Froling RBG 3200 Touch Operating Instructions Manual

Type
Operating Instructions Manual
Operating Instructions
Room console RBG 3200 Touch
Translation of the original German operating instructions for the operator
Read and follow the instructions and safety information!
Technical changes, typographical errors and omissions reserved!
B0780115_en | Edition 08/06/2015
Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Table of contents
1 General 4
1.1 About these instructions 4
1.2 Safety information 4
2 Installation 5
2.1 Initial start-up 5
2.1.1 Connecting the bus cable 5
2.1.2 Setting end jumpers 6
2.1.3 Calibrate the display 6
2.1.4 Setting the module address 6
3 Overview of the basic functions 8
3.1 Visual display 8
3.1.1 Status LED 8
3.1.2 Icons 9
4 Operation 10
4.1 Navigation within the info menu 10
4.2 Navigation within the system menu 10
4.2.1 Navigating the menus 10
4.3 Adjusting parameters 12
4.4 Setting times 13
4.5 Setting the room temperature setpoints 15
4.6 Set the heating circuit mode 15
4.6.1 “OFF” mode 16
4.6.2 “Auto” mode 16
4.6.3 “Party” mode 16
4.6.4 “Setback” mode 16
5 Menu overview and parameters 17
5.1 Heating 17
5.1.1 Heating - Status 17
5.1.2 Heating - Temperatures 18
5.1.3 Heating - Times 19
5.2 Water 20
5.2.1 Water - Status 20
5.2.2 Water - Temperatures 21
5.2.3 Water - Times 21
5.3 Solar 22
5.3.1 Solar - Status 22
5.3.2 Solar - Temperatures 24
5.3.3 Solar - Heat meter 25
5.4 Buffer tank 26
5.4.1 Buffer tank - Status 26
5.4.2 Buffer tank - Temperatures 27
5.4.3 Buffer tank - Times 27
5.5 Boiler 2 28
Table of contents
2 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5.5.1 Boiler 2 - Status 28
5.5.2 Boiler 2 - Temperatures 29
5.6 Difference regulator 30
5.6.1 Difference regulator - Status 30
5.7 Circulation pump 31
5.7.1 Circulation pump - Status 31
5.7.2 Circulation pump - Temperatures 31
5.7.3 Circulation pump - Times 31
5.8 System 32
5.8.1 System - Current values 32
5.8.2 System - Display operating rights 33
Froling Connect
33
5.9 Diagnostics 34
5.9.1 Diagnostics - Error display 34
5.10 Display settings 34
5.10.1 Display settings - General 34
Network settings
35
5.10.2 Display settings - Date / Time 35
6 Troubleshooting 36
6.1 Procedure for fault messages 36
7 FAQ 38
7.1 Updating the software of the touch control 38
7.2 Calibrating the touchscreen 40
Table of contents
Operating Instructions RBG 3200 Touch | B0780115_en 3
1 General
1.1 About these instructions
These instructions contain information about the electrical connection, operation,
control parameters and troubleshooting for the RBG 3200 Touch room console. All
parameters, which are visible at the “customer” operator level, are shown. The
parameters actually displayed may vary depending on system configuration and
operating level.
The constant further development of our products means that there may be minor
differences from the pictures and content. If you discover any errors, please let us
Subject to technical change.
Froling's RBG 3200 Touch room console is a multifunctional device for convenient
operation of the boiler from your living room.
1.2 Safety information
DANGER
When working on electrical components:
Risk of electrocution!
When work is carried out on electrical components:
Only have work carried out by a qualified electrician
Observe the applicable standards and regulations
Work must not be carried out on electrical components by unauthorised
persons
1General
About these instructions
4 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
2 Installation
Run the bus cable through the large grommet
Fit the holding frame as shown at the desired position in the room using the
anchors and screws provided
The large grommet must be on the right!
It is recommended to install the device above a flush-mounted socket so that
there is plenty of space to stow away the bus cable.
2.1 Initial start-up
NOTICE
You should have the initial startup carried out by the authorised heating engineer
from Froling customer services.
2.1.1 Connecting the bus cable
For the bus connections between the individual modules, cable type
LIYCY paired 2x2x0.5 should be used. The connection to the 5-pin plugs should be
carried out according to the following diagram:
+UBUS
CANH
CANL
+UBUS
CANH
CANL
Braidedshield
White
Green
Yellow
Brown
Braidedshield
White
Green
Yellow
Brown
Installation 2
Initial start-up
Operating Instructions RBG 3200 Touch | B0780115_en 5
2.1.2 Setting end jumpers
To ensure that the bus system continues to work properly,
the end jumpers (J) need to be set.
If there is an RBG 3200 Touch at the end of a bus
system, the end jumper at this module must be set. All
the previous ones, with the exception of that at the
core module, have to be deleted.
2.1.3 Calibrate the display
Once the power supply has been switched on for the first time, the RBG 3200 Touch
starts by calibrating the display. To calibrate the touchscreen, you much press five
points indicated by a crosshair in the order shown.
