Ravel RE-717MM is a monitor module designed for intelligent two-wire systems, allowing for the connection of normally open contact fire alarm, supervisory, or other devices. It features individual address selection via DIP switches, providing either 2 or 4 wire fault initiating circuits. The module operates on 24 VDC nominal voltage, has a maximum alarm current of 2.7 mA and a standby current of 0.7 mA. It can withstand temperatures ranging from 0 to 49 degrees Celsius and humidity levels of 10% to 93% non-condensing.

Ravel RE-717MM is a monitor module designed for intelligent two-wire systems, allowing for the connection of normally open contact fire alarm, supervisory, or other devices. It features individual address selection via DIP switches, providing either 2 or 4 wire fault initiating circuits. The module operates on 24 VDC nominal voltage, has a maximum alarm current of 2.7 mA and a standby current of 0.7 mA. It can withstand temperatures ranging from 0 to 49 degrees Celsius and humidity levels of 10% to 93% non-condensing.

+
-
IDC
IDC
IDC
IDC
IDC
INSTALLATION AND MAINTENANCE INSTRUCTIONS
RE-717MM MONITOR MODULE
SPECIFICATION
Operating Voltage : 24 VDC Nominal.
Alarm Current : 2.7 mA Max.(Latched)
Standby Current : 0.7 mA( 47K EOL.)
IDC wiring Resistance : 100 Ohms Max.
IDC Voltage : 8 V Max.
o o .
Temperature Range : 0 C to 49 C
Humidity : 10% to 93% Non - condensing.
Dimensions : 95 mm x 75 mm x 24mm (L x B x H)
Before Installation:
This instruction manual is about quick reference installation guide. For
detailed system information refer the control panel installation manual.
Inform to the operator and authority person that system will be temporarily
out of service, while the module is installed in the existing system.
Note:
Disconnect the power to the control panel before installing the module.
General Instruction:
This monitor module is intended for the use in intelligent two wire system.
The individual address of the each module is selected by using the DIP
Switch. This module provides 2 or 4 wire fault initiating circuit for normally
open contact fire alarm, supervisory, or other devices.
Compatibility Requirement:
This monitor module should be connected to listed compatible control
panel only.
NOTE:
All wiring should be conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Wire should be stripped to the appropriate length. Exposed conductor
should be secured under the clamping plate and should not protrude
beyond the terminal block area.
Caution: Do not loop wire under terminals.
Doc.: No.:RE/IIM/AMM V 1.0
Wiring Configuration for IDC Wiring (Class B,Style B)
From Panel or
Previous Device
SIGNAL LINE
CIRCUIT (SLC)
28 VDC MAX.
+
-
To Next
Device
+
-
Use only Listed
Compatible Panel
47K EOL
Resistor
RE-47K
* D = NO CONNECTION
* ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
NOTE:
RAVEL ELECTRONICS PVT LTD.,
150A, ELECTRONICS INDUSTRIAL ESTATE, PERUNGUDI, CHENNAI - 96 .INDIA.
Ph.: +91-44-2496 1004 / 0825. Fax: +91-44-4204 9599.
E-Mail: [email protected]; www.ravelfirepanels.com
Address Selection Chart
Doc.: No.:RE/IIM/AMM V 1.0
  • Page 1 1
  • Page 2 2

Ravel RE-717MM Installation And Maintenance Instructions

Category
Fire protection
Type
Installation And Maintenance Instructions

Ravel RE-717MM is a monitor module designed for intelligent two-wire systems, allowing for the connection of normally open contact fire alarm, supervisory, or other devices. It features individual address selection via DIP switches, providing either 2 or 4 wire fault initiating circuits. The module operates on 24 VDC nominal voltage, has a maximum alarm current of 2.7 mA and a standby current of 0.7 mA. It can withstand temperatures ranging from 0 to 49 degrees Celsius and humidity levels of 10% to 93% non-condensing.

Ask a question and I''ll find the answer in the document

Finding information in a document is now easier with AI