verify Metered
Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Static Tests of Protective Functions . . . . . . . . . . . . . . . . . . . . . . . . 123
Operational Testing of the CGCM-DLR Unit Functions. . . . 129
Test Synchronization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Verify Applicable Automatic Operating Modes . . . . . . . . . . . . . 132
Verify Operation of Limiter Functions and Diode Monitor . . 136
Document Configuration Parameter and Wiring Changes. . . . . . . 138
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 5
Table of Contents
Chapter 6
CGCM-DLR Unit Software
Interface
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
CGCM-DLR Unit Data Table Summary. . . . . . . . . . . . . . . . . . . 139
CGCM-DLR Unit User Program Interface . . . . . . . . . . . . . . . . . . . . 140
Configuration Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Operating Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
CGCM-DLR Unit Data Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Assembly Object Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Input Data Table (scheduled read) . . . . . . . . . . . . . . . . . . . . . . . . . 145
Output (scheduled write) Data Table . . . . . . . . . . . . . . . . . . . . . . 149
Unscheduled Read Data Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Unscheduled Write Data Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
Configuration Data Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Chapter 7
Troubleshooting Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 172
Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Redundancy. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175
Appendix A
Time Over-current Characteristic
Curves
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Curve Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Time Over-current Characteristic Curve Graphs . . . . . . . . . . . . . . . 178
Time Dial Setting Cross-reference . . . . . . . . . . . . . . . . . . . . . . . . . 179
Voltage Restraint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Appendix B
CGCM-DLR Unit Math Models Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Synchronous Machine Terminal Voltage Transducer and Load
Compensator Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Voltage Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
VAR/Power Factor Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Limiters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
V/Hz Limiter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Soft Start Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Field Current Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Appendix C
Additional EtherNet/IP Network
Information
EtherNet/IP DLR Application Objects . . . . . . . . . . . . . . . . . . . . . . . . 205
Data Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Identity Object (class code 0x01) . . . . . . . . . . . . . . . . . . . . . . . . . . 205
6 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Table of Contents
Assembly Object (class code 0x04) . . . . . . . . . . . . . . . . . . . . . . . . . 208
Appendix D
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Control Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Waste Electrical and Electronic Equipment (WEEE) . . . . . . . . 209
Excitation Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
Generator Voltage Sensing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Generator Current Sensing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Bus Voltage Sensing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Auxiliary Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
Remote Excitation Enable Input . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Open Collector Outputs (fault relay and redundancy relay) . . 212
Field Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Parallel Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Loss of Excitation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213
Over-excitation Voltage Protection . . . . . . . . . . . . . . . . . . . . . . . . 214
Over-current Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Undervoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Overvoltage Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Loss of Sensing Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Loss of PMG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Reverse VAR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Over/Under-frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Reverse Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Rotating Diode Monitor - Range. . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Phase Rotation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Soft Start Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Voltage Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Over-excitation Limiting - Online . . . . . . . . . . . . . . . . . . . . . . . . . 216
Over-excitation Limiting - Offline . . . . . . . . . . . . . . . . . . . . . . . . . 217
Under-excitation Limiting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Manual Excitation Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Metering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Agency Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Schedule of Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Physical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Appendix E
Detailed CGCM-DLR Unit Tag
Descriptions
Generator Parameters and Configuration Status . . . . . . . . . . . . . . . . 221
Inputs to CGCM-DLR Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