NOTICE
Inaccurate calibration
If you do not tap the indicated points accurately, the control may stop working
properly and a software update may be required.
2.1.4 Setting the module address
Once the display has been calibrated, the module address must be set. If it is the first
RBG 3200 Touch in the bus system, set module address 1. Number any others in
sequence.
NOTICE! Do not select an address of 0 as it leads to malfunctions with the RBG 3200
Touch!
2Installation
Initial start-up
6 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
Once you have set the module address, you will need to restart the boiler controller
(switch main switch on boiler off and on). All of the system information will then be
loaded into the RBG 3200 Touch. This process can be time-consuming.
The following screen appears after the RBG 3200 Touch’s first system start:
The basic screen displays only the external temperature as no components have been
assigned to the RBG 3200 Touch yet.
Installation 2
Initial start-up
Operating Instructions RBG 3200 Touch | B0780115_en 7
3 Overview of the basic functions
3.1 Visual display
A
B
F
C
D
G
HI
E
J
K
Number Description
ADate and time display
BShows the current external temperature
CShows the current temperature at the allocated DHW tank. This field is hidden if
no DHW tank has been assigned.
DShows the current room temperature of the allocated heating circuit. This field is
hidden if no heating circuit has been assigned.
EDown arrow to decrease the desired temperature setpoint for the room
FShows the temperature setpoint for the room
GUp arrow to increase the desired temperature setpoint for the room
HInfo menu icon for viewing all system information
ISystem menu icon for opening the system settings All parameters can be
displayed/edited depending on the user level
JFavourites menu icon for viewing the available quick functions
KMode icon for setting the mode of the allocated heating circuit
3.1.1 Status LED
The status LED shows the operating status of the system:
GREEN flashing (interval: 5 sec OFF, 1 sec ON): Off / Boiler off
GREEN constant: BOILER SWITCHED ON
ORANGE flashing: WARNING
RED flashing: FAULT
3Overview of the basic functions
Visual display
8 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
3.1.2 Icons
Home icon
Tapping the Home icon takes you back to the basic display from any menu.
Back icon
Takes you back up one menu level of the system menu. Can be used to return to the
basic display.
Info menu icon
To access all system information. The information is ordered in a circular buffer. The
right and left arrows are used to switch between the individual pages.
System menu icon
Opens the system settings. Depending on the operating level and system
configuration, the various menu items available are organised in a circular buffer
which can be navigated using the right and left arrow.
Quick menu icon
Opens the quick menu. Various functions are available depending on the user level,
system configuration and current status.
Pen icon
If a parameter has the pen symbol beside it, it means that the parameter can be
adjusted. If you open the parameter, either the numeric keypad or a list box for
changing the value of the parameter will appear.
Confirm icon
Confirms any values entered and activates parameters.
Cancel icon
Discards any values entered without saving and closes messages.
An “i” at the top left after selecting a parameter indicates additional information
available for this parameter. Pressing the Cancel icon takes you back to the selected
parameter.
Overview of the basic functions 3
Visual display
Operating Instructions RBG 3200 Touch | B0780115_en 9
4 Operation
4.1 Navigation within the info menu
The info menu displays all the information about the system. Use the right and left
arrows to go to the individual menu items for the relevant information. The next time
you open the info menu, the last page viewed will be displayed.
4.2 Navigation within the system menu
The system menu shows the menu items available depending on the user level and
the system configuration. Tap the icon to open the corresponding menu item. The
system menu is structured in a circular buffer, which can be navigated using the right
and left arrows. The next time you open the system menu, the last page viewed will be
displayed.
4.2.1 Navigating the menus
After you open a menu item, the corresponding status display with current values will
appear. If, for example, several heating circuits are installed, you can use the right and
left arrows to navigate to the desired heating circuit. You can open any other menu
items available in the same way.
4Operation
Navigation within the info menu
10 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
The individual menus are divided into tabs for quicker navigation.
Tap on the desired tab
The list of parameters for the selected area will appear
The parameter list shows three parameters. The up and down arrows can be used to
scroll through longer lists of parameters. If you have reached the start or end of the
parameter list, the relevant arrow symbol will become inactive.
Operation 4
Navigation within the system menu
Operating Instructions RBG 3200 Touch | B0780115_en 11
4.3 Adjusting parameters
A parameter can only be adjusted if there is a pen icon beside it. Depending on the
type of parameter, either the numeric keypad...
... or a list box will appear.
In both cases you need to tap the confirm icon to save the entry.
4Operation
Adjusting parameters
12 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
4.4 Setting times
The desired time window for the component can be set in the "Times" tab in the
individual menus of the heating components (heating circuits, DHW tanks etc.). The
structure of the time menu and the procedure for changing the times are always the
same.
Use the left or right arrow to navigate to the desired day of the week
Tap the symbol under the day of the week
The edit window will appear
You can specify up to four time windows per component and day.