Outputs from CGCM Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
General Excitation Control Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 7
Table of Contents
Inputs to CGCM Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Outputs from CGCM-DLR Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 222
AVR Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
AVR Mode Inputs to CGCM-DLR Unit. . . . . . . . . . . . . . . . . . . 223
AVR Mode Outputs from CGCM-DLR Unit . . . . . . . . . . . . . . 224
FCR Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
FCR Mode Inputs to CGCM-DLR Unit. . . . . . . . . . . . . . . . . . . 224
FCR Mode Outputs from CGCM-DLR Unit . . . . . . . . . . . . . . 224
Power Factor Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Inputs to CGCM Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Outputs from CGCM Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
VAR Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Inputs to CGCM Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Outputs from CGCM-DLR Unit. . . . . . . . . . . . . . . . . . . . . . . . . . 226
Excitation Control Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Soft Start Inputs to CGCM-DLR Unit. . . . . . . . . . . . . . . . . . . . . 227
Droop (Reactive Current Compensation) Inputs to
CGCM-DLR Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Under-frequency Limit Inputs to CGCM-DLR Unit. . . . . . . . 227
Cross-current Compensation Inputs to CGCM-DLR Unit . . 227
Over-excitation Limit Inputs to CGCM-DLR Unit . . . . . . . . . 228
Over-excitation Limit Outputs from CGCM Unit . . . . . . . . . . 228
Line-drop Compensation Inputs to CGCM-DLR Unit. . . . . . 229
Under-excitation Limit Inputs to CGCM-DLR Unit . . . . . . . 229
Under-excitation Limit Outputs from CGCM Unit. . . . . . . . . 230
Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
General Protection Inputs to CGCM-DLR Unit. . . . . . . . . . . . 230
General Protection Outputs from CGCM Unit. . . . . . . . . . . . . 230
Loss of Excitation Inputs to CGCM-DLR Unit. . . . . . . . . . . . . 230
Loss of Excitation Outputs from CGCM Unit. . . . . . . . . . . . . . 231
Shorted Excitation Output from CGCM-DLR Unit . . . . . . . . 231
Over-excitation Voltage Inputs to CGCM-DLR Unit . . . . . . . 231
Over-excitation Voltage Outputs from CGCM Unit . . . . . . . . 231
Generator Overvoltage Inputs to CGCM-DLR Unit . . . . . . . . 231
Generator Overvoltage Outputs from CGCM Unit . . . . . . . . . 232
Inputs to CGCM-DLR Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Generator Undervoltage Outputs from CGCM Unit. . . . . . . . 232
Loss of Sensing Inputs to CGCM-DLR Unit . . . . . . . . . . . . . . . 232
Loss of Sensing Outputs from CGCM Unit . . . . . . . . . . . . . . . . 232
Loss of Operating Power Inputs to CGCM-DLR Unit . . . . . . 233
Loss of Operating Power Outputs from CGCM Unit . . . . . . . 233
Reverse VAR Inputs to CGCM-DLR Unit . . . . . . . . . . . . . . . . . 233
Reverse VAR Outputs from CGCM-DLR Unit. . . . . . . . . . . . . 233
Definite Time Over-frequency Inputs to CGCM-DLR Unit. 233
Definite Time Over-frequency Outputs
from CGCM Unit . . 234
Definite Time Under-frequency Inputs to CGCM-DLR Unit 234
Definite Time Under-frequency Outputs from CGCM . . . . . 234
8 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Table of Contents
Reverse Power Protection Inputs to CGCM-DLR Unit . . . . . 234
Reverse Power Protection Outputs from CGCM Unit . . . . . . 235
Rotating Diode Monitor Inputs to CGCM-DLR Unit . . . . . . 235
Rotating Diode Monitor Outputs from CGCM Unit . . . . . . . 235
Phase Rotation Check Inputs to CGCM-DLR Unit. . . . . . . . . 235
Phase Rotation Check Outputs from CGCM-DLR Unit . . . . 236
Generator Over-current Inputs to CGCM-DLR Unit . . . . . . . 236
Generator Over-current Outputs to CGCM Unit. . . . . . . . . . . 236
Synchronizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Synchronizing Inputs to CGCM Unit . . . . . . . . . . . . . . . . . . . . . 237
Synchronizing Outputs from CGCM-DLR Unit . . . . . . . . . . . 238
Load Sharing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240
Load Sharing Inputs to CGCM Unit. . . . . . . . . . . . . . . . . . . . . . . 240
Load Sharing Outputs from CGCM-DLR Unit. . . . . . . . . . . . . 240
Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Metering Inputs to CGCM Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Metering Outputs from CGCM-DLR Unit . . . . . . . . . . . . . . . . 242
Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Redundancy Inputs to CGCM-DLR Unit. . . . . . . . . . . . . . . . . . 244
Redundancy Outputs from CGCM-DLR Unit . . . . . . . . . . . . . 245
Appendix F
Configuration Record Worksheet Generator Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
CGCM-DLR Unit Configuration Settings . . . . . . . . . . . . . . . . . 248
Appendix G
Installing the Add-on Profile Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Download the AOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Perform the Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 9
Preface
The information in this manual applies to the 1407-CGCM-DLR module,
Series D, Revision A or later, with host firmware revision 05.25 or later, and
EtherNet/IP® DLR firmware revision 01.09 or later. The manual notes
differences with earlier versions of the product where they occur.
Download firmware, associated files (such as AOP, DTM, and EDS), and access
product release notes from the Product Compatibility and Download Center at
http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page
.
Summary of Changes
This publication contains new or updated information as indicated in the
following table.
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
You can view or download publications at http://www.rockwellautomation.com/
literature/.
Topic Page
Updated the Summary of Data Tables to indicate the size of the Configuration tag. 139
Added the Waste Electrical and Electronic Equipment (WEEE) statement. 209
Updated the Load Sharing parameters. 217
Added the schedule of limitations. 218
Resource Description
Safety Guidelines for the Application,
Installation, and Maintenance of Solid State
Controls, publication SGI-1.1
Describes some important differences between
solid-state equipment and hard-wired
electromechanical devices.
EtherNet/IP Media Planning and Installation
Manual ODVA Pub. 148 and EtherNet/IP Network
Infrastructure Guidelines ODVA Pub. 35
(1)
(1) For ODVA publications, see the ODVA EtherNet/IP library at
http://odva.org/Home/ODVATECHNOLOGIES/EtherNetIP/EtherNetIPLibrary/tabid/76/lng/en-US/Default.aspx
Provides installation procedures for the
EtherNet/P network.
EtherNet/IP Network Configuration, publication
ENET-UM001
Provides Network configuration procedures for
the EtherNet/IP network.
Logix5000â„¢ Controllers Common Procedures,
publication 1756-PM001
This publication links to a collection of
programming manuals that describe how you can
use procedures that are common to all
Logix5000â„¢ controller projects.
Industrial Automation Wiring and Grounding
Guidelines, publication 1770.4.1
.
Provides general guidelines for installing a
Rockwell Automation
®
industrial system.
Product Certifications website,
rok.auto/certifications
.
Provides declarations of conformity, certificates,
and other certification details.
10 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Preface
Studio 5000 Environment
The Studio 5000® Engineering and Design Environment™ combines engineering
and design elements into a common environment. The first element in the Studio
5000® environment is the Logix Designer application. The Logix Designer
application is the rebranding of RSLogixâ„¢ 5000 software and continues to be the
product to program Logix5000 controllers for discrete, process, batch, motion,
safety, and drive-based solutions.
The Studio 5000 environment is the foundation for the future of Rockwell
Automation® engineering design tools and capabilities. It is the one place for
design engineers to develop all elements of their control system.
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 11
Chapter
1
General Information
Introduction
The Combination Generator Control Module with EtherNet/IP® Device Level
Ring communication (CGCM-DLR unit) is a microprocessor-based control and
protection device. The CGCM-DLR unit is designed to integrate with a Logix
family programmable controller to provide generator control, protection, and
synchronization functions. Programmability of system parameters, regulation
settings, and protective functions enable the CGCM-DLR unit to be used in a
wide range of applications.
Functions
The following sections outline the functions of the unit.
Generator Regulation and Control Functions
This list contains the generator regulation and control functions:
• Four excitation control modes
• Automatic voltage regulation (AVR)
• Manual or field current regulation (FCR)
• Power factor (PF)
• Reactive power (VAR)
• Soft start voltage buildup with an adjustable ramp in AVR and FCR
control modes
• Over-excitation (OEL) and under-excitation (UEL) limiting in AVR,
VAR , and PF control modes
• Under-frequency compensation (Volts/Hertz)
• Line drop compensation
• Auto-tracking between operating modes and between redundant
CGCM-DLR units
• Automatic transfer to a back-up CGCM-DLR unit in redundant systems
• Generator paralleling with reactive droop compensation or cross-current
(reactive differential) compensation
• Generator paralleling with real power load sharing
• Synchronizing for one or two circuit breakers
12 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 1 General Information
Generator Protection Functions
This list contains the generator protection functions:
• Loss of excitation current (40)
• Over-excitation voltage (59F)
• Generator overvoltage (59)
• Generator undervoltage (27)
• Loss of sensing (60FL)
• Loss of permanent magnet generator
(PMG/Excitation power) (27)
• Reverse VAR (40Q)
• Over-frequency (81O)
• Under-frequency (81U)
• Reverse power (32R)
• Rotating diode monitor
• Phase rotation error (47)
• Generator overcurrent (51)
Metering Functions
This list contains the metering functions:
• Vo l t a g e
• Current
• Frequency
• Real Power
• Apparent Power
• Reactive Power
• Power Factor