Tap the desired time window
The time window will open for editing
Set the start and end time for the time window using the up and down arrows
Save the time window setting by tapping on the confirm icon
Operation 4
Setting times
Operating Instructions RBG 3200 Touch | B0780115_en 13
To delete a time window, set the times so that the hour and minute displays are
replaced by two dashes.
If you want to apply the time window setting to another day in addition, you can do this
by activating the relevant day.
4Operation
Setting times
14 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
4.5 Setting the room temperature setpoints
The desired room temperature setpoint can be set in the lower left area of the basic
display:
Change the temperature in the room using the up and down arrows
NOTICE! The room temperature can only be changed in automatic mode (when the
heating circuit control is active) and in party mode!
4.6 Set the heating circuit mode
The current mode for the allocated heating circuit is displayed in the basic display to
the left of the mode icon.
Operation 4
Setting the room temperature setpoints
Operating Instructions RBG 3200 Touch | B0780115_en 15
Setting another mode:
Tap the mode icon
Mode-select is displayed
Tap the appropriate icon to change the heating circuit mode
The following modes are available:
4.6.1 “OFF” mode
The allocated heating circuit is switched off, the frost protection function remains
active.
4.6.2 “Auto” mode
The allocated heating circuit and the allocated DHW tank are controlled according to
the timed program settings.
4.6.3 “Party” mode
The allocated heating circuit is set to heating mode until the end of the next heating
phase or until a different mode is activated.
4.6.4 “Setback” mode
The allocated heating circuit is set to setback mode until the start of the next heating
phase or until a different mode is activated. The temperature setpoint displayed in
setback mode on the basic screen is for display purposes only and cannot be
changed. To change this, go to the “Heating” menu → under the “Temperature” tab.
4Operation
Set the heating circuit mode
16 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
5 Menu overview and parameters
5.1 Heating
5.1.1 Heating - Status
System menu Heating
Control heating circuit according to program (NO -> heating circuit is switched off) YES
YES: The heating circuit is operated according to the selected heating times.
NO: Heating circuit is completely switched off, frost protection remains active!
Actual flow temperature 46°C
Shows the current flow temperature.
Flow temperature setpoint 52°C
Shows the calculated flow temperature setpoint.
Room temperature 20°C
Prerequisite: Heating circuit used in conjunction with remote control
Shows the current room temperature.
Override switch Auto
Prerequisite: Heating circuit used in conjunction with remote control
Shows the current heating circuit mode:
Party: party mode; the current or next setback program is ignored
Setback: setback mode; the heating phases are ignored
Auto: automatic mode: heating phases according to the set heating times
Off: switched-off; heating circuit deactivated, only frost protection!
Outside air temperature 2°C
Shows the current external temperature.
Menu overview and parameters 5
Heating
Operating Instructions RBG 3200 Touch | B0780115_en 17
5.1.2 Heating - Temperatures
System menu Heating
Desired room temperature during heating mode 20°C
Prerequisite: Heating circuit used in conjunction with remote control
Room temperature which is regulated during the set heating times
Desired room temperature during setback mode 16°C
Prerequisite: Heating circuit used in conjunction with remote control
Room temperature which is regulated outside of the set heating times
Flow temperature SP at external temperature of +10°C 40°C
First setting point for definition of heating curve
Flow temperature SP at external temperature of -10°C 60°C
Second setting point for definition of heating curve
Reduction of flow temperature in setback mode 15°C
The flow temperature is reduced by this value during setback mode.
External temperature below which the heating circuit pump switches on in heating mode 18°C
If the external temperature exceeds this value during heating, the heating circuit pumps and mixing valve are
deactivated.
5Menu overview and parameters
Heating
18 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
External temperature below which the heating circuit pump switches on in setback mode 7°C
If the external temperature falls below this value in setback mode, the heating circuit pumps and mixing valve
are activated.
Frost protection temperature 10°C
If the room temperature or the flow temperature is lower than the set value, the heating circuit pump will be
switched on and the heating circuit mixer keeps to the maximum heating circuit flow temperature that is set.
5.1.3 Heating - Times
System menu Heating
⇨ See "Setting times" [page 13]
Menu overview and parameters 5
Heating
Operating Instructions RBG 3200 Touch | B0780115_en 19
5.2 Water
5.2.1 Water - Status
System menu Water
DHW tank top temperature 58°C
Current temperature of the DHW tank. The DHW tank is heated when the time window for the DHW tank load‐
ing is reached and the current temperature of the DHW tank has fallen below the value using the parameter
“Reload if DHW tank temperature is below”. A loading of the DHW tank takes place when either
the time window has elapsed or the temperature value which is set under “Set DHW temperature” is
reached.
DHW tank bottom temperature 55°C
Prerequisite: Solar panel system is regulated by Froling!
Current temperature in the area of the reference sensor of the solar panel system.
DHW tank pump control 0%
Specifies the speed of the DHW tank pump as a percentage of maximum speed.
5Menu overview and parameters
Water
20 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41