• Real Energy (kWh)
• Apparent Energy (kVAh)
• Reactive Energy (kVARh)
• Controller Excitation Current and Voltage
• Diode Monitor Ripple Level
• Load Share Error
• Synchronization Parameters
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 13
General Information Chapter 1
Inputs
This list contains the inputs for the CGCM-DLR unit:
• Single-phase or 3-phase true rms generator voltage sensing
• Single-phase dual bus or 3-phase single bus voltage sensing
• 3-phase generator current sensing (1 or 5 A nominal)
• Single-phase cross current loop 1 or 5 A current transformer (CT) input
• Auxiliary ±10V DC input providing remote control of the setpoints
• DC power input
Outputs
This list contains the outputs for the CGCM-DLR unit:
• Pulse-width modulated output power stage that is rated at 15 A
• Discrete redundancy relay output
• Discrete fault output driver
• Load sharing connection for use with the Allen-Bradley® Line
Synchronization Moduleâ„¢ (1402-LSM) or compatible hardware
Communication Interfaces
The CGCM-DLR unit has these three communication ports:
• Redundant EtherNet/IP DLR connector
• RS-232 port for dedicated communication with a redundant CGCM
• RS-232 port for factory configuration and test (not for customer use)
14 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 1 General Information
Notes:
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 15
Chapter
2
Installation
Mounting Requirements
This equipment is intended for use in a Pollution Degree 2 Industrial
Environment, in overvoltage Category II applications (as defined by IEC
publication 60664-1). Because the units contain a heat sink, they must be
mounted vertically. Any other mounting angle reduces the heat dissipation
capabilities of the units, which can lead to premature failure of critical
components. The unit can be mounted anywhere that the ambient temperature
does not exceed the rated environmental conditions or clearance requirements.
The clearance requirements for the CGCM-DLR unit are:
• 63.5 mm (2.5 in.) of clearance is required on both sides of the unit when
mounted.
• 101.6 mm (4 in.) of clearance is required above and below the unit when
mounted.
Overall dimensions for the unit are shown in CGCM-DLR
Unit Overall
Dimensions on page 16.
WARNING: Explosion Hazard
• Substitution of components can impair suitability for Class I, Division 2.
• Do not replace components or disconnect equipment unless power has been switched
off or the area is known to be nonhazardous.
• Do not connect or disconnect components unless power has been switched off or the
area is known to be nonhazardous.
• This product must be installed in an enclosure. All cables that are connected to the
product must remain in the enclosure or be protected by conduit or other means.
• All wiring must comply with N.E.C. article 501-4(b).
16 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 2 Installation
Figure 1 - CGCM-DLR Unit Overall Dimensions
00-87,
89-98
88
RESTORE FACTORY
IP ADDRESS
192.168.1.1XY
99
SELECTED PER DHCP
OR USER ENTERED
247.7
(9.75)
355.6
(14.00)
363
(~14.3)
1/4 - 20 Ground
Stud (2 Places)
7.14 (0.281) DIA
Mounting Hole
(6 Places)
209.6
(8.25)
25.4
(1.00)
152.4
(6.00)
152.4
(6.00)
228.6
(9.00)
9.7
(0.38)
159.0
(6.26)
190.0
(~7.5)
Notes:
1. Weight = 7.7 kg (17 lb)
2. Dimensions are in millimeters (inches)
Ground Studs
DEFAULTS
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 17
Installation Chapter 2
Electrical Connections
The CGCM-DLR unit connections are dependent on the application and
excitation scheme. All inputs or outputs cannot be used in a given installation.
Incorrect wiring can result in damage to the unit.
Connect the CGCM-DLR unit terminals with copper wire rated for a minimum
of 600V. General appliance wire that is rated for minimum temperatures of
105 °C (221
°
F) is acceptable. All wire must be copper. Select circuit conductors
that are based on good design practice.
The wire gauge range that is listed in the Terminal Block Label Description
table
indicates the physical capabilities of the connector.
The CGCM-DLR unit terminals are on the front, bottom, and right panel of the
unit. The nine-pin connector on the bottom of the unit is used for
communication between CGCM-DLR units in a redundant system. Suggested
torque for terminal screws is 1 N•m (9 lb•in).
See pages 19
…36 for typical connection diagrams.
Terminals to be used as landing points for shielded wires are provided on several
terminal strips. Shield terminals with the same name are internally connected
together but are not connected to protective earth or any internal unit circuitry.
Table 1 - Terminal Block Label Description
Terminal Block Wire Gauge
Range
Label Description
TB1
2.6…2.1 mm
2
(10…12 AWG)
PMG A Phase A excitation power supply
PMG B Phase B excitation power supply (three phases only)
PMG C Phase C excitation power supply
SHLD1 Shield 1: landing points are tied together but are not connected internally to protective earth or
other unit circuitry
SHLD1
TB2 SHLD2 Shield 2: landing points are tied together but are not connected internally to protective earth or
other unit circuitry
SHLD2
EXC(-) Excitation output negative
EXC(+) Excitation output positive
18 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 2 Installation
TB3
2.6…2.1 mm
2
(10…12 AWG)
ID(+)1 A 1 A cross-current compensation CT input
ID(+)5 A 5 A cross-current compensation CT input
ID(-) Cross-current compensation CT common input
I3(+)1 A 1 A phase C CT input
I3(+)5 A 5 A phase C CT input
I3(-) Phase C CT common input
I2(+)1 A 1 A phase B CT input
I2(+)5 A 5 A phase B CT input
I2(-) Phase B CT common input
I1(+)1 A 1 A phase A CT input
I1(+)5 A 1 A phase A CT input
I1(-) Phase A CT common input
TB4
1.6…1.0 mm
2
(14…18 AWG)
BAT(+) 24V DC control power input
BAT(-) 24V DC control power return
FLT Open collector fault output
RD RLY Open collector output for redundancy relay
CH GND Chassis ground
TB5 V Gen A Phase A generator voltage input
V Gen B Phase B generator voltage input
V Gen C Phase C generator voltage input
V Gen N Neutral generator voltage input
TB6 V Bus A
Phase A bus voltage input
(1)
V Bus B
Phase B bus voltage input
(1)
V Bus C Phase C bus voltage input
V Bus N Neutral bus voltage input
TB7
1.6…1.0 mm
2
(14…18 AWG)
VREF(+) Remote setpoint adjusts input
VREF(-) Remote setpoint adjusts input return
SHLD3 Shield 3 landing points are tied together but are not connected internally to protective earth or
other unit circuitry
SHLD3
A-COM Analog common
EX-D(+) Excitation enable input
EX-D(-) Excitation enable return
LS(+) Real power load-sharing input
LS(-) Real power load-sharing return
SHLD4 Shield 4 landing point is not connected internally to protective earth or other unit circuitry
(1) When used in a dual breaker configuration, Bus A voltage input is wired from V Bus A to V Bus N and Bus B is wired from V Bus B to V Bus N.
Table 1 - Terminal Block Label Description
Terminal Block Wire Gauge
Range
Label Description
Rockwell Automation Publication 1407-UM002B-EN-P - February 2019 19
Installation Chapter 2
Excitation Power
Excitation power is wired to the PMG terminals, whether connected to the
generator output (Shunt Excited) or to a PMG. Connect shunt excited inputs
with a voltage transformer (VT).
PMG inputs are on TB1 and are labeled PMG A, PMG B, and PMG C, to
illustrate their respective phase relationships. Single-phase excitation power must
be connected to terminals PMG A and PMG C. Twisted, shielded cabling is
required for the PMG inputs.
See these wiring diagrams for more information.
Figure 2 - Excitation Power Connections, 3-phase PMG
Figure 3 - Excitation Power Connections, Single-phase PMG
Figure 4 - Excitation Power Connections, Single-phase Shunt
TB1
PMG A
PMG B
PMG C
SHLD 1
SHLD 1
PMG
TB1
PMG A
PMG B
PMG C
SHLD 1
SHLD 1
PMG
TB1
PMG A
PMG B
PMG C
SHLD 1
SHLD 1
Fuse
G
AC
B
20 Rockwell Automation Publication 1407-UM002B-EN-P - February 2019
Chapter 2 Installation
Figure 5 - Excitation Power Connections, 3-phase Shunt
Figure 6 - Excitation Power Connections, AREP Generator
TB1
PMG A
PMG B
PMG C
SHLD 1
SHLD 1
Fuse
Fuse
G
AC
B
TIP
This diagram is based on a Leroy Somer 300 kW AREP (auxiliary-winding
regulation excitation principle) machine. Details can differ on other
machines.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56
  • Page 57 57
  • Page 58 58
  • Page 59 59
  • Page 60 60
  • Page 61 61
  • Page 62 62
  • Page 63 63
  • Page 64 64
  • Page 65 65
  • Page 66 66
  • Page 67 67
  • Page 68 68
  • Page 69 69
  • Page 70 70
  • Page 71 71
  • Page 72 72
  • Page 73 73
  • Page 74 74
  • Page 75 75
  • Page 76 76
  • Page 77 77
  • Page 78 78
  • Page 79 79
  • Page 80 80
  • Page 81 81
  • Page 82 82
  • Page 83 83
  • Page 84 84
  • Page 85 85
  • Page 86 86
  • Page 87 87
  • Page 88 88
  • Page 89 89
  • Page 90 90
  • Page 91 91
  • Page 92 92
  • Page 93 93
  • Page 94 94
  • Page 95 95
  • Page 96 96
  • Page 97 97
  • Page 98 98
  • Page 99 99
  • Page 100 100
  • Page 101 101
  • Page 102 102
  • Page 103 103
  • Page 104 104
  • Page 105 105
  • Page 106 106
  • Page 107 107
  • Page 108 108
  • Page 109 109
  • Page 110 110
  • Page 111 111
  • Page 112 112
  • Page 113 113
  • Page 114 114
  • Page 115 115
  • Page 116 116
  • Page 117 117
  • Page 118 118
  • Page 119 119
  • Page 120 120
  • Page 121 121
  • Page 122 122
  • Page 123 123
  • Page 124 124
  • Page 125 125
  • Page 126 126
  • Page 127 127
  • Page 128 128
  • Page 129 129
  • Page 130 130
  • Page 131 131
  • Page 132 132
  • Page 133 133
  • Page 134 134
  • Page 135 135
  • Page 136 136
  • Page 137 137
  • Page 138 138
  • Page 139 139
  • Page 140 140
  • Page 141 141
  • Page 142 142
  • Page 143 143
  • Page 144 144
  • Page 145 145
  • Page 146 146
  • Page 147 147
  • Page 148 148
  • Page 149 149
  • Page 150 150
  • Page 151 151
  • Page 152 152
  • Page 153 153
  • Page 154 154
  • Page 155 155
  • Page 156 156
  • Page 157 157
  • Page 158 158
  • Page 159 159
  • Page 160 160
  • Page 161 161
  • Page 162 162
  • Page 163 163
  • Page 164 164
  • Page 165 165
  • Page 166 166
  • Page 167 167
  • Page 168 168
  • Page 169 169
  • Page 170 170
  • Page 171 171
  • Page 172 172
  • Page 173 173
  • Page 174 174
  • Page 175 175
  • Page 176 176
  • Page 177 177
  • Page 178 178
  • Page 179 179
  • Page 180 180
  • Page 181 181
  • Page 182 182
  • Page 183 183
  • Page 184 184
  • Page 185 185
  • Page 186 186
  • Page 187 187
  • Page 188 188
  • Page 189 189
  • Page 190 190
  • Page 191 191
  • Page 192 192
  • Page 193 193
  • Page 194 194
  • Page 195 195
  • Page 196 196
  • Page 197 197
  • Page 198 198
  • Page 199 199
  • Page 200 200
  • Page 201 201
  • Page 202 202
  • Page 203 203
  • Page 204 204
  • Page 205 205
  • Page 206 206
  • Page 207 207
  • Page 208 208
  • Page 209 209
  • Page 210 210
  • Page 211 211
  • Page 212 212
  • Page 213 213
  • Page 214 214
  • Page 215 215
  • Page 216 216
  • Page 217 217
  • Page 218 218
  • Page 219 219
  • Page 220 220
  • Page 221 221
  • Page 222 222
  • Page 223 223
  • Page 224 224
  • Page 225 225
  • Page 226 226
  • Page 227 227
  • Page 228 228
  • Page 229 229
  • Page 230 230
  • Page 231 231
  • Page 232 232
  • Page 233 233
  • Page 234 234
  • Page 235 235
  • Page 236 236
  • Page 237 237
  • Page 238 238
  • Page 239 239
  • Page 240 240
  • Page 241 241
  • Page 242 242
  • Page 243 243
  • Page 244 244
  • Page 245 245
  • Page 246 246
  • Page 247 247
  • Page 248 248
  • Page 249 249
  • Page 250 250
  • Page 251 251
  • Page 252 252
  • Page 253 253
  • Page 254 254
  • Page 255 255
  • Page 256 256
  • Page 257 257
  • Page 258 258
  • Page 259 259
  • Page 260 260
  • Page 261 261
  • Page 262 262
  • Page 263 263
  • Page 264 264
  • Page 265 265
  • Page 266 266
  • Page 267 267
  • Page 268 268

Allen-Bradley 1407-CGCM-DLR User manual

Type
User manual

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